| Complementary |
| Network type | AC |
| Network frequency | 50/60 Hz |
| [Ue] rated operational voltage | 200...440 V AC 50/60 Hz conforming to IEC 60947-2 |
| Earth-leakage protection | Without |
| Maximum breaking time | 800 ms |
| Overvoltage category | IV |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Electrical shock protection class | Class II |
| Standards | IEC 60947-2 |
| Logistical informations |
| Country of origin | IT |
| Main |
| Range of product | ComPacT NSX400...630; ComPact NSX400...630 |
| Device short name | VigiPacT |
| Product or component type | Vigi add-on |
| Device application | Wiring |
| Range compatibility | ComPacT ComPacT NSX400 circuit breaker; ComPacT ComPacT NSX630 circuit breaker; ComPact ComPact NSX400 circuit breaker; ComPact ComPact NSX630 circuit breaker |
| Poles description | 4P |
| [In] rated current | 400 A; 630 A |
| Earth-leakage protection class | Class A; Class AC |
| Residual earth-leakage sensitity adjustment type | Adjustable |
| Earth-leakage sensitivity | 0.03 A for class A; 0.1 A for class A; 0.3 A for class A; 0.5 A for class A; 1 A for class A; 3 A for class A; 10 A for class AC; 30 A for class AC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.0 cm |
| Package 1 Width | 17.0 cm |
| Package 1 Length | 19.8 cm |
| Package 1 Weight | 3.32 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 30.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 13.754 kg |
This is a Vigi add-on module for ComPact NSX 400/630 that provides a residual current alarm. It is used for 4-pole circuit breakers. The operating voltage is between 200 and 440 VAC 50/60 Hz. The differential current sensitivity is adjustable from 30 mA to 30 A. It is installed directly on the device connection terminals and gives an alarm without tripping in the event of a fault due to residual current. This Vigi add-on module is internally powered by the voltage of the distribution network, even if it is only powered by 2 phases. It is compliant with the IEC 60947-2 standard, Annex B.