Further information for Schneider Electric LUCB1XBL Contactor 3p 24 VDC
Complementary
Control circuit voltage limits
20...27 V for DC circuit 24 V in operation; 14.5 V for DC circuit 24 V drop-out
Typical current consumption
130 mA at 24 V DC I maximum while closing with LUB12; 220 mA at 24 V DC I maximum while closing with LUB32; 220 mA at 24 V DC I maximum while closing with LUB38; 60 mA at 24 V DC I rms sealed with LUB12; 80 mA at 24 V DC I rms sealed with LUB32; 80 mA at 24 V DC I rms sealed with LUB38
Heat dissipation
2 W for control circuit with LUB12; 3 W for control circuit with LUB32; 3 W for control circuit with LUB38
Operating time
35 ms opening with LUB12 for control circuit; 35 ms opening with LUB32 for control circuit; 35 ms opening with LUB38 for control circuit; 70 ms closing with LUB12 for control circuit; 70 ms closing with LUB32 for control circuit; 70 ms closing with LUB38 for control circuit
Reset
Manual reset
Standards
EN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
Product certifications
CE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
[Ui] rated insulation voltage
690 V conforming to IEC 60947-6-2; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-6-2
Safe separation of circuit
400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1; 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Fixing mode
Plug-in (front face)
Width
45 mm
Height
66 mm
Depth
60 mm
Compatibility code
LUCB
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 front panel and wired terminals conforming to IEC 60947-1; IP20 other faces conforming to IEC 60947-1; IP40 front panel outside connection zone conforming to IEC 60947-1
Protective treatment
TH conforming to IEC 60068
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Operating altitude
2000 m
Fire resistance
960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Shock resistance
10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance
2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6; 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
Resistance to electrostatic discharge
8 kV level 3 in open air conforming to IEC 61000-4-2; 8 kV level 4 on contact conforming to IEC 61000-4-2
Resistance to radiated fields
10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients
2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields
10 V conforming to IEC 61000-4-6
Immunity to microbreaks
3 ms
Immunity to voltage dips
70 % / 500 ms conforming to IEC 61000-4-11
Logistical informations
Country of origin
FR
Main
Range
TeSys
Range of product
TeSys Ultra
Product name
TeSys Ultra
Device short name
LUCB
Product or component type
Advanced control unit
Device application
Motor control; Motor protection
Product specific application
Basic protection and advanced functions, communication
main function available
Earth fault protection; Protection against phase failure and phase imbalance; Protection against overload and short-circuit; Manual reset
Product compatibility
Power base LUB12; Power base LUB32; Power base LUB38; Power base LUB120; Power base LUB320; Power base LUB380; Reversing contactor breaker LU2B12BL; Reversing contactor breaker LU2B32BL; Reversing contactor breaker LU2B38BL
[Ue] rated operational voltage
690 V AC
Network frequency
40...60 Hz
Load type
3-phase motor - cooling: self-cooled
Utilisation category
AC-43; AC-44; AC-41
Motor power kW
0.25 kW at 400...440 V AC 50/60 Hz
rated motor current adjustment range
0.35…1.4 A
Thermal overload class
Class 10 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to IEC 60947-6-2; Class 10 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to UL 508
Tripping threshold
14.2 x Ir +/- 20 %
[Uc] control circuit voltage
24 V DC
Phase failure sensitivity
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
5.2 cm
Package 1 Width
8.2 cm
Package 1 Length
8.8 cm
Package 1 Weight
119.0 g
Unit Type of Package 2
S02
Number of Units in Package 2
23
Package 2 Height
15.0 cm
Package 2 Width
30.0 cm
Package 2 Length
40.0 cm
Package 2 Weight
3.03 kg
The control unit LUCB1XBL from Schneider Electric belongs to the TeSys series and is designed as an extended control unit for motor control and motor protection functions. It is used within the TeSys Ultra series and serves as a modular add-on device for base units such as Power base LUB12, LUB32, LUB38, LUB120, LUB320, LUB380, as well as for the reversing contactor breaker models LU2B12BL, LU2B32BL, and LU2B38BL. The unit is plug-in and mounted on the front of the base unit, enabling flexible and quick integration into existing control systems.
Applications
The control unit is designed for controlling and protecting three-phase motors, particularly in applications with self-cooling. It is suitable for usage categories AC-41, AC-43, and AC-44, which are typical for drives with high starting and braking operations. The maximum motor power is 0.25 kW at an operating voltage of 400–440 V AC and a frequency of 50/60 Hz. The unit is designed for operating altitudes up to 2,000 m above sea level and can be operated in ambient temperatures from -25 °C to 70 °C.
Functions and Equipment in Detail
The LUCB1XBL offers an extended protection range, including overload and short-circuit protection, protection against phase failure and phase imbalance, as well as earth fault protection. The tripping class is 10, corresponding to a slowly increasing tripping characteristic, suitable for motors with high starting currents. The adjustment range for the rated motor current is between 0.35 A and 1.4 A. The tripping threshold is 14.2 times the set rated current (Ir) with a tolerance of ±20 %. Resetting is manual, enabling a secure and controlled reactivation after a tripping event.
Technology Explained Simply
The control unit operates with a control voltage of 24 V DC. The permissible voltage limits are 20–27 V DC during operation and 14.5 V DC at drop-out. Power consumption varies depending on the connected base unit: for LUB12, it is up to 130 mA and effectively 60 mA in sealed condition; for LUB32 and LUB38, it is up to 220 mA and effectively 80 mA. Heat dissipation is 2 W for LUB12 and 3 W for LUB32 and LUB38. The response time is 35 ms for opening and 70 ms for closing, regardless of the connected base unit. The unit is designed for an operating voltage of 690 V AC and complies with standards IEC 60947-6-2, EN 60947-6-2, UL 60947-4-1, and CSA C22.2 No. 60947-4-1. The rated insulation voltage is 690 V (IEC) or 600 V (UL/CSA), with an impulse voltage withstand of 6 kV. A safe circuit separation of 400 V SELV is ensured between control and auxiliary circuits, as well as between control or auxiliary circuits and main circuits.
Compatibility and Accessories
The control unit is compatible with the specified base units of the TeSys U series. Available accessories include various auxiliary switch modules (e.g. LUFN20, LUA1C20), FU modules (e.g. LUFDH11, LUFDA10), communication modules (e.g. LUFP7, LULC08), and display modules (e.g. LUFV2). These can be used to extend functionality, such as displaying motor load or integrating into fieldbus systems.
Mounting and Installation
Mounting is plug-in on the front of the base unit. The protection rating is IP20 on the front plate and on wired terminals, and IP40 on the front plate outside the connection zone. The coating corresponds to class TH according to IEC 60068. The unit is shock-resistant (10 Gn with open, 15 Gn with closed current poles) and vibration-resistant (2 Gn with open, 4 Gn with closed current poles) according to IEC 60068. Fire resistance is 960 °C for parts used to mount current-carrying components and 650 °C for other parts.
Advantages in Operation
The modular design allows flexible adaptation to different requirements. Integrated protection functions increase motor safety and lifespan. Manual reset ensures controlled reactivation. Compliance with international standards and certifications (CE, UL, CSA, CCC, EAC, ASEFA, ATEX, Marine) ensures suitability for use in various industries and regions. The control unit is designed for industrial environments with high demands on reliability and safety.