Further information for Schneider Electric LUCAX6BL contactor 3p 24 VDC
Complementary
Control circuit voltage limits
20...27 V for DC circuit 24 V in operation; 14.5 V for DC circuit 24 V drop-out
Typical current consumption
130 mA at 24 V DC I maximum while closing with LUB12; 220 mA at 24 V DC I maximum while closing with LUB32; 220 mA at 24 V DC I maximum while closing with LUB38; 60 mA at 24 V DC I rms sealed with LUB12; 80 mA at 24 V DC I rms sealed with LUB32; 80 mA at 24 V DC I rms sealed with LUB38
Heat dissipation
2 W for control circuit with LUB12; 3 W for control circuit with LUB32; 3 W for control circuit with LUB38
Operating time
35 ms opening with LUB12 for control circuit; 35 ms opening with LUB32 for control circuit; 35 ms opening with LUB38 for control circuit; 70 ms closing with LUB12 for control circuit; 70 ms closing with LUB32 for control circuit; 70 ms closing with LUB38 for control circuit
Standards
EN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase barrier; CSA C22.2 No 60947-4-1, with phase barrier
Product certifications
CE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
[Ui] rated insulation voltage
690 V conforming to IEC 60947-6-2; 600 V conforming to UL 60947-4-1; 600 V conforming to CSA C22.2 No 60947-4-1
[Uimp] rated impulse withstand voltage
6 kV conforming to IEC 60947-6-2
Safe separation of circuit
400 V SELV between the control and auxiliary circuits conforming to IEC 60947-1; 400 V SELV between the control or auxiliary circuit and the main circuit conforming to IEC 60947-1
Fixing mode
Plug-in (front face)
Width
45 mm
Height
66 mm
Depth
60 mm
Net weight
0.135 kg
Compatibility code
LUCA
Contractual warranty
Warranty (in months)
18
Environment
IP degree of protection
IP20 front panel and wired terminals conforming to IEC 60947-1; IP20 other faces conforming to IEC 60947-1; IP40 front panel outside connection zone conforming to IEC 60947-1
Protective treatment
TH conforming to IEC 60068
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-40…85 °C
Operating altitude
2000 m
Fire resistance
960 °C parts supporting live components conforming to IEC 60695-2-12; 650 °C conforming to IEC 60695-2-12
Shock resistance
10 gn power poles open conforming to IEC 60068-2-27; 15 gn power poles closed conforming to IEC 60068-2-27
Vibration resistance
2 gn, 5…300 Hz, power poles open conforming to IEC 60068-2-6; 4 gn, 5…300 Hz, power poles closed conforming to IEC 60068-2-6
Resistance to electrostatic discharge
8 kV level 3 in open air conforming to IEC 61000-4-2; 8 kV level 4 on contact conforming to IEC 61000-4-2
Resistance to radiated fields
10 V/m 3 conforming to IEC 61000-4-3
Resistance to fast transients
2 kV class 3 serial link conforming to IEC 61000-4-4; 4 kV class 4 all circuits except for serial link conforming to IEC 61000-4-4
Immunity to radioelectric fields
10 V conforming to IEC 61000-4-6
Immunity to microbreaks
3 ms
Immunity to voltage dips
70 % / 500 ms conforming to IEC 61000-4-11
Logistical informations
Country of origin
FR
Main
Range
TeSys
Range of product
TeSys Ultra
Product name
TeSys Ultra
Device short name
LUCA
Product or component type
Standard control unit
Device application
Motor control; Motor protection
Product specific application
Basic protection requirements for motor starters: overload and short-circuit
main function available
Earth fault protection; Protection against overload and short-circuit; Protection against phase failure and phase imbalance; Manual reset
Product compatibility
Power base LUB12; Power base LUB32; Power base LUB38; Power base LUB120; Power base LUB320; Power base LUB380; Reversing contactor breaker LU2B12BL; Reversing contactor breaker LU2B32BL; Reversing contactor breaker LU2B38BL
[Ue] rated operational voltage
690 V AC
Network frequency
40...60 Hz
Load type
3-phase motor - cooling: self-cooled
Utilisation category
AC-43; AC-44; AC-41
Motor power kW
0.09 kW at 400...440 V AC 50/60 Hz
rated motor current adjustment range
0.15…0.6 A
Thermal overload class
Class 10 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to IEC 60947-6-2; Class 10 - frequency limit: 40…60 Hz - temperature compensation: -25…70 °C conforming to UL 508
Tripping threshold
14.2 x Ir +/- 20 %
[Uc] control circuit voltage
24 V DC
Phase failure sensitivity
Packing Units
Unit Type of Package 1
PCE
Number of Units in Package 1
1
Package 1 Height
8.500 cm
Package 1 Width
8.000 cm
Package 1 Length
5.000 cm
Package 1 Weight
119.000 g
Unit Type of Package 2
S02
Number of Units in Package 2
23
Package 2 Height
15.000 cm
Package 2 Width
30.000 cm
Package 2 Length
40.000 cm
Package 2 Weight
3.002 kg
The standard control unit LUCA from the TeSys Ultra series by Schneider Electric is a modular component for motor control and protection applications. It serves as a control unit for three-phase motors and is used in combination with suitable base units to ensure overload and short-circuit protection, as well as protection against phase loss and phase imbalance. The unit is designed for operating voltages up to 690 V AC and frequencies between 40 and 60 Hz, and supports load types such as self-cooled three-phase motors. The control unit is specifically designed for usage categories AC-41, AC-43, and AC-44, which are typical for applications with high requirements for switching frequency and load conditions.
Applications
The LUCA control unit is designed for industrial applications where reliable motor control and protection functions are required. It is commonly used in systems with three-phase motors, particularly in areas such as conveyor technology, pump control, fan systems, or machine building. The unit is designed for motor powers up to 0.09 kW at 400–440 V AC and 50/60 Hz. The integrated manual reset function enables easy reactivation after tripping events. The protection functions include overload and short-circuit protection, earth fault protection, as well as protection against phase loss and phase imbalance, which increases the reliability of the system.
Functions and Equipment in Detail
The control unit offers an adjustable rated current range of 0.15 to 0.6 A, allowing flexible adaptation to different motor powers. The tripping class is 10, which defines a standardized response time for overload according to IEC 60947-6-2 and UL 508. The tripping threshold is set at 14.2 times the set rated current (Ir) with a tolerance of ±20 %, ensuring precise protection. Phase loss sensitivity is activated, so that a shutdown occurs in case of phase failure. The unit is designed for an operating voltage of 24 V DC, with an operating voltage range between 20 and 27 V DC and a drop-out value set at 14.5 V DC.
Technology Explained Simply
The LUCA control unit is designed as a plug-in module mounted on the front side of TeSys U base units. The mounting is done via a plug mechanism, enabling quick installation and replaceability. The electrical insulation is rated for 690 V (IEC 60947-6-2) or 600 V (UL 60947-4-1, CSA C22.2 No. 60947-4-1), ensuring high safety at high voltages. The impulse voltage withstand is 6 kV, protecting the unit against transient voltage surges. The safe circuit separation between control and main circuit is 400 V SELV, providing high electrical safety according to IEC 60947-1. The unit is designed for operating temperatures from -25 to 70 °C and can be used up to an operating altitude of 2,000 m. The coating corresponds to category TH according to IEC 60068, ensuring high resistance to environmental influences such as humidity and temperature fluctuations.
Compatibility and Accessories
The LUCA control unit is compatible with various base units from the TeSys U series, including Power bases LUB12, LUB32, LUB38, LUB120, LUB320, and LUB380, as well as reversing combinations LU2B12BL, LU2B32BL, and LU2B38BL. The unit can be extended with auxiliary switch modules such as LUA1C20, LUFN02, LUA1C11, LUFN20, LUFN11, or LUA8E20 to realize additional switching functions such as signal inputs or outputs. The combination with base units allows integration into existing control panels without additional mounting effort.
Mounting and Installation
Mounting is done by plugging the unit into the designated slots of the base units. The unit is designed for front mounting and requires no additional fastening elements. The connection terminals are designed for wiring with screw terminals. The degree of protection is IP20 on the front plate and wired terminals, and IP40 on the front plate outside the connection zone, providing protection against contact and limited protection against solid objects. The unit is intended for use in enclosed control panels.
Advantages in Operation
The LUCA control unit offers high reliability through integrated protection functions and precise adjustability of the rated current. The plug-in design enables quick installation and maintenance. The high thermal load capacity and robust construction ensure a long service life even under industrial operating conditions. Certifications according to EN 60947-6-2, IEC 60947-6-2, UL 60947-4-1, and CSA C22.2 No. 60947-4-1, as well as approvals CE, UL, CSA, CCC, EAC, ASEFA, ATEX, and Marine, guarantee compliance with international safety and quality standards. The unit is suitable for use in various industries, including shipping (Marine approval) and explosive environments (ATEX).