Further information for Schneider Electric LUCA18BL Contactor 3p 24VDC
Additional features
Control circuit voltage limits
20 - 27 V for DC circuit 24 V in operation; 14.5 V for DC circuit 24 V drop
Typical power consumption
220 mA at 24 V DC I max. during closing with LUB32; 220 mA at 24 V DC I max. during closing with LUB38; 80 mA at 24 V DC I eff. sealed with LUB32; 80 mA at 24 V DC I eff. sealed with LUB38
Heat dissipation
3 W for control circuit with LUB32; 3 W for control circuit with LUB38
Response time
35 ms opening with LUB32 for control circuit; 35 ms opening with LUB38 for control circuit; 70 ms closing with LUB32 for control circuit; 70 ms closing with LUB38 for control circuit
Standards
EN 60947-6-2; IEC 60947-6-2; UL 60947-4-1, with phase separator; CSA C22.2 No. 60947-4-1, with phase separator
Product certifications
CE; UL; CSA; CCC; EAC; ASEFA; ATEX; Marine
[Ui] Rated insulation voltage
690 V corresponds to IEC 60947-6-2; 600 V corresponds to UL 60947-4-1; 600 V corresponds to CSA C22.2 No. 60947-4-1
[Uimp] Rated impulse voltage withstand
6 kV complies with IEC 60947-6-2
Safe circuit disconnection
400 V SELV between control and auxiliary circuits, corresponds to IEC 60947-1; 400 V SELV between control or auxiliary circuit and main circuit, corresponds to IEC 60947-1
Mounting mode
pluggable (front)
Width
45 mm
Height
66 mm
Depth
60 mm
Product weight
0,135 kg
Compatibility code
LUCA
Contractual warranty
Warranty (in months)
18
Main features
Product series
TeSys
Product name
TeSys Ultra
Device short name
LUCA
Product or component type
Standard control unit
Device application
Motor control; Motor protection
Product-specific application
Requirements for basic protection of motor outputs: overload and short-circuit
Function available
Manual reset; protection against phase failure and phase imbalance; overload and short-circuit protection; earth fault protection
Product compatibility
Power base LUB32; Power base LUB38; Power base LUB320; Power base LUB380; Reversing contactor breaker LU2B32BL; Reversing contactor breaker LU2B38BL
Operating rated voltage Ue
690 V AC
Network frequency
40 - 60 Hz
Load type
Three-phase motor - cooling: self-cooled
Application category
AC-41; AC-44; AC-43
Motor power (kW)
7.5 kW at 400-440 V AC 50/60 Hz; 9 kW at 500 V AC 50/60 Hz; 15 kW at 690 V AC 50/60 Hz
Rated motor current adjustment range
4,5…18 A
Overload trip class
Class 10 - frequency range: 40…60 Hz - temperature compensation: -25…70 °C complies with IEC 60947-6-2; Class 10 - frequency range: 40…60 Hz - temperature compensation: -25…70 °C complies with UL 508
Trigger threshold
14,2 x Ir ± 20 %
Rated operating voltages [Uc]
24 V DC
Phase loss sensitivity
Mounting
Degree of protection (IP)
IP20 front plate and wired terminals complies with IEC 60947-1; IP20 other sides complies with IEC 60947-1; IP40 front plate outside connection zone complies with IEC 60947-1
Coating
TH corresponds to IEC 60068
Operating ambient temperature
-25…70 °C
Ambient temperature during storage
-40…85 °C
Operating altitude
2.000 m
Fire resistance
960 °C parts for mounting current-carrying components complies with IEC 60695-2-12; 650 °C complies with IEC 60695-2-12
Shock resistance
10 Gn current poles open corresponds to IEC 60068-2-27; 15 Gn current poles closed corresponds to IEC 60068-2-27
Vibration resistance
2 Gn, 5…300 Hz, current poles open corresponds to IEC 60068-2-6; 4 Gn, 5…300 Hz, current poles closed corresponds to IEC 60068-2-6
Resistance to electrostatic discharge
8 kV Level 3 outdoors, complies with IEC 61000-4-2; 8 kV Level 4 contact, complies with IEC 61000-4-2
Order if radiation fields
10 V/m 3 corresponds to IEC 61000-4-3
Resistance to short-duration disturbances
2 kV Class 3 serial line conforms to IEC 61000-4-4; 4 kV Class 4 all circuits except serial connection conforms to IEC 61000-4-4
Immunity to HF fields
10 V corresponds to IEC 61000-4-6
Immunity to short-term dips
3 ms
Immunity to voltage dips
70 % / 500 ms corresponds to IEC 61000-4-11
Packaging units
VPE 1 type
PCE
Number of devices per package
1
VPE 1 height
5,200 cm
VPE 1 width
8,100 cm
VPE 1 length
8,500 cm
Packaging weight (Lbs)
122,000 g
VPE 2 type
S02
VPE 2 quantity
23
VPE 2 height
15,000 cm
VPE 2 width
30,000 cm
VPE 2 length
40,000 cm
VPE 2 weight
3,057 kg
TeSys U - control units. Standard control unit LUCA. Setting range 4.5-18 A, control voltage 24 V DC. Plug-in control units. Trip class 10, for TeSys U basic units.