Schneider Electric LRD3806, EAN: 3606481312006

Schneider Electric LRD3806 motor protection relay 62-80 A

Industrial Material > Industrial relays and contactors > Switching units / measuring, control relay

Schneider Electric LRD3806 motor protection relay 62-80 A

Lieske Part No. 1861760
Mfg Part No LRD3806
EAN-Code 3606481312006
Manufacturer Schneider Electric
Here only 214,70 EUR
255,49 EUR incl. VAT

Further information for Schneider Electric LRD3806 motor protection relay 62-80 A

Additional features
Network frequency0 - 400 Hz
Mounting bracketPlate, with terminal block LAD96560 on top; Rail, with terminal block LAD96560 on top; Direct mounting under contactor
Trigger threshold1.14 +/- 0.06 Ir corresponds to IEC 60947-4-1
Configuration of auxiliary contacts1 S + 1 Ö
[Ith] conventional thermal current in free air5 A for signal circuits
Permissible current0.95 A at 380 V AC-15 for signal circuit; 0.06 A at 440 V DC-13 for signal circuit
[Ue] Rated operational voltage690 V AC 0 - 400 Hz for circuit in accordance with IEC 60947-4-1
Associated fuse4 A gG for signal circuit; 4 A BS for signal circuit
[Uimp] Rated impulse voltage withstand6 kV
Power dissipation per pole4,8 W
Phase loss sensitivityTrip current 130 % of Ir on two phases, the last at 0
Control typeRed push-button: Stop; Blue push-button: Reset
Temperature compensation-20…60 °C
Terminal pitch17,5 mm
Connections - terminalsControl circuit: screw terminals 2 cable(s) 1…2.5 mm² flexible with cable end; control circuit: screw terminals 2 cable(s) 1…2.5 mm² solid; power circuit: ring cable lugs outer diameter: 16.5 mm; power circuit: rails 6 x 13.5 mm; control circuit: screw terminals 2 cable(s) 1…2.5 mm² flexible; power circuit: direct terminal connection on top
Tightening momentControl circuit: 1.7 Nm - on screw terminals; Power circuit: 6 Nm - on ring cable lugs M6; Power circuit: 6 Nm - on rails M6
Height70 mm
Width55 mm
Depth123 mm
Product weight0,375 kg
Contractual warranty
Warranty (in months)18
Main features
Product seriesTeSys; TeSys Deca
Product nameTeSys LRD; TeSys Deca
Product or component typethermal overload relay with differential protection
Device short nameLRD
Device applicationMotor protection
Product compatibilityLC1D80A
Type of networkAC; DC
Thermal trip classClass 10 A according to IEC 60947-4-1
Adjustable range for thermal protection62…80 A
[Ui] Rated insulation voltageCircuit: 690 V corresponds to IEC 60947-4-1; Circuit: 600 V corresponds to UL 60947-4-1; Circuit: 600 V corresponds to CSA C22.2 No. 14
Mounting
Climate resistancecomplies with IACS E10
Degree of protection (IP)IP20 complies with IEC 60529
Operating ambient temperature-20…60 °C without power derating, complies with IEC 60947-4-1
Ambient temperature during storage-60…70 °C
Flame retardancyV1 corresponds to UL 94
Mechanical robustnessShocks: 15 Gn for 11 ms corresponds to IEC 60068-2-7; Vibrations: 3 Gn corresponds to IEC 60068-2-6
Dielectric strength1.89 kV at 50 Hz corresponds to IEC 60947-1
StandardsEN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No. 60947-4-1; CSA C22.2 No. 60947-5-1; GB/T 14048.4; GB/T 14048.5
Product certificationsIEC; UL; CSA; CCC; EAC; DNV-GL; RMRS; EU-RO MR; UKCA
Packaging units
VPE 1 typePCE
Number of devices per package1
VPE 1 height6,250 cm
VPE 1 width11,000 cm
VPE 1 length14,000 cm
Packaging weight (Lbs)362,000 g
VPE 2 typeS02
VPE 2 quantity12
VPE 2 height15,000 cm
VPE 2 width30,000 cm
VPE 2 length40,000 cm
VPE 2 weight4,594 kg
VPE 3 typeP06
VPE 3 quantity192
VPE 3 height75,000 cm
VPE 3 width60,000 cm
VPE 3 length80,000 cm
VPE 3 weight81,504 kg
Motor protection relay - Thermal overload relay with differential protection - TeSys LRD. 3-phase, rated current 62 - 80A, class 10A for a motor power of up to 45kW at 400V. Compliant with ATEX D 94/9/CE, EN/IEC 60947-4-1, EN/IEC 60947-5-1, CSA C22.2 No 14, UL 60947-4-1 and certified according to ATEX INERIS, CCC, EAC. Features such as captive cable lug connection, optimized width of only 55mm and manual - automatic reset. For the highest requirements in the area of overload protection. Can be used for motors of all energy efficiency classes IE0 - IE4 up to 14 times the rated current. In combination with TeSys D they become an extremely compact starter.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1861760
qrcode für Schneider Electric LRD3806 motor protection relay 62-80 A