| Additional features |
| Network frequency | 0 - 400 Hz |
| Mounting bracket | Plate, with terminal block LAD96560 on top; Rail, with terminal block LAD96560 on top; Direct mounting under contactor |
| Trigger threshold | 1.14 +/- 0.06 Ir corresponds to IEC 60947-4-1 |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| [Ith] conventional thermal current in free air | 5 A for signal circuits |
| Permissible current | 0.95 A at 380 V AC-15 for signal circuit; 0.06 A at 440 V DC-13 for signal circuit |
| [Ue] Rated operational voltage | 690 V AC 0 - 400 Hz for circuit in accordance with IEC 60947-4-1 |
| Associated fuse | 4 A gG for signal circuit; 4 A BS for signal circuit |
| [Uimp] Rated impulse voltage withstand | 6 kV |
| Power dissipation per pole | 4,8 W |
| Phase loss sensitivity | Trip current 130 % of Ir on two phases, the last at 0 |
| Control type | Red push-button: Stop; Blue push-button: Reset |
| Temperature compensation | -20…60 °C |
| Terminal pitch | 17,5 mm |
| Connections - terminals | Control circuit: screw terminals 2 cable(s) 1…2.5 mm² flexible with cable end; control circuit: screw terminals 2 cable(s) 1…2.5 mm² solid; power circuit: ring cable lugs outer diameter: 16.5 mm; power circuit: rails 6 x 13.5 mm; control circuit: screw terminals 2 cable(s) 1…2.5 mm² flexible; power circuit: direct terminal connection on top |
| Tightening moment | Control circuit: 1.7 Nm - on screw terminals; Power circuit: 6 Nm - on ring cable lugs M6; Power circuit: 6 Nm - on rails M6 |
| Height | 70 mm |
| Width | 55 mm |
| Depth | 123 mm |
| Product weight | 0,375 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys; TeSys Deca |
| Product name | TeSys LRD; TeSys Deca |
| Product or component type | thermal overload relay with differential protection |
| Device short name | LRD |
| Device application | Motor protection |
| Product compatibility | LC1D80A |
| Type of network | AC; DC |
| Thermal trip class | Class 10 A according to IEC 60947-4-1 |
| Adjustable range for thermal protection | 62…80 A |
| [Ui] Rated insulation voltage | Circuit: 690 V corresponds to IEC 60947-4-1; Circuit: 600 V corresponds to UL 60947-4-1; Circuit: 600 V corresponds to CSA C22.2 No. 14 |
| Mounting |
| Climate resistance | complies with IACS E10 |
| Degree of protection (IP) | IP20 complies with IEC 60529 |
| Operating ambient temperature | -20…60 °C without power derating, complies with IEC 60947-4-1 |
| Ambient temperature during storage | -60…70 °C |
| Flame retardancy | V1 corresponds to UL 94 |
| Mechanical robustness | Shocks: 15 Gn for 11 ms corresponds to IEC 60068-2-7; Vibrations: 3 Gn corresponds to IEC 60068-2-6 |
| Dielectric strength | 1.89 kV at 50 Hz corresponds to IEC 60947-1 |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No. 60947-4-1; CSA C22.2 No. 60947-5-1; GB/T 14048.4; GB/T 14048.5 |
| Product certifications | IEC; UL; CSA; CCC; EAC; DNV-GL; RMRS; EU-RO MR; UKCA |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 6,250 cm |
| VPE 1 width | 11,000 cm |
| VPE 1 length | 14,000 cm |
| Packaging weight (Lbs) | 362,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 12 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 4,594 kg |
| VPE 3 type | P06 |
| VPE 3 quantity | 192 |
| VPE 3 height | 75,000 cm |
| VPE 3 width | 60,000 cm |
| VPE 3 length | 80,000 cm |
| VPE 3 weight | 81,504 kg |
Motor protection relay - Thermal overload relay with differential protection - TeSys LRD. 3-phase, rated current 62 - 80A, class 10A for a motor power of up to 45kW at 400V. Compliant with ATEX D 94/9/CE, EN/IEC 60947-4-1, EN/IEC 60947-5-1, CSA C22.2 No 14, UL 60947-4-1 and certified according to ATEX INERIS, CCC, EAC. Features such as captive cable lug connection, optimized width of only 55mm and manual - automatic reset. For the highest requirements in the area of overload protection. Can be used for motors of all energy efficiency classes IE0 - IE4 up to 14 times the rated current. In combination with TeSys D they become an extremely compact starter.