| Complementary |
| Network frequency | 0...400 Hz |
| Mounting support | Plate, with terminal block LAD96560 on top; Rail, with terminal block LAD96560 on top; Direct mounting under contactor |
| Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| Permissible current | 0.95 A at 380 V AC-15 for signalling circuit; 0.06 A at 440 V DC-13 for signalling circuit |
| [Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
| Associated fuse rating | 4 A gG for signalling circuit; 4 A BS for signalling circuit |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Power dissipation per pole | 4.8 W |
| Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
| Control type | Red push-button: stop; Blue push-button: reset |
| Temperature compensation | -20…60 °C |
| Tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals; Power circuit: 5 N.m - on EverLink BTR screw connectors - cable 25 mm²; Power circuit: 8 N.m - on EverLink BTR screw connectors - cable 35 mm² |
| Height | 70 mm |
| Width | 55 mm |
| Depth | 123 mm |
| Net weight | 0.375 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Climatic withstand | conforming to IACS E10 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 |
| Ambient air temperature for storage | -60…70 °C |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7; Vibrations: 3 GN conforming to IEC 60068-2-6 |
| Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5 |
| Product certifications | IEC; UL; CSA; CCC; EAC; DNV-GL; RMRS; EU-RO MR; UKCA |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys LRD; TeSys Deca |
| Product or component type | Differential thermal overload relay |
| Device short name | LRD |
| Relay application | Motor protection |
| Product compatibility | LC1D80A |
| Network type | AC; DC |
| Thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Thermal protection adjustment range | 62…80 A |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V conforming to UL 60947-4-1; Power circuit: 600 V conforming to CSA C22.2 No 14 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.000 cm |
| Package 1 Width | 10.500 cm |
| Package 1 Length | 13.500 cm |
| Package 1 Weight | 392.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 13 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.383 kg |
Motor protection relay - Thermal overload relay with differential protection - TeSys LRD. 3-phase, rated current 62 - 80A, class 10A for a motor power of up to 45kW at 400V. Compliant with ATEX D 94/9/CE, EN/IEC 60947-4-1, EN/IEC 60947-5-1, CSA C22.2 No 14, UL 60947-4-1 and certified according to ATEX INERIS, CCC, EAC. Features such as low-maintenance EverLink terminal technology (removable), optimized width of only 55mm and manual - automatic reset. For the highest requirements in the area of overload protection. Can be used for motors of all energy efficiency classes IE0 - IE4 up to 14 times the rated current. In combination with TeSys D they become an extremely compact starter.