| Additional features |
| Network frequency | 0 - 400 Hz |
| Mounting bracket | Plate, with special accessories; rail, with special accessories; under contactor |
| Trigger threshold | 1.14 +/- 0.06 Ir corresponds to IEC 60947-4-1 |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| [Ith] conventional thermal current in free air | 5 A for signal circuits |
| Permissible current | 0.72 A at 500 V AC-15 for signal circuit; 0.06 A at 440 V DC-13 for signal circuit |
| [Ue] Rated operational voltage | 1,000 V AC 0 - 400 Hz for circuit corresponds to IEC 60947-4-1 |
| Associated fuse | 4 A gG for signal circuit; 4 A BS for signal circuit |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947-1 |
| Phase loss sensitivity | Trip current 130 % of Ir on two phases, the last at 0 |
| Control type | Red push-button: Stop; Blue push-button: Reset |
| Temperature compensation | -20…60 °C |
| Terminal pitch | 17,5 mm |
| Connections - terminals | Control circuit: screw terminals 2 cable(s) 1…2.5 mm² flexible without cable end; control circuit: screw terminals 2 cable(s) 1…2.5 mm² flexible with cable end; control circuit: screw terminals 2 cable(s) 1…2.5 mm² solid without cable end; power circuit: ring terminal connectors |
| Tightening moment | Control circuit: 1.7 Nm - on screw terminals; power circuit: 11.3 Nm - on ring terminal lugs M10 |
| Height | 81 mm |
| Width | 70 mm |
| Depth | 115 mm |
| Product weight | 0,51 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys |
| Product name | TeSys LRD; TeSys Deca |
| Product or component type | thermal overload relay with differential protection |
| Device short name | LRD |
| Device application | Motor protection |
| Product compatibility | LC1D95; LC1D80 |
| Type of network | AC; DC |
| Thermal trip class | Class 10 A according to IEC 60947-4-1 |
| Adjustable range for thermal protection | 23…32 A |
| [Ui] Rated insulation voltage | Circuit: 1000 V corresponds to IEC 60947-4-1; Circuit: 600 V corresponds to CSA; Circuit: 600 V corresponds to UL |
| Mounting |
| Climate resistance | complies with IACS E10 |
| Degree of protection (IP) | IP20 complies with IEC 60529 |
| Operating ambient temperature | -20…60 °C without power derating, complies with IEC 60947-4-1 |
| Ambient temperature during storage | -60…70 °C |
| Flame retardancy | V1 corresponds to UL 94 |
| Mechanical robustness | Vibrations: 6 Gn according to IEC 60068-2-6; shocks: 15 Gn for 11 ms according to IEC 60068-2-7 |
| Dielectric strength | 2.2 kV at 50 Hz corresponds to IEC 60947-1 |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No. 60947-4-1; CSA C22.2 No. 60947-5-1; GB/T 14048.4; GB/T 14048.5 |
| Product certifications | IEC; UL; CSA; CCC; EAC; UKCA |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 7,7 cm |
| VPE 1 width | 8,5 cm |
| VPE 1 length | 11,8 cm |
| Packaging weight (Lbs) | 402,0 g |
Motor protection relays 0.06 -75 kW Thermal overload relays TeSys LRD are extremely reliable and cover the entire motor range up to 150 A. They have a manual-automatic reset and are available with different terminal variants. In combination with TeSys D they become an extremely compact starter.