| Complementary |
| Network frequency | 0...400 Hz |
| Mounting support | Plate, with specific accessories; Rail, with specific accessories; Under contactor |
| Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| Permissible current | 1.5 A at 240 V AC-15 for signalling circuit; 0.1 A at 250 V DC-13 for signalling circuit |
| [Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
| Associated fuse rating | 4 A gG for signalling circuit; 4 A BS for signalling circuit |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
| Control type | Red push-button: stop; Blue push-button: reset |
| Temperature compensation | -20…60 °C |
| Connections - terminals | Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid; Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² flexible without cable end; Power circuit: screw clamp terminals 1 cable(s) 1…6 mm² flexible with cable end; Power circuit: screw clamp terminals 1 cable(s) 1.5…10 mm² solid |
| Tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals; Power circuit: 2.5 N.m - on screw clamp terminals |
| Height | 66 mm |
| Width | 45 mm |
| Depth | 70 mm |
| Net weight | 0.124 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Climatic withstand | conforming to IACS E10 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 |
| Ambient air temperature for storage | -60…70 °C |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations: 6 Gn conforming to IEC 60068-2-6; Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 |
| Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5; EN 50495 |
| Product certifications | IEC; UL; CSA; CCC; EAC; BV; RINA; DNV-GL; LROS (Lloyds register of shipping); ATEX INERIS; UKCA |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys LRD; TeSys Deca |
| Product or component type | Differential thermal overload relay |
| Device short name | LRD |
| Relay application | Motor protection |
| Product compatibility | LC1D32; LC1D25; LC1D38 |
| Network type | AC; DC |
| Thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Thermal protection adjustment range | 23…32 A |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.000 cm |
| Package 1 Width | 7.800 cm |
| Package 1 Length | 8.800 cm |
| Package 1 Weight | 142.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 3.720 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 384 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 67.520 kg |
The
motor protection relay LRD32 from the
TeSys Deca series by
Schneider Electric is a
thermal overload relay with differential protection, specifically designed for protecting electric motors in industrial applications. It serves as a protective component mounted directly beneath a contactor and covers motor ratings from 23 to 32 amperes. The devices are designed for use in
AC and DC networks and operate within a frequency range of 0 to 400 Hz. The
thermal trip class 10 A complies with IEC 60947-4-1 and ensures precise response to overloads, with the trip threshold set at 1.14 ± 0.06 times the set nominal current (Ir).
Temperature compensation in the range of -20 to 60 °C ensures reliable operation regardless of environmental influences.
Applications include motor protection in production plants, conveyor systems, pump and fan drives, and other industrial drive systems where high operational reliability is required. The device is compatible with contactor types
LC1D32, LC1D25, and LC1D38, enabling flexible integration into existing control systems.
Phase loss sensitivity is defined by a trip condition of 130 % of the set current on two phases when the third phase is disconnected, providing reliable protection against unbalanced operating conditions.
Functions and features in detail include a
spring-loaded connection for mounting beneath the contactor, as well as a front panel with two control buttons: a
red button for triggering the test function and a
blue button for Off" and "Manual reset functions. A
yellow mechanical indicator visually signals the tripped state. Resetting can be done either manually or automatically, with the setting adjusted directly on the device front. The auxiliary contacts consist of
1 normally closed and 1 normally open contact (1S+1Oe), which can be used for control and signaling purposes.
Technology explained simply shows that the relay features
screw terminals for both power and control circuits. In the power circuit, cables with a cross-section of 1.5 to 10 mm² (flexible or rigid) can be connected, with flexible cables without end ferrules allowing a cross-section of 1 to 6 mm². In the control circuit, cables with 1 to 2.5 mm² (flexible or rigid) are permissible. The
torque values are 2.5 Nm for the power circuit and 1.7 Nm for the control circuit. The
rated operational voltage is 690 V AC, the
rated insulation voltage is 600 V (CSA/UL) or 690 V (IEC). The
impulse voltage withstand is specified at 6 kV, ensuring high electrical strength. The
dielectric strength is 1.89 kV at 50 Hz.
Compatibility and accessories include use with the mentioned contactor types LC1D32, LC1D25, and LC1D38. Accessories available include, for example, the
wiring kit LAD7C2 for D25–D38,
remote tripping units such as LAD703F or LA-D703M, and
reset buttons such as XB5AL84101 (red, projecting) or XB5AA86102 (blue, flush). These components enable extended functionality, such as remote control or improved operability in complex systems.
Mounting and installation can be done directly beneath the contactor, on a plate (with special accessories), or on a rail (also with special accessories). The
protection rating IP20 according to IEC 60529 protects against finger contact and solid foreign objects, but is not suitable for outdoor use or in damp environments. The
ambient temperature during operation ranges from -20 to 60 °C without performance reduction. The
flame retardancy corresponds to class V1 according to UL 94.
Mechanical robustness is defined by vibration loads of 6 Gn (IEC 60068-2-6) and shock loads of 15 Gn for 11 ms (IEC 60068-2-7).
Operational advantages include reliable overload and phase loss protection, easy operation via front buttons, clear visual indication, and flexible mounting options. Compliance with international standards such as EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, and GB/T 14048.4 ensures suitability for various markets. Certifications include IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS (Lloyds Register of Shipping), and ATEX INERIS, confirming suitability for demanding industrial and marine applications. The
rated operational voltage of 690 V AC and the
impulse voltage withstand of 6 kV ensure high electrical safety. The
climate resistance meets IACS E10, supporting use in marine environments.
The device is available in single packaging (PCE) with a weight of 0.124 kg. Dimensions are 45 mm (width), 66 mm (height), and 70 mm (depth).