| Complementary |
| Network frequency | 0...400 Hz |
| Mounting support | Plate, with specific accessories; Rail, with specific accessories; Under contactor |
| Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| Permissible current | 0.95 A at 380 V AC-15 for signalling circuit; 0.06 A at 440 V DC-13 for signalling circuit |
| [Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
| Associated fuse rating | 4 A gG for signalling circuit; 4 A BS for signalling circuit |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
| Control type | Red push-button: stop; Blue push-button: reset |
| Temperature compensation | -20…60 °C |
| Tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals; Power circuit: 5 N.m - on EverLink BTR screw connectors |
| Height | 70 mm |
| Width | 55 mm |
| Depth | 123 mm |
| Net weight | 0.375 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Climatic withstand | conforming to IACS E10 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 |
| Ambient air temperature for storage | -60…70 °C |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7; Vibrations: 4 gn conforming to IEC 60068-2-6 |
| Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5; EN 50495 |
| Product certifications | IEC; UL; CSA; CCC; EAC; DNV-GL; RMRS; EU-RO MR; LROS (Lloyds register of shipping); ATEX INERIS; UKCA |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys LRD; TeSys Deca |
| Product or component type | Differential thermal overload relay |
| Device short name | LRD |
| Relay application | Motor protection |
| Product compatibility | LC1D40A; LC1D50A; LC1D65A |
| Network type | DC; AC |
| Thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Thermal protection adjustment range | 12…18 A |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.300 cm |
| Package 1 Width | 10.500 cm |
| Package 1 Length | 13.800 cm |
| Package 1 Weight | 392.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 13 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.388 kg |
TeSys LR - 3-pole motor protection relays. Motor protection relay, spring-loaded connection. Relay setting range 12-18 A, Max. size aM 20, Max. size BS88 35, Max. size gG 32, MTZ 01, use D40A-D65A. Temperature compensated with differential protection. With manual or automatic reset. Trip class 10 A. Screw terminals. Mounting directly under the contactor. Choice of manual or automatic reset on the front of the device. Red button for triggering the Test" function. Blue button for the "Off" and "Manual reset functions. Yellow mechanical indicator appears when the relay is triggered. Auxiliary switch 1NO+1NC.