| Complementary |
| Network frequency | 30...60 Hz; 100 Hz |
| Overvoltage category | III |
| Tripping threshold | 1.125 +/- 0.07 In conforming to IEC 60947-4-1 |
| Protection type | Ground fault protection - tripping time adjustment: 0…1 s - for alarm circuit conforming to IEC 60947-4-1; Ground fault protection - tripping time adjustment: 0…1 s - for alarm circuit conforming to UL 60947-4-1; Phase loss - tripping time adjustment: 0…4 s - for alarm circuit; Phase imbalance - tripping time adjustment: 0…5 s - for alarm circuit conforming to IEC 60947-4-1; Phase imbalance - tripping time adjustment: 0…5 s - for alarm circuit conforming to UL 60947-4-1 |
| Local signalling | LED; Trip indicator |
| Contacts type and composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A |
| [Uc] control circuit voltage | 24...500 V AC 50/60 Hz; 24...250 V DC |
| [Ue] rated operational voltage | 1000 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Reset | Automatic reset; Manual |
| Mechanical durability | 7000 cycles |
| Surge withstand | 4 kV |
| Electromagnetic compatibility | EMC immunity conforming to IEC 60947-4-1; Emission tests criteria A conforming to IEC 60947-4-1; Immunity to radiated radio-electrical interference - test level: 20 V/m conforming to EN/IEC 61000-4-3; Voltage dips and interruptions immunity test conforming to SEMI F47 |
| Connections - terminals | Power circuit: bar - busbar cross section: 25 x 6 mm; Power circuit: lugs-ring terminals 1 185 mm²; Control circuit: push-in 1 0.2…2.5 mm² - cable stiffness: solid stranded without cable end; Control circuit: push-in 1 0.25…2.5 mm² - cable stiffness: flexible with cable end; Control circuit: push-in 2 0.5…1.0 mm² with cable end |
| Tightening torque | 18 N.m |
| Mounting support | Direct on contactor; Plate |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; JIS C8201-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; UL 60335-1 |
| Product certifications | CB Scheme; CCC; cULus; UKCA; ATEX; EU-RO-MR by DNV-GL; EAC |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP2X front face with shrouds conforming to IEC 60529; IP2X front face with shrouds conforming to VDE 0106 |
| Protective treatment | TH |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Permissible ambient air temperature around the device | -40…60 °C at Uc |
| Adjustment of dial setting | -25…60 °C |
| Mechanical robustness | Vibrations 5…300 Hz 6 gn contactor open; Shocks 15 gn 11 ms contactor closed |
| Height | 107 mm |
| Width | 105 mm |
| Depth | 126 mm |
| Net weight | 0.8 kg |
| Colour | Dark grey |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range | TeSys |
| Product name | TeSys LRG |
| Product or component type | Electronic thermal overload relay |
| Device short name | LR9G |
| Relay application | Motor protection |
| Network type | AC |
| Thermal overload class | Class 5E...30E conforming to IEC 60947-4-1 |
| Thermal protection adjustment range | 57…225 A |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 17.000 cm |
| Package 1 Width | 20.000 cm |
| Package 1 Length | 21.000 cm |
| Package 1 Weight | 1.425 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 3.383 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 16 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 35.624 kg |
TeSys protect - Giga overload relay with a rated current range of 57-225A, Class 5E-30E for optimal motor protection. It offers protection against phase unbalance, phase failure, built-in earth fault and single-phase loads. The device has manual and automatic reset and shows motor ON and pre-alarm via an LED display. The trip classes are selectable from Class 5E to 30E to meet different application requirements, such as extremely light starting to extremely heavy starting. Green Premium compliant (RoHs/Reach).