| Complementary |
| Network frequency | 50...60 Hz |
| [Us] rated supply voltage | 24 V DC |
| Supply voltage limits | 17…32 V |
| Mounting support | Under contactor; Rail |
| Tripping threshold | 1.05 +/- 0.06 In alarm conforming to IEC 60947-4-1; 1.12 +/- 0.06 In de-energisation conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| [Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
| Associated fuse rating | 4 A gG for signalling circuit; 4 A BS for signalling circuit |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947-1 |
| Phase failure sensitivity | Tripping in 4 s +/- 20 % conforming to IEC 60947-4-1 |
| Control type | Red push-button: stop; Blue push-button: reset |
| Temperature compensation | -20…60 °C |
| Switching capacity in mA | 0...150 mA |
| Connections - terminals | Power circuit: bars; Control circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 0.5…1.5 mm² flexible without cable end; Alarm circuit: screw clamp terminals 1 cable(s) 0.5…1.5 mm² flexible without cable end |
| Tightening torque | Alarm circuit: 0.45 N.m - on screw clamp terminals; Power circuit: 18 N.m - on bars M8; Control circuit: 1.2 N.m - on screw clamp terminals |
| Height | 118 mm |
| Width | 115 mm |
| Depth | 125 mm |
| Net weight | 0.885 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Climatic withstand | conforming to IACS E10 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 |
| Ambient air temperature for storage | -60…70 °C |
| Mechanical robustness | Vibrations: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Shocks: 13 Gn for 11 ms conforming to IEC 60068-2-7 |
| Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5 |
| Product certifications | UL; CSA; CCC; UKCA |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys LRD; TeSys Deca |
| Product or component type | Electronic thermal overload relay |
| Device short name | LR9D |
| Relay application | Motor protection |
| Product compatibility | LC1D115; LC1D150; NSX circuit breaker |
| Network type | AC |
| Thermal overload class | Class 10 conforming to IEC 60947-4-1 |
| Signalling function | Alarm |
| Thermal protection adjustment range | 60…100 A |
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1; Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.000 cm |
| Package 1 Width | 16.000 cm |
| Package 1 Length | 13.000 cm |
| Package 1 Weight | 934.000 g |
| Unit Type of Package 2 | S04 |
| Number of Units in Package 2 | 12 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 40.000 cm |
| Package 2 Length | 60.000 cm |
| Package 2 Weight | 11.978 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 48 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 56.000 kg |
The
motor protection relay LR9D5367 from the
TeSys series by
Schneider Electric is an
electronic thermal overload relay designed for industrial applications. It protects electric motors against thermal overload and is specifically designed for applications in the 60 to 100 A range. The device is part of the TeSys LRD and TeSys Deca families and is used in combination with contactors such as LC1D115, LC1D150, or NSX circuit breakers to create a compact and reliable motor starter. The protection function operates according to
thermal trip class 10, as defined by IEC 60947-4-1, ensuring precise adaptation to the thermal characteristics of the motor.
Applications
This relay is designed for use in industrial drive systems, particularly in installations with motors in the power range of 0.06 to 75 kW. It protects motors against overload caused by continuous or short-term current overloads, phase loss, and other disturbances. The relay is used in electrical control panels where reliable motor monitoring is required, for example in manufacturing, process engineering, or pump and fan applications. The operating temperature range of -20 to 60 °C allows use in a wide variety of environments without requiring derating.
Functions and Features in Detail
The device features
manual and automatic reset, with reset performed via a
red pushbutton (stop) and a
blue pushbutton (reset). Signaling is provided by an integrated
alarm, which activates when the relay trips. The auxiliary contacts are configured as
1 NO + 1 NC, enabling flexible integration into control and monitoring systems. The
trip threshold is 1.05 ± 0.06 In for alarm and 1.12 ± 0.06 In for disconnection, in accordance with IEC 60947-4-1. In the event of phase loss, the relay trips within 4 seconds ± 20%. The
temperature compensation function ensures stable protection performance in ambient temperatures between -20 and 60 °C.
Technical Explanation
The relay operates using an
electronic thermal overload protection function, which simulates heat development in the motor and disconnects the motor when permissible values are exceeded. Power supply is via
24 V DC, with a tolerance range of 17 to 32 V. The rated operating voltage for the power circuit is 690 V AC at frequencies from 0 to 400 Hz. The
rated insulation voltage is 1000 V (IEC 60947-4-1), 600 V (CSA), and 600 V (UL). The
rated impulse withstand voltage is 6 kV, ensuring high electrical strength even under transient voltage surges. The
dielectric strength is 1.89 kV at 50 Hz. The
conventional thermal current in the signaling circuit is 5 A.
Compatibility and Accessories
The relay is compatible with contactors
LC1D115,
LC1D150, and
NSX circuit breakers. It can be enhanced with accessories such as the
reset button XB5AL84101 (red, projecting) or
XB5AA86102 (blue, flush) to optimize operation. Remote operation is possible using accessory
LA7D305. Alternatively, the device can be combined with other TeSys products such as
GV4LE115N or
GV4L115N. The successor model is specified as
LR9G115 (28–115 A).
Mounting and Installation
Mounting is either
under the contactor or on a
rail. Connections consist of
rails for the power circuit and
screw terminals for the control and alarm circuits. Cable cross-sections for control and alarm circuits range from 0.5 to 1.5 mm² flexible, without cable ends. Tightening torques are 18 Nm for rails, 1.2 Nm for control terminals, and 0.45 Nm for alarm circuits. The
protection rating IP20 according to IEC 60529 protects against finger contact and solid foreign objects, but is not waterproof. Mechanical robustness is certified according to IEC 60068-2-6 (vibrations: 2 Gn, 5–300 Hz) and IEC 60068-2-7 (shocks: 13 Gn, 11 ms).
Operational Advantages
The relay offers high reliability through electronic thermal simulation, enabling precise adaptation to motor load. The integrated signaling and manual/automatic reset simplify maintenance and operation. Combination with TeSys D contactors results in a compact starter, saving space in the enclosure. Certifications according to
EN/IEC 60947-4-1,
UL 60947-4-1,
CSA C22.2 No. 60947-4-1, and
CCC ensure compliance with international safety and quality standards. The operating temperature range of -20 to 60 °C and mechanical robustness make the device suitable for demanding industrial applications.