| Complementary |
| Network frequency | 0...400 Hz |
| Mounting support | Plate, with specific accessories; Rail, with specific accessories; Under contactor |
| Tripping threshold | 1.14 +/- 0.06 Ir conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 5 A for signalling circuit |
| Permissible current | 3 A at 120 V AC-15 for signalling circuit; 0.22 A at 125 V DC-13 for signalling circuit |
| [Ue] rated operational voltage | 690 V AC 0...400 Hz for power circuit conforming to IEC 60947-4-1 |
| Associated fuse rating | 4 A gG for signalling circuit; 4 A BS for signalling circuit |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Phase failure sensitivity | Tripping current 130 % of Ir on two phase, the last one at 0 |
| Control type | Red push-button: stop; Blue push-button: reset |
| Temperature compensation | -20…60 °C |
| Connection pitch | 14.5 mm |
| Connections - terminals | Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible without cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² flexible with cable end; Control circuit: screw clamp terminals 2 cable(s) 1…2.5 mm² solid without cable end; Power circuit: lugs-ring terminals |
| Tightening torque | Control circuit: 1.7 N.m - on screw clamp terminals; Power circuit: 2.3 N.m - on lugs-ring terminals M4 |
| Height | 66 mm |
| Width | 45 mm |
| Depth | 70 mm |
| Net weight | 0.124 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Climatic withstand | conforming to IACS E10 |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Ambient air temperature for operation | -20…60 °C without derating conforming to IEC 60947-4-1 |
| Ambient air temperature for storage | -60…70 °C |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations: 6 Gn conforming to IEC 60068-2-6; Shocks: 15 Gn for 11 ms conforming to IEC 60068-2-7 |
| Dielectric strength | 1.89 kV at 50 Hz conforming to IEC 60947-1 |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; GB/T 14048.4; GB/T 14048.5; EN 50495 |
| Product certifications | IEC; UL; CSA; CCC; EAC; BV; RINA; DNV-GL; LROS (Lloyds register of shipping); ATEX INERIS; UKCA |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys LRD; TeSys Deca |
| Product or component type | Non differential thermal overload relay |
| Device short name | LR3D |
| Relay application | Motor protection |
| Product compatibility | LC1D25; LC1D32; LC1D12; LC1D18; LC1D09; LC1D38 |
| Network type | DC; AC |
| Thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Thermal protection adjustment range | 2.5…4 A |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to CSA; Power circuit: 600 V conforming to UL; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.8 cm |
| Package 1 Width | 7.7 cm |
| Package 1 Length | 8.8 cm |
| Package 1 Weight | 152.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 24 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 3.904 kg |
The LR3D086 motor protection relay from the TeSys Deca series by Schneider Electric is a thermal overload relay without differential protection, specifically designed for protecting electric motors in industrial applications. It serves as a protection component in drive systems and is used in combination with contactors from the TeSys D series to create a compact and reliable motor starter. The device is designed for use in electrical installations with alternating and direct voltage and covers the motor range up to 150 A, making it suitable for motors in the power range of 0.06 to 75 kW.
Applications
The relay is intended for use in industrial installations such as machine building, conveyor technology, packaging technology, and other areas with electric drives. It protects motors against thermal overload due to continuous overload or phase failure. The thermal trip class 10 A corresponds to the standard IEC 60947-4-1 and ensures precise response to overloads. The trip threshold is set at 1.14 ± 0.06 times the set rated current Ir, enabling reliable protection for motors slightly overloaded.
Functions and Equipment in Detail
The relay features manual and automatic reset, with reset performed via a blue push-button. A red push-button is used to stop the motor. The control functions are thus directly visible and operable on the device. The temperature compensation function enables stable operation at ambient temperatures from -20 to 60 °C without requiring performance reduction. The adjustment range for thermal protection is between 2.5 and 4 A, making it suitable for small to medium-sized motors.
Technology Explained Simply
The device operates on the principle of thermal overload protection, where a bimetal strip is deformed by the heat of the motor current and disconnects the contact when the set current value is exceeded. The rated operating voltage is 690 V AC at frequencies from 0 to 400 Hz, with the rated insulation voltage also being 690 V (IEC 60947-4-1). The rated impulse voltage withstand is 6 kV, ensuring high electrical strength. The dielectric strength is 1.89 kV at 50 Hz, highlighting the insulation quality.
Compatibility and Accessories
The relay is compatible with various contactors from the TeSys D series, including LC1D09, LC1D12, LC1D18, LC1D25, LC1D32, and LC1D38. It can be mounted directly under the contactor or secured to a plate or rail using special brackets. As an accessory, a carrier for individual mounting (LAD7B106) is available, enabling modular installation. The connections consist of screw terminals for the control circuit (cable cross-section 1…2.5 mm², flexible or rigid, with or without wire end ferrule) and ring terminal connectors for the power circuit. The tightening torque is 1.7 Nm for control circuit terminals and 2.3 Nm for ring terminal connectors (M4).
Mounting and Installation
Mounting is done either directly under the contactor or using special brackets on a plate or rail. The terminal spacing is 14.5 mm. The device dimensions are 45 mm (width), 66 mm (height), and 70 mm (depth). Mechanical robustness is certified according to IEC 60068-2-6 for vibrations of 6 Gn and according to IEC 60068-2-7 for shocks of 15 Gn (11 ms). The protection rating IP20 corresponds to IEC 60529 and protects against finger contact and solid foreign objects. Flame resistance corresponds to class V1 according to UL 94.
Operational Advantages
The relay offers high reliability through thermal tripping function and precise adjustability. The integrated reset function enables quick reactivation after a tripping event. Compatibility with TeSys D contactors reduces space requirements and simplifies installation. Certifications according to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1 and other standards ensure compliance with international safety standards. The operating temperature range of -20 to 60 °C allows use in a wide range of industrial environments. The permissible current values for the signal circuit are 3 A at 120 V AC-15 and 0.22 A at 125 V DC-13. The associated fuse rating is 4 A gG or 4 A BS for the signal circuit.
Control Type
The control functions are implemented via two push-buttons: a red button for stopping and a blue button for resetting. This operation is directly visible on the device and allows for quick response during operation. The phase failure sensitivity is designed such that with a failure of two phases, a tripping current of 130 % of the set current Ir is reached, with the last phase at 0 %. This ensures protection even with incomplete phase supply.
Standards and Certifications
The device complies with standards EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, UL 60947-5-1, CSA C22.2 No. 60947-4-1, CSA C22.2 No. 60947-5-1, GB/T 14048.4, GB/T 14048.5, and EN 50495. Additionally, it is certified by IEC, UL, CSA, CCC, EAC, BV, RINA, DNV-GL, LROS (Lloyds Register of Shipping), and ATEX INERIS, highlighting its international usability.
Climate Resistance and Environment
Climate resistance corresponds to IACS E10, ensuring high durability in industrial environments. The storage temperature range is between -60 and 70 °C, enabling long-term storage even under extreme conditions. The product weight is 0.124 kg, with the packaging weight being 0.152 kg. The packaging unit consists of a single device (PCE) and is available in cartons of 24 pieces (S02).