| Complementary |
| Mounting support | Under contactor; Plate, with specific accessories; Rail, with specific accessories |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ith] conventional free air thermal current | 6 A for signalling circuit |
| Associated fuse rating | 6 A gG for signalling circuit conforming to VDE 0660; 6 A gG for signalling circuit conforming to IEC 60947 |
| [Uimp] rated impulse withstand voltage | 6 kV |
| Power dissipation per pole | 2 W |
| Phase failure sensitivity | Yes conforming to IEC 60947-4-1 |
| Local signalling | Trip indicator (yellow) |
| Control type | Red push-button: trip test function; Blue push-button: stop and manual reset; selector switch: manual or automatic reset |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Tightening torque | 1.3 N.m - on screw clamp terminals - with screwdriver Philips No 2; 1.3 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; 1.3 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 65 mm |
| Net weight | 0.145 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60947; VDE 0660; BS 4941; NF C 63-650 |
| Product certifications | UL; CSA; UKCA |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50016 |
| IP degree of protection | IP2X conforming to IEC 60529 |
| Ambient air temperature for operation | -20…55 °C without derating conforming to IEC 60947; -30…60 °C with derating conforming to IEC 60947 |
| Ambient air temperature for storage | -40…70 °C |
| Operating altitude | 2000 m without derating |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Mechanical robustness | Shocks NO contact: 10 Gn for 11 ms conforming to IEC 60068-2-27; Shocks NC contact: 10 Gn for 11 ms conforming to IEC 60068-2-27; Vibrations NO contact: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6; Vibrations NC contact: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Product name | TeSys LRK |
| Product or component type | Differential thermal overload relay |
| Device short name | LR2K |
| Relay application | Motor protection |
| Product compatibility | LC7K; LP1K; LC1K; LP4K |
| Network type | DC; AC |
| Thermal overload class | Class 10A conforming to IEC 60947-4-1 |
| Thermal protection adjustment range | 8…11.5 A |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to BS 4941; Power circuit: 690 V conforming to IEC 60947; Power circuit: 750 V conforming to VDE 0110 group C; Power circuit: 600 V conforming to CSA C22.2 No 14 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 7.200 cm |
| Package 1 Width | 4.800 cm |
| Package 1 Length | 8.500 cm |
| Package 1 Weight | 157.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 41 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 6.855 kg |
The
motor protection relay LR2K0316 from the
TeSys series by
Schneider Electric is a
thermal overload relay with differential protection, specifically designed for use in industrial drive systems. It protects electric motors against overload and phase failure, with the thermal protection setting range between
8 and 11.5 A. The trip class is
Class 10 A, enabling fast response to overloads in accordance with IEC 60947-4-1. The device is designed for use in
AC and DC networks and is suitable for motor protection applications with contactor types LC7K, LP1K, LC1K, and LP4K.
Applications include industrial automation, particularly in systems with electric drives, where reliable motor monitoring is required. The relay is designed for operation in environments with an operating temperature of
-20 to 55 °C without derating, while derating is required at temperatures from
-30 to 60 °C. The operating altitude is up to
2,000 m without derating. The protection rating
IP2x in accordance with IEC 60529 protects against contact with fingers and larger solid objects, but not against water or dust.
Functions and equipment in detail include a
temperature-compensated tripping function with
differential protection, which detects phase failures. Local signaling is provided by a
yellow mechanical trip indicator, visible when tripped. Resetting can be set via a
selector switch to
manual or automatic. A
red pushbutton is used to activate the test function, while a
blue pushbutton performs the Off" and "manual reset functions. The auxiliary contacts consist of
1 normally closed and 1 normally open contact, facilitating integration into control systems.
Technology explained simply shows that the relay features
screw terminals suitable for various cable cross-sections: rigid 1.5 to 4 mm², flexible 0.75 to 4 mm² without cable end ferrule, and flexible 0.34 to 2.5 mm² with cable end ferrule. The tightening torque is
1.3 Nm, with installation using a Phillips screwdriver No. 2, a flat screwdriver Ø 6, or a positioning screwdriver No. 2. The rated insulation voltage is
690 V in accordance with IEC 60947 and BS 4941, as well as
750 V in accordance with VDE 0110 Group C and
600 V in accordance with CSA C22.2 No. 14. The rated impulse voltage withstand is
6 kV, and the power loss per pole is
2 W. The associated fuse for the signaling circuit is a
6 A gG fuse in accordance with VDE 0660 and IEC 60947.
Compatibility and accessories include use with contactor types LC7K, LP1K, LC1K, and LP4K. Suitable accessories include various contactors from the TeSys series, such as LC1K0910R7, LC1K0910F72, LC1K0910D7, LC1K0901B72, LP2K0901BD, LC2K0910B7TQ, LC1K09107E7, LC2K0910D7, carrier LA7-K0064 for LR2-K, LC1K0910E7, LP1K0910SD, LC2K0901E7, LC1K0901V7, LP1K0901ED, LP1K0910BD, LC1K0910B7TQ, LC1K0910U7, LP1K0910ED3, LC2K0910P7, and LC2K0901F72. These components enable flexible integration into existing systems.
Mounting and installation is done directly under the contactor, with mounting on panel or rail also possible using special accessories. Dimensions are
58 mm height, 45 mm width, and 65 mm depth, with a product weight of
0.145 kg. Mechanical robustness is certified in accordance with IEC 60068-2-27 and IEC 60068-2-6 for shocks (10 Gn, 11 ms) and vibrations (2 Gn, 5–300 Hz). Flame retardancy meets UL 94 V1, NF F 16-101 Requirement 2, and NF F 16-102 Requirement 2. Fire resistance is
850 °C in accordance with IEC 60695-2-1.
Operational advantages include reliable motor monitoring via differential protection, which detects phase failures, and simple operation via front pushbuttons and selector switch. The temperature-compensated tripping ensures precise response regardless of ambient temperature. Integration into existing contactor systems is easy and quick due to compatibility with various TeSys contactors. Certifications in accordance with IEC 60947, VDE 0660, BS 4941, NF C 63-650, as well as product certifications UL, CSA, and UKCA, guarantee compliance with international standards.