| Complementary |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | Operational: 0.7...1.30 Uc (at |
| Inrush power in W | 1.8 W (at 20 °C) |
| Hold-in power consumption in W | 1.8 W at 20 °C |
| Heat dissipation | 1.8 W |
| Auxiliary contacts type | type instantaneous 1 NC |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20 conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50016 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Height | 58 mm |
| Width | 90 mm |
| Depth | 57 mm |
| Net weight | 0.49 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys K |
| Product or component type | Reversing contactor |
| Device short name | LP5K |
| Device application | Control |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-1; AC-4; AC-3e |
| Device presentation | Preassembled with reversing power busbar |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: 690 V AC 50/60 Hz; Signalling circuit: |
| [Ie] rated operational current | 20 A (at |
| Motor power kW | 2.2 kW at 220...230 V AC 50/60 Hz; 4 kW at 380...415 V AC 50/60 Hz; 4 kW at 440 V AC 50/60 Hz; 4 kW at 480 V AC 50/60 Hz; 4 kW at 500...600 V AC 50/60 Hz; 4 kW at 660...690 V AC 50/60 Hz |
| Control circuit type | DC low consumption |
| [Uc] control circuit voltage | 24 V DC |
| Auxiliary contact composition | 1 NC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 20 A (at 50 °C) for power circuit; 10 A (at 50 °C) for signalling circuit |
| Irms rated making capacity | 110 A AC for power circuit conforming to NF C 63-110; 110 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit; 20 A 50 °C - >= 15 min for power circuit |
| Associated fuse rating | 25 A gG at |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
| Electrical durability | 1.3 Mcycles 9 A AC-3 at Ue |
| Interlocking type | Mechanical |
| Mounting support | Rail; Plate |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Tightening torque | 0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm; 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2 |
| Operating time | 10...20 ms coil de-energisation and NO opening; 30...40 ms coil energisation and NO closing |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 5 Mcycles |
| Maximum operating rate | 3600 cyc/h |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 9.200 cm |
| Package 1 Length | 6.000 cm |
| Package 1 Weight | 450.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.334 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 160 |
| Package 3 Height | 45.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 83.820 kg |
The Schneider Electric TeSys K-reversing contactor LP5K0901BW3 is a 3-pole contactor for controlling electric drives and resistive loads. It is specifically designed for motor applications, with a maximum motor power of 4 kW at 400 V AC (AC-3). The device features a 24 V DC coil with low power consumption, suitable for actuation via programmable control outputs. The coil is equipped with overvoltage protection, enhancing reliability in industrial environments. The rated operational voltage is 690 V AC at 50/60 Hz, and the rated operational current is 20 A. The rated insulation voltage is 690 V for the power circuit and signal circuit according to IEC 60947-4-1, as well as 600 V according to UL 508 and CSA C22.2 No. 14.
Reversing contactor refers to a contactor used to reverse the rotation direction of a motor. The LP5K0901BW3 is provided as a pre-assembled combination with a reversing power busbar, simplifying installation and commissioning. The mechanical interlock prevents simultaneous switching of both contactors, ensuring safe operation. Connections are made via screw terminals suitable for rigid cables from 1.5 to 4 mm² and flexible cables from 0.75 to 4 mm² without wire ends, and from 0.34 to 2.5 mm² with wire ends. The tightening torque is 0.8 to 1.3 Nm, and terminals are to be secured using a Phillips screwdriver No. 2 or flat screws with Ø 6 mm.
Functions and equipment in detail include built-in auxiliary contacts configured as 2 normally open (2NO). These are used for signal transmission in control circuits, for example, to indicate the switching status. The electrical life is 1.3 million switching cycles at 9 A AC-3, indicating high load capacity. The mechanical life is specified at 5 million switching cycles, highlighting the robustness of the device. The operating time is 10 to 20 ms for coil de-energization and NO opening, and 30 to 40 ms for coil energization and NO closing.
Technology explained simply shows that the contactor is designed for usage categories AC-1, AC-3, AC-3e, and AC-4. The rated breaking capacity is, for example, 110 A at 415 V and 70 A at 660–690 V, with values defined according to IEC 60947. The rated impulse voltage withstand is 8 kV, and the overvoltage category is III. The conventional thermal current (Ith) is 20 A for the power circuit and 10 A for the signal circuit at 50 °C. The average impedance is 3 MΩ at 20 A and 50 Hz for the power circuit.
Compatibility and accessories include use with various motor protection circuit breakers such as GV2LE14 or GV2ME14, as well as motor protection relays like LR2K0314 or LR2K0316. Additional auxiliary switches such as LA2KT2U (delayed 30 s) or LA2KT2E (time-delayed 1–30 s) are available. Nameplates such as LA9D90 and auxiliary switch blocks such as LA1KN20 (2 NO) or LA1KN02 (2 NO) can be used as supplements. Mounting is on DIN rail or directly on a panel, with screw fastening ensuring a secure and stable installation.
Mounting and installation is straightforward by securing to a DIN rail or mounting plate. The pre-assembled power busbar reduces installation time and minimizes error sources. The screw terminals allow for secure connections with various cable types. The mechanical interlock ensures that the contactors cannot be actuated simultaneously, guaranteeing safe operation.
Advantages in operation include high service life, compact design, and easy installation. The 24 V DC coil with low power consumption is ideal for integration into modern control systems. Certifications according to EN/IEC 60947-4-1, UL, CSA, CCC, EAC, and CE, as well as compliance with RoHS/REACH, ensure adherence to international standards. The device is designed for industrial applications where reliability and safety are critical.