| Complementary |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at |
| Inrush power in W | 3 W (at 20 °C) |
| Hold-in power consumption in W | 3 W at 20 °C |
| Heat dissipation | 3 W |
| Auxiliary contacts type | type instantaneous 1 NC |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20 conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50016 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Height | 58 mm |
| Width | 90 mm |
| Depth | 57 mm |
| Net weight | 0.48 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys K |
| Product or component type | Reversing contactor |
| Device short name | LP2K |
| Device application | Control |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-4; AC-1 |
| Device presentation | Preassembled with reversing power busbar |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: 690 V AC 50/60 Hz; Signalling circuit: |
| [Ie] rated operational current | 9 A (at |
| Motor power kW | 2.2 kW at 220...230 V AC 50/60 Hz; 4 kW at 380...415 V AC 50/60 Hz; 4 kW at 440/690 V AC 50/60 Hz |
| Control circuit type | DC standard |
| [Uc] control circuit voltage | 48 V DC |
| Auxiliary contact composition | 1 NC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit |
| Irms rated making capacity | 110 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit |
| Associated fuse rating | 25 A gG at |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
| Electrical durability | 1.3 Mcycles 9 A AC-3 at Ue |
| Interlocking type | Mechanical |
| Mounting support | Rail; Plate |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Tightening torque | 0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm; 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2 |
| Operating time | 30...40 ms coil energisation and NO closing; 10 ms coil de-energisation and NO opening |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 5 Mcycles |
| Maximum operating rate | 3600 cyc/h |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 9.400 cm |
| Package 1 Length | 6.100 cm |
| Package 1 Weight | 445.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.000 kg |
Mini contactors 0.06 - 5.5 kW TeSys K offers you a complete range of mini contactors with an optimal ratio of performance to compactness and seamless integration into your applications.