| Complementary |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at |
| Inrush power in W | 3 W (at 20 °C) |
| Hold-in power consumption in W | 3 W at 20 °C |
| Heat dissipation | 3 W |
| Auxiliary contacts type | type instantaneous 1 NC |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Non overlap distance | 0.5 mm |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20 conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50016 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Height | 58 mm |
| Width | 90 mm |
| Depth | 57 mm |
| Net weight | 0.48 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys K |
| Product or component type | Reversing contactor |
| Device short name | LP2K |
| Device application | Control |
| Contactor application | Motor control |
| Utilisation category | AC-3; AC-3e; AC-4 |
| Device presentation | Preassembled with reversing power busbar |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: 690 V AC 50/60 Hz; Signalling circuit: |
| [Ie] rated operational current | 6 A (at |
| Motor power kW | 1.5 kW at 220...230 V AC 50/60 Hz; 2.2 kW at 380...415 V AC 50/60 Hz; 3 kW at 440/690 V AC 50/60 Hz |
| Control circuit type | DC standard |
| [Uc] control circuit voltage | 24 V DC |
| Auxiliary contact composition | 1 NC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit |
| Irms rated making capacity | 110 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit |
| Associated fuse rating | 25 A gG at |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
| Electrical durability | 1.3 Mcycles 6 A AC-3 at Ue |
| Interlocking type | Mechanical |
| Mounting support | Plate; Rail |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Tightening torque | 0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm |
| Operating time | 30...40 ms coil energisation and NO closing; 10 ms coil de-energisation and NO opening |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 5 Mcycles |
| Maximum operating rate | 3600 cyc/h |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.0 cm |
| Package 1 Width | 6.5 cm |
| Package 1 Length | 9.2 cm |
| Package 1 Weight | 447.0 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 20 |
| Package 2 Height | 15.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 9.275 kg |
The Schneider Electric reversing contactor LP2K0601BD from the TeSys K series is a compact, 3-pole device for motor control in industrial applications. It is designed for controlling electric motors with a rated power of up to 2.2 kW at 380–415 V AC 50/60 Hz and is suitable for usage categories AC-3, AC-3e, and AC-4. The device is pre-assembled with a reversing power busbar, simplifying installation and wiring for reversing drives. The integrated mechanical interlock prevents both contactors from being switched on simultaneously, which is essential for safety during reversing operations.
Applications
This reversing contactor is designed for simple motor applications in industry, particularly in systems requiring drive direction changes, such as conveyor systems, machine tools, or pumps. The operating voltage in the main circuit is up to 690 V AC, while the control circuit rated operating voltage is 24 V DC. The coil is designed for a control circuit voltage of 24 V DC, enabling easy integration into existing control systems. The operating voltage range is between 0.8 and 1.15 times the rated voltage, ensuring reliable operation under varying network conditions.
Functions and Features in Detail
The device includes an integrated auxiliary contact with one normally open (1 NO) contact, which can be used for signaling functions in control systems. The contact configuration in the main circuit is 3 NO, indicating three normally open contacts. The rated switching capacity is 110 A AC in the main circuit and in the signaling circuit, according to IEC 60947. The rated breaking capacity depends on the operating voltage and is, for example, 110 A at 220–230 V and 70 A at 660–690 V. The electrical service life is 1.3 million switching cycles at 6 A AC-3, while the mechanical service life is 5 million switching cycles. The maximum operating rate is specified as 3600 switching operations per hour.
Technical Explanation
The contactor coil is operated at 24 V DC and has an inrush power of 3 W at 20 °C and a holding power consumption of 3 W. The operating time is 30–40 ms for coil energization and contact closing, and 10 ms for de-energization and contact opening. The rated impulse voltage withstand is 8 kV, and the overvoltage category is III, indicating suitability for industrial environments with moderate overvoltage stress. The rated insulation voltage is 690 V for the main circuit and signaling circuit according to IEC 60947-4-1, as well as 600 V according to UL 508 and CSA C22.2 No. 14. The conventional thermal current rating is 20 A in the main circuit at 60 °C and 10 A in the signaling circuit at 50 °C.
Compatibility and Accessories
The contactor is designed for mounting on a plate or DIN rail, allowing flexible integration into enclosures. It is equipped with screw terminals suitable for cable cross-sections of 1.5 to 4 mm² (rigid) and 0.75 to 4 mm² (flexible without cable end). For flexible cables with cable ends, the permissible cross-section is 0.34 to 2.5 mm². The tightening torque is between 0.8 and 1.3 Nm, and the terminals are tightened using a Phillips screwdriver No. 2 or flat screwdrivers with Ø 6 mm. Compatible accessories include motor protection circuit breakers such as GV2LE08 or GV2ME10, motor protection relays such as LR2K0306, auxiliary switches such as LA1KN22 or LA1KN40, and overvoltage limiters such as LA4KE1B. These components can be combined to extend protection and control functions.
Mounting and Installation
Mounting is performed on a DIN rail or flat plate. The pre-assembled reversing circuit reduces installation time and minimizes wiring errors. The screw terminals ensure a secure and reliable connection of the conductors. The mechanical interlock ensures that both contactors cannot be switched on simultaneously, which is essential for reversing drives to avoid short circuits and mechanical stress.
Operational Advantages
The reversing contactor LP2K0601BD offers high reliability due to its long service life and robust construction. The integrated mechanical interlock and pre-wired reversing circuit reduce installation time and enhance safety. The 24 V DC coil enables easy integration into modern control systems. Certifications according to EN/IEC 60947-4-1, UL, CSA, CCC, EAC, CE, and UKCA, as well as compliance with RoHS/REACH, guarantee adherence to international safety and environmental standards. The device is designed for industrial environments and meets requirements for electrical safety and reliability.
Safety Level and Standards
The device complies with standards EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No. 60947-4-1, and JIS C8201-4-1. Product certifications include CB Scheme, CCC, UL, CSA, EAC, CE, and UKCA. The safety level according to EN/ISO 13849-1 is B10d = 1,369,863 cycles at rated load and B10d = 20,000,000 cycles at mechanical load, highlighting the high reliability of the device. The associated fuse rating is 25 A gG, enabling selection of the appropriate fuse for protecting the contactor.
Connections and Terminals
Connections are made via screw terminals designed for various cable cross-sections. The terminals are suitable for rigid cables of 1.5 to 4 mm², flexible cables without cable ends of 0.75 to 4 mm², and flexible cables with cable ends of 0.34 to 2.5 mm². When using two cables, the permissible cross-section is 1.5 to 4 mm² (rigid) and 0.75 to 4 mm² (flexible without cable ends), as well as 0.34 to 1.5 mm² (flexible with cable ends). The tightening torque is 0.8 to 1.3 Nm, and the terminals are tightened using a Phillips screwdriver No. 2 or flat screwdrivers with Ø 6 mm. The terminals are designed to ensure a secure and durable connection.
Operating Parameters and Performance
The rated operating voltage for the coil is 24 V DC. The operating voltage range is between 0.8 and 1.15 times the rated voltage. The operating time is 30–40 ms for coil energization and NO contact closing, and 10 ms for coil de-energization and NO contact opening. The rated short-time current withstand is 90 A for 1 second, 85 A for 5 seconds, 80 A for 10 seconds, 60 A for 30 seconds, 45 A for 1 minute, 40 A for 3 minutes, and 20 A for at least 15 minutes in the main circuit. In the signaling circuit, the rated short-time current withstand is 80 A for 1 second, 90 A for 500 ms, and 110 A for 100 ms. The average impedance is 3 MΩ at 20 A and 50 Hz in the main circuit.