| Complementary |
| Compatibility code | LP1D |
| Pole contact composition | 2 NO + 2 NC |
| Protective cover | With |
| [Ith] conventional free air thermal current | 60 A (at 60 °C) for power circuit |
| Irms rated making capacity | 800 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 800 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 72 A 40 °C - 10 min for power circuit; 165 A 40 °C - 1 min for power circuit; 320 A 40 °C - 10 s for power circuit; 720 A 40 °C - 1 s for power circuit |
| Associated fuse rating | 80 A gG at |
| Average impedance | 1.5 mOhm - Ith 60 A 50 Hz for power circuit |
| Power dissipation per pole | 5.4 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 10 Mcycles |
| Electrical durability | 1.4 Mcycles 60 A AC-1 at Ue |
| Control circuit type | DC DC standard |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1...0.3 Uc (-40…55 °C):drop-out DC; 0.85...1.1 Uc (-40…55 °C):operational DC |
| Inrush power in W | 22 W (at 20 °C) |
| Hold-in power consumption in W | 22 W at 20 °C |
| Operating time | 4...19 ms opening; 12...26 ms closing |
| Time constant | 75 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Tightening torque | Power circuit: 8 N.m - on screw clamp terminals - cable 25…35 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 5 N.m - on screw clamp terminals - cable 1…25 mm² hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1 |
| Product certifications | UL; CSA; CCC; EAC; UKCA; CB; DNV-GL; RINA; BV; LROS (Lloyds register of shipping) |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Shocks contactor open (8 Gn for 11 ms) ; Shocks contactor closed (10 Gn for 11 ms) ; Vibrations contactor opened (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 182 mm |
| Net weight | 2.21 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LP1D |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 60 A (at |
| [Uc] control circuit voltage | 110 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 22.5 cm |
| Package 1 Width | 14.8 cm |
| Package 1 Length | 18.0 cm |
| Package 1 Weight | 2.4 kg |
The contactor LP1D40008FD from the TeSys series by Schneider Electric is an industrial power switch designed for use in electrical installations with resistive loads. It features four poles (4P) and a contact configuration of two normally open and two normally closed contacts (2S+2Ö), making it suitable for applications with complex control requirements. The rated operational voltage is 440 V, and the rated operational current is 60 A, with usage category AC-1 defined. The control circuit voltage is 110 V DC, enabling use in systems with direct current supply. The coil is equipped with integrated bidirectional surge-limiting diode suppressor technology, which increases the coil's lifespan and reduces interference with control devices caused by voltage spikes.
Applications
This contactor is designed for use in industrial installations, particularly in applications with resistive loads, such as heaters, resistance brakes, or other consumers that do not represent inductive or capacitive loads. Usage category AC-1 specifies that the device is designed for operation with purely resistive loads. The rated insulation voltage is 690 V, allowing use in installations with higher voltages, and complies with standards IEC 60947-4-1 as well as UL and CSA. Overvoltage category III and pollution degree 3 indicate that the device is designed for environments with increased risk of overvoltage and contamination, such as production plants or industrial machinery.
Functions and Equipment in Detail
The device features a safety cover that prevents access to contacts and the coil during operation, thereby enhancing safety. The contact configuration of 2S+2Ö enables integration into complex control circuits where multiple switching operations must occur in parallel or sequentially. The rated making capacity is 800 A at 440 V, ensuring safe switching capability under high inrush currents. The rated breaking capacity is also designed for 800 A at 440 V, confirming the contactor's ability to interrupt load currents under these conditions.
Technology Explained Simply
The contactor coil is operated at 110 V DC, with the operating voltage required to be between 0.85 and 1.1 times the nominal voltage to ensure secure engagement. The release voltage is between 0.1 and 0.3 times the nominal voltage, enabling secure release of the contactor during voltage fluctuations. The pickup power is 22 W at 20 °C, and the holding power consumption is also 22 W, indicating constant power draw during operation. The operating time is 4 to 19 ms for opening and 12 to 26 ms for closing, ensuring fast responsiveness of the device. The time constant of 75 ms influences switching behavior and stability of the contactor under dynamic load changes.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include auxiliary switch blocks such as LADN04 (4Ö) or LADN22 (2S+2Ö), which provide additional switching functions for control circuits. Time delay blocks such as LADT2 (1S+1Ö, 0.10–30.00 s) or LADT4 (1S+1Ö, 10.00–180.00 s) enable delayed switching operations. Additionally, overvoltage limiters such as LA4-DC3U (24–250 V DC) are available to protect the coil from transient voltage spikes. Mounting is possible either on a plate or on a rail, enabling flexible installation in enclosures.
Mounting and Installation
Mounting is done on a plate or rail, with screw terminals for power circuits requiring a torque of 5 Nm (for cables 1–25 mm²) or 8 Nm (for cables 25–35 mm²). Control circuit terminals require a torque of 1.7 Nm, with installation performed using either a flat screwdriver Ø 6 or a Phillips No. 2. The device ambient temperature range is -40 to 60 °C, with performance reduction required at temperatures from 60 to 70 °C. The operating altitude is limited to 0 to 3,000 m, allowing use in high-altitude installations or aircraft. The front protection rating IP20 corresponds to IEC 60529 and protects against finger contact, but not against dust or water.
Advantages in Operation
The mechanical life is 10 million switching cycles, while the electrical life at 60 A AC-1 and nominal voltage is 1.4 million switching cycles. The maximum operating rate is 3,600 switching operations per hour at 60 °C, enabling high load capacity in continuously operated installations. Flame retardancy V1 according to UL 94 and fire resistance of 850 °C according to IEC 60695-2-1 enhance safety in case of fire. Mechanical robustness against shocks (8 Gn open, 10 Gn closed) and vibrations (2 Gn open, 4 Gn closed) ensures reliable function even in vibrating environments. Certifications according to UL, CSA, CCC, EAC, UKCA, CB, DNV-GL, RINA, BV, and LROS (Lloyds Register of Shipping) confirm compliance with international safety and quality standards.