| Complementary |
| [Ithe] conventional enclosed thermal current | 9 A |
| Cable entry number | 2 ISO20 top; 2 ISO20 bottom |
| Width | 88 mm |
| Height | 166 mm |
| Depth | 135 mm |
| Net weight | 0.92 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | IEC 60947-4-1 |
| Product certifications | CB Scheme; CE; UKCA |
| IP degree of protection | IP65 conforming to IEC 60529 |
| IK degree of protection | IK07 conforming to IEC 60529 |
| Ambient air temperature for operation | -5…40 °C |
| Material | Polycarbonate |
| Environmental characteristic | Standard environment |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product name | TeSys LE |
| Product or component type | Enclosed DOL starter |
| Device short name | LE1D |
| Device application | Standard |
| Utilisation category | AC-3 |
| Device composition | Thermal overload relay ordered separately; Contactor |
| Control type | Push-button reset blue R; Selector switch 3 positions automatic start/stop/manual start I-O-II |
| Motor power kW | 4 kW at 380/400 V AC 50/60 Hz; 4 kW at 415 V AC 50/60 Hz; 4 kW at 440 V AC 50/60 Hz; 2.2 kW at 220/230 V AC 50/60 Hz; 5.5 kW at 500 V AC 50/60 Hz; 5.5 kW at 660/690 V AC 50/60 Hz |
| [Uc] control circuit voltage | 400 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 15.700 cm |
| Package 1 Width | 17.500 cm |
| Package 1 Length | 20.700 cm |
| Package 1 Weight | 886.000 g |
The Schneider Electric direct starter type LE1D09V7A09 belongs to the TeSys series and is designed as an encapsulated direct starter for standard applications in industrial environments. The device is used for controlling and protecting electric motors and enables direct-on-line (DOL) starting without additional starting control. It is designed for usage category AC-3, which is typical for drives with medium load and frequent start/stop operation. The control circuit voltage is 400 V AC at 50/60 Hz, enabling control via standard networks in industrial environments. The device features a selector switch with three positions: automatic start, stop, and manual start, as well as a blue push-button for reset. Operating conditions include an ambient temperature range of -5 °C to 40 °C, allowing use in indoor and protected outdoor environments.
Applications
The direct starter is suitable for controlling electric motors across various voltage ranges. Motor power ratings are 4 kW at 380/400 V, 415 V, and 440 V AC, 2.2 kW at 220/230 V AC, and 5.5 kW at 500 V and 660/690 V AC. This range makes the device suitable for a variety of drive systems in manufacturing, packaging, or building automation. The combination of contactor and separate motor protection relay (thermal overload protection) allows flexible adaptation to different motor powers and protection requirements.
Functions and Equipment in Detail
This enables a modular configuration, allowing the user to select the appropriate relay based on motor current and protection requirements. The actuation method includes a selector switch with three positions (automatic start, stop, manual start) and a blue push-button for reset. Cable entry is via two ISO20 connectors at the top and two at the bottom, enabling flexible mounting and wiring. Dimensions are 88 mm width, 166 mm height, and 135 mm depth, allowing installation in standard control panels.
Technology Explained Simply
The direct starter operates on the principle of direct-on-line (DOL) starting, where the motor is connected directly to the full rated voltage. This is suitable for motors that do not require special starting conditions. Protection is provided by an external motor protection relay, which handles thermal overload protection. Control is via a 400 V AC network, enabling easy integration into existing control systems. The IP65 protection rating means the device is dust-tight and protected against water jets, allowing use in outdoor or damp environments. The IK07 protection rating provides resistance against mechanical impacts such as shocks or vibrations.
Compatibility and Accessories
The device is compatible with various motor protection relays from the LRD series, which can be selected based on the required thermal current (Ithe). Available models include, for example, LRD02 (0.16–0.25 A), LRD05 (0.63–1 A), LRD07 (1.6–2.5 A), LRD10 (4–6 A), and LRD14 (7–10 A). Additionally, motor protection switches from the GV2L series are available, such as GV2L05 (1 A), GV2L07 (2.5 A), GV2L10 (6.3 A), and GV2L14 (10 A). These components can be combined as needed to adapt protection functions to specific motor and operating conditions.
Mounting and Installation
The direct starter is mounted in standard control panels and features ISO20 cable entry at the top and bottom. Mounting is done via screw fastening, with specified torque values (0.9 N·m) to be observed. The device is made of polycarbonate, ensuring high mechanical stability and weather resistance. Installation follows the standards defined in IEC 60947-4-1, which specify requirements for contactors and direct starters.
Advantages in Operation
The combination of contactor and separate motor protection relay offers high flexibility in configuration. The IP65 and IK07 protection ratings enable robust use in demanding environments. Simple operation via selector switch and push-button reduces error susceptibility. The compact design and standard dimensions facilitate integration into existing control systems. Certifications CE, UKCA, and CB regulation ensure compliance with European and international safety standards.