| Complementary |
| Tightening torque | Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6...8 mm; Control circuit: 1.2 N.m - on connector - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on connector - with screwdriver Philips No 2 |
| Mechanical durability | 8 Mcycles |
| Maximum operating rate | 30 cyc/h 60 °C |
| Starting time | 30 s |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | Drop-out: 0.3...0.5 Uc at 50/60 Hz (at |
| Inrush power in VA | 280…350 VA 60 Hz cos phi 0.8 (at 20 °C); 280…350 VA 50 Hz cos phi 0.8 (at 20 °C) |
| Hold-in power consumption in VA | 2…18 VA 60 Hz cos phi 0.3 (at 20 °C); 2…18 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 3…8 W at 50/60 Hz |
| Auxiliary contacts type | Mechanically linked conforming to IEC 60947-5-1 3 x 1 NO + 1 NC; Mirror contact conforming to IEC 60947-4-1 3 x 1 NC |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching current | 5 mA for signalling circuit |
| minimum switching voltage | 17 V for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Width | 450 mm |
| Height | 555 mm |
| Depth | 205 mm |
| Net weight | 11.8 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Insulation resistance | > 10 MOhm for signalling circuit |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Pollution degree | 3 |
| Ambient air temperature for storage | -60…80 °C |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor closed: 15 Gn for 11 ms; Shocks contactor open: 6 Gn for 11 ms |
| Main |
| Range | TeSys |
| Product name | TeSys Deca |
| Product or component type | Star delta starter |
| Device short name | LC3D |
| Contactor application | Motor control |
| Utilisation category | AC-3 |
| Device presentation | Pre-wired |
| Poles description | 3 x 3P |
| power pole contact composition | 3 x 3 NO |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 115 A (at |
| Motor power kW | 110 kW at 380/400 V AC 50/60 Hz; 110 kW at 415 V AC 50/60 Hz; 110 kW at 440 V AC 50/60 Hz; 63 kW at 220/230 V AC 50/60 Hz |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Auxiliary contact composition | 1 NC for KM2 line contactor; 1 NO for KM3 delta contactor |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Overvoltage category | III |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 1000 V conforming to IEC 60947-1 |
| Electrical durability | 0.95 Mcycles 115 A AC-3 at Ue |
| Mounting support | Plate |
| Standards | UL 508; EN 60947-5-1; IEC 60947-5-1; IEC 60947-4-1; EN 60947-4-1; CSA C22.2 No 14 |
| Product certifications | GOST; RINA; BV; DNV; CSA; UL; GL; LROS (Lloyds register of shipping); CCC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 35.0 cm |
| Package 1 Width | 67.0 cm |
| Package 1 Length | 77.0 cm |
| Package 1 Weight | 11.8 kg |
Standard contactors 0.06 -75 kW In addition to an attractive and functional design, the TeSys D contactors offer quick and easy installation with a narrow width of 45 or 55 mm. They meet international standards. The power sizes 40 to 65 A are equipped with EverLink terminals. These are patented and ensure a reliable and permanent connection.