| Complementary |
| Assembly style | Ready assembled |
| Coil technology | Without built-in bidirectional peak limiting diode suppressor |
| Interlocking type | Mechanical |
| Control circuit voltage limits | Drop-out: >= 0.20 Uc at 50/60 Hz (at |
| [Ui] rated insulation voltage | Control circuit: 690 V conforming to BS 5424; Control circuit: 690 V conforming to IEC 60947; Power circuit: 690 V conforming to BS 5424; Power circuit: 690 V conforming to IEC 60947; Power circuit: 690 V conforming to NF C 20-040; Control circuit: 750 V conforming to VDE 0110 group C; Power circuit: 750 V conforming to VDE 0110 group C; Control circuit: 600 V conforming to CSA C22.2 No 14; Power circuit: 600 V UL 508 certified conforming to CSA C22.2 No 14 |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Mounting support | Plate; Rail |
| Flame retardance | Class C2 conforming to NF F 16-101; Class C2 conforming to NF F 16-102; V1 conforming to UL 94 |
| Tightening torque | Power circuit: - cable 0.34…1.5 mm² - with screwdriver Philips No 2 flat screw head M6; Power circuit: - cable 0.34…2.5 mm² - with screwdriver Philips No 2 flat screw head M6; Power circuit: - cable 0.75…4 mm² - with screwdriver Philips No 2 flat screw head M6; Power circuit: - cable 1.5…4 mm² - with screwdriver Philips No 2 flat screw head M6 |
| [Ue] rated operational voltage | Power circuit: |
| [Ith] conventional free air thermal current | 10 A (at 50 °C) for control circuit; 20 A (at 50 °C) for power circuit |
| Irms rated making capacity | 110 A at 690 V AC for control circuit conforming to IEC 60947; 110 A at 690 V AC for power circuit conforming to IEC 60947; 110 A at 690 V AC for power circuit conforming to NF C 63-110 |
| Associated fuse rating | 10 A gG for control circuit conforming to IEC 60947; 10 A gG for control circuit conforming to VDE 0660; 25 A gG at |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| Inrush power in VA | 30 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.5 VA 50/60 Hz (at 20 °C) |
| Operating time | 10...20 ms coil de-energisation and NO opening; 15...25 ms coil de-energisation and NC opening; 5...15 ms coil energisation and NC opening; 10...20 ms coil energisation and NO closing |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 5000000 cycles |
| Maximum operating rate | 3600 cyc/h |
| Minimum switching current | 5 mA for control circuit |
| Minimum switching voltage | 17 V for control circuit |
| Insulation resistance | > 10 MOhm for control circuit |
| Height | 58 mm |
| Width | 90 mm |
| Depth | 57 mm |
| Net weight | 0.39 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| IP degree of protection | IP2X conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068 |
| Ambient air temperature for operation | -25…50 °C |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Shock resistance | 10 gn contactor closed; 6 gn contactor opened |
| Vibration resistance | 2 gn 5…300 Hz contactor opened; 4 gn 5…300 Hz contactor closed |
| Heat dissipation | 1.3 W at 50/60 Hz for control circuit |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range of product | TeSys K |
| Product or component type | Reversing contactor |
| Device short name | LC2K |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-1; AC-3e |
| Control circuit type | AC |
| Coil type | AC 50/60 Hz |
| Poles description | 3P |
| Pole contact composition | 3 NO |
| [Ie] rated operational current | Power circuit: 20 A AC AC-1 (at |
| Motor power kW | 2.2 kW at 220...230 V AC 50/60 Hz; 4 kW at 380...415 V AC 50/60 Hz; 4 kW at 440/500 V AC 50/60 Hz; 4 kW at 660/690 V AC 50/60 Hz |
| Motor power hp | 2 hp at 200/208 V AC 60 Hz conforming to CSA; 2 hp at 200/208 V AC 60 Hz conforming to UL; 3 hp at 230/240 V AC 60 Hz conforming to CSA; 3 hp at 230/240 V AC 60 Hz conforming to UL; 5 hp at 460/480 V AC 60 Hz conforming to CSA; 5 hp at 460/480 V AC 60 Hz conforming to UL; 5 hp at 575/600 V AC 60 Hz conforming to CSA; 5 hp at 575/600 V AC 60 Hz conforming to UL |
| Auxiliary contact composition | 1 NO |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| Quantity per set | Set of 10 |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.000 cm |
| Package 1 Width | 6.000 cm |
| Package 1 Length | 9.000 cm |
| Package 1 Weight | 350.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 15 |
| Package 2 Height | 6.500 cm |
| Package 2 Width | 29.500 cm |
| Package 2 Length | 29.500 cm |
| Package 2 Weight | 5.450 kg |
| Unit Type of Package 3 | S03 |
| Number of Units in Package 3 | 30 |
| Package 3 Height | 30.000 cm |
| Package 3 Width | 30.000 cm |
| Package 3 Length | 40.000 cm |
| Package 3 Weight | 10.950 kg |
Mini contactors 0.06 - 5.5 kW TeSys K offers you a complete range of mini contactors with an optimal ratio of performance to compactness and seamless integration into your applications.