| Additional features |
| Control circuit voltage limits | Operation: 0.8 - 1.15 Uc (at |
| Input power in VA | 30 VA (at 20 °C) |
| Hold power consumption in VA | 4.5 VA (at 20 °C) |
| Heat emission | 1,3 W |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys |
| Product name | TeSys K |
| Product or component type | Reversing contactor |
| Device short name | LC2K |
| Device application | Control |
| Application of contactor | resistive load |
| Application category | AC-1 |
| Device representation | Pre-fabricated with reversing power busbar |
| Pole description | 4P |
| Pole contact composition | 4 S |
| [Ue] Rated operational voltage | Power circuit: 690 V AC 50/60 Hz |
| [Ie] rated operational current | 20 A (at |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| [Uimp] Rated impulse voltage withstand | 8 kV |
| Over voltage category | III |
| [Ith] conventional thermal current in free air | 20 A (at 60 °C) for circuit |
| [Irms] Rated making capacity | 110 A AC for circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 220 - 230 V corresponds to IEC 60947; 110 A at 380 - 400 V corresponds to IEC 60947; 110 A at 415 V corresponds to IEC 60947; 110 A at 440 V corresponds to IEC 60947; 80 A at 500 V corresponds to IEC 60947; 70 A at 660 - 690 V corresponds to IEC 60947 |
| [Icw] rated short-time current withstand | 90 A 50 °C - 1 s for circuit; 85 A 50 °C - 5 s for circuit; 80 A 50 °C - 10 s for circuit; 60 A 50 °C - 30 s for circuit; 45 A 50 °C - 1 min for circuit; 40 A 50 °C - 3 min for circuit; 20 A 50 °C - >= 15 min. for circuit |
| Associated fuse | 25 A gG at |
| Average impedance | 3 MOhm - Ith 20 A 50 Hz for circuit |
| [Ui] Rated insulation voltage | Circuit: 600 V corresponds to UL 508; Circuit: 690 V corresponds to IEC 60947-4-1; Circuit: 600 V corresponds to CSA C22.2 No. 14 |
| Electrical lifetime | 0.16 Mcycles 20 A AC-1 at Ue |
| Locking type | Mechanical |
| Mounting bracket | Plate; rail |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No. 60947-4-1; JIS C8201-4-1 |
| Product certifications | CB certification; CCC; UL; CSA; EAC; CE; UKCA |
| Connections - terminals | Screw terminals 1 cable(s) 1.5…4 mm² solid; screw terminals 1 cable(s) 0.75…4 mm² stranded without ferrule; screw terminals 1 cable(s) 0.34…2.5 mm² stranded with ferrule; screw terminals 2 cable(s) 1.5…4 mm² solid; screw terminals 2 cable(s) 0.75…4 mm² stranded without ferrule; screw terminals 2 cable(s) 0.34…1.5 mm² stranded with ferrule |
| Tightening moment | 0.8…1.3 Nm - on screw terminals Phillips No. 2; 0.8…1.3 Nm - on screw terminals flat Ø 6; 0.8…1.3 Nm - on screw terminals position No. 2 |
| Operating time | 10 - 20 ms coil energizing and NO closing; 10 - 20 ms coil de-energizing and NO opening |
| Security level rating | B10d = 1369863 cycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load corresponds to EN/ISO 13849-1 |
| Mechanical life | 5 Mcycles |
| Max. operating rate | 3600 cyc/h |
| Mounting |
| Degree of protection (IP) | IP20 corresponds to VDE 0106 |
| Coating | TC corresponds to IEC 60068; TC corresponds to DIN 50016 |
| Operating ambient temperature | -25…50 °C |
| Ambient temperature during storage | -50…80 °C |
| Operating altitude | 2,000 m without derating |
| Flame retardancy | V1 corresponds to UL 94; Requirement 2 corresponds to NF F 16-101; Requirement 2 corresponds to NF F 16-102 |
| Height | 58 mm |
| Width | 90 mm |
| Depth | 57 mm |
| Product weight | 0,38 kg |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,9 cm |
| VPE 1 width | 6,5 cm |
| VPE 1 length | 9,2 cm |
| Packaging weight (Lbs) | 358,0 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 25 |
| VPE 2 height | 15,0 cm |
| VPE 2 width | 30,0 cm |
| VPE 2 length | 40,0 cm |
| VPE 2 weight | 9,342 kg |
4-pole (4 NO) TeSys K changeover contactor for AC-1 load applications up to 20 A/690 V. It offers 24 V 50/60 Hz AC coils, screw terminal connection, pre-wired mains switching circuit, mechanical interlock. Without built-in auxiliary switches, additional plug-in auxiliary switch blocks can be added on the front (to be ordered separately). Compact DIN rail mounting and screw fixing ensure reliability and durability in standard applications. Certified with multiple standards (IEC, UL, CSA, CCC, EAC) and Green Premium (RoHs/Reach).