| Complementary |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Time constant | 28 ms |
| Inrush power in W | 5.4 W (at 20 °C) |
| Hold-in power consumption in W | 5.4 W at 20 °C |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10; conforming to IEC 60947-1 Annex Q category D |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Pollution degree | 3 |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor open: 10 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms |
| Height | 77 mm |
| Width | 90 mm |
| Depth | 95 mm |
| Net weight | 1.037 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys D; TeSys Deca |
| Product or component type | Reversing contactor |
| Device short name | LC2D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-1; AC-3; AC-3e |
| Device presentation | Preassembled with reversing power busbar |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 18 A (at |
| Motor power kW | 4 kW at 220...230 V AC 50...60 Hz; 7.5 kW at 380...400 V AC 50...60 Hz; 9 kW at 415 V AC 50...60 Hz; 9 kW at 440 V AC 50...60 Hz; 10 kW at 500 V AC 50...60 Hz; 10 kW at 660...690 V AC 50...60 Hz |
| Motor power hp | 1 hp at 115 V AC 60 Hz for 1 phase motors; 3 hp at 230/240 V AC 60 Hz for 1 phase motors; 5 hp at 200/208 V AC 60 Hz for 3 phases motors; 5 hp at 230/240 V AC 60 Hz for 3 phases motors; 10 hp at 460/480 V AC 60 Hz for 3 phases motors; 15 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Control circuit type | DC standard |
| [Uc] control circuit voltage | 24 V DC |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 32 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 300 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 300 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 40 A 40 °C - 10 min for power circuit; 84 A 40 °C - 1 min for power circuit; 145 A 40 °C - 10 s for power circuit; 240 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 50 A gG at |
| Average impedance | 2.5 mOhm - Ith 32 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Electrical durability | 1.65 Mcycles 18 A AC-3 at Ue |
| Power dissipation per pole | 0.8 W AC-3; 2.5 W AC-1; 0.8 W AC-3e |
| Front cover | With |
| Interlocking type | Mechanical |
| Mounting support | Rail; Plate |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60335-2-40:Annex JJ; IEC 60335-1 |
| Product certifications | DNV; CSA; CCC; UL; GL; LROS (Lloyds register of shipping); BV; RINA; GOST; UKCA |
| Operating time | 53.55...72.45 ms closing; 16...24 ms opening |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Maximum operating rate | 3600 cyc/h 60 °C |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 9.600 cm |
| Package 1 Width | 11.700 cm |
| Package 1 Length | 14.200 cm |
| Package 1 Weight | 1.133 kg |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.101 kg |
The LC2D18BD reversing contactor from the TeSys Deca series by Schneider Electric is a standard contactor for motor control and operation of resistive loads. It is designed for use in industrial plants where reliable and safe control of electric motors is required. The device features a 3-pole power circuit (3P) and is equipped with an auxiliary contact block consisting of one normally open and one normally closed contact (1S + 1Oe). Control is achieved via a coil with a rated voltage of 24 V DC, making it suitable for applications with DC control. The pre-assembled reversing power busbar enables simple and quick installation, especially in systems requiring direction reversal.
Applications
The contactor is designed for use in various application categories, including AC-1 (resistive load), AC-3 (motors with direct start) and AC-3e (motors with direct start and electric brake). It is therefore suitable for a wide range of industrial applications, such as controlling drives in material handling, machine building or packaging technology. The motor powers that can be operated with this contactor range from 4 kW at 220–230 V AC to 10 kW at 660–690 V AC, depending on voltage. In the USA and Canada, the corresponding powers are 1 hp at 115 V AC to 15 hp at 575/600 V AC, with separate specifications for single- and three-phase motors.
Functions and Equipment in Detail
The device is equipped with a front cover that enables mechanical interlocking, thereby increasing safety during operation. The auxiliary contacts (1S + 1Oe) are arranged on the front and allow for easy integration into control systems. The main circuit contacts are rated for an operational current of 18 A, with the conventional thermal current rating (Ith) in the circuit being 32 A (at 60 °C). The control circuits are rated for 10 A (at 60 °C). The rated transient voltage withstand is 6 kV, complying with IEC 60947, and the overvoltage category is III. The rated insulation voltage is 690 V for the main circuit and 600 V for the control circuit, with approvals according to IEC, UL, CSA and other standards.
Technology Explained Simply
The electrical life expectancy is 1.65 million switching cycles at 18 A and AC-3 operation, ensuring high operational reliability and longevity. The power loss per pole is 0.8 W for AC-3 and AC-3e, and 2.5 W for AC-1, indicating efficient heat generation. The operating time is 53.55 to 72.45 ms for closing and 16 to 24 ms for opening, enabling fast responsiveness. The rated breaking capacity is 300 A at 440 V, highlighting the contactor’s ability to safely interrupt short-circuit currents. The rated short-time current withstand is defined for various durations, with values for the main circuit up to 240 A at 1 s and for the control circuit up to 140 A at 100 ms.
Compatibility and Accessories
The contactor is equipped with a pre-assembled reversing power busbar, enabling easy installation. It can be combined with various accessories, including freewheeling diodes (LAD4DDL), time blocks (LADT2), motor protection relays (LRD21), auxiliary switch blocks (LADN22, LADN11), interlocking blocks (LAD6K10B) and motor protection switches (GV2LE20, GV2ME20). These components extend the functionality of the contactor and allow individual adaptation to specific requirements, such as integration into safety or control systems.
Mounting and Installation
Mounting is done either on a rail or directly on a plate. The tightening torques for the screw terminals are 1.7 Nm for both main and control circuits, with 2.5 Nm also specified for main circuits at higher powers. The terminals are designed for use with flat screwdrivers (Ø 6) and Phillips screwdrivers (No. 2). The width is 55 mm, allowing for compact placement in enclosures. The device dimensions are 90 mm (width), 77 mm (height) and 95 mm (depth).
Operational Advantages
The contactor offers high operational safety through mechanical interlocking and the pre-assembled reversing power busbar. Compliance with international standards such as EN 60947-4-1, IEC 60947-4-1, UL 60335-2-40:Annex JJ and CSA C22.2 No. 14 ensures reliability and compatibility in various markets. The integrated auxiliary contacts enable easy integration into control systems, and the high electrical life expectancy reduces maintenance requirements. The use of EverLink terminals for power ratings from 40 A (not applicable for 18 A) ensures a reliable and durable connection, although the LC2D18BD model does not fall into this category. Certifications according to DNV, CSA, CCC, UL, GL, LROS, BV, RINA, GOST and UKCA underscore the international recognition of the product.