| Complementary |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10; conforming to IEC 60947-1 Annex Q category D |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Pollution degree | 3 |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor open: 10 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms |
| Height | 77 mm |
| Width | 90 mm |
| Depth | 86 mm |
| Net weight | 0.697 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys D; TeSys Deca |
| Product or component type | Reversing contactor |
| Device short name | LC2D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-1; AC-3; AC-3e |
| Device presentation | Preassembled with reversing power busbar |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 25 A (at |
| Motor power kW | 3 kW at 220...230 V AC 50 Hz; 5.5 kW at 380...400 V AC 50 Hz; 5.5 kW at 415 V AC 50 Hz; 5.5 kW at 440 V AC 50 Hz; 7.5 kW at 500 V AC 50 Hz; 7.5 kW at 660...690 V AC 50 Hz |
| Motor power hp | 1 hp at 115 V AC 60 Hz for 1 phase motors; 2 hp at 230/240 V AC 60 Hz for 1 phase motors; 3 hp at 200/208 V AC 60 Hz for 3 phases motors; 3 hp at 230/240 V AC 60 Hz for 3 phases motors; 7.5 hp at 460/480 V AC 60 Hz for 3 phases motors; 10 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 115 V AC 50/60 Hz |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 25 A (at 60 °C) for power circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 40 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Electrical durability | 2 Mcycles 12 A AC-3 at Ue |
| Power dissipation per pole | 1.56 W AC-1; 0.36 W AC-3; 0.36 W AC-3e |
| Front cover | With |
| Interlocking type | Mechanical |
| Mounting support | Plate; Rail |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60335-2-40:Annex JJ; IEC 60335-1 |
| Product certifications | DNV; CSA; CCC; UL; GL; LROS (Lloyds register of shipping); BV; RINA; GOST; UKCA |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Maximum operating rate | 3600 cyc/h 60 °C |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.000 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 11.300 cm |
| Package 1 Weight | 808.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.211 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 48 |
| Package 3 Height | 45.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 49.688 kg |
The
reversing contactor LC2D12FE7 from the
TeSys Deca series by
Schneider Electric is a pre-assembled contactor system for controlling electric motors and resistive loads. It is specifically designed for use in industrial applications where safe and reliable switching of motor loads is required. The device features a
3-pole main contact configuration (3P) and integrated auxiliary contacts in the configuration
1 S + 1 Ö, making it suitable for complex control tasks. The
control circuit voltage is 115 V AC at 50/60 Hz, enabling its use in standard AC control systems.
Applications
This contactor is designed for
motor control and operation with
resistive loads. It covers usage categories
AC-1, AC-3, and AC-3e, allowing application with various load types, including the control of three-phase motors. The motor power rating is up to
5.5 kW at 380–400 V AC 50 Hz and
7.5 kW at 660–690 V AC 50 Hz, with exact values varying depending on voltage and frequency. In the USA and Canada, it is certified for motors up to
10 hp at 575/600 V AC 60 Hz. The
rated operating voltage for the circuit is defined according to standards, with the
rated insulation voltage for the circuit being
690 V and for the signal circuit also
690 V as per IEC 60947-1. The
overvoltage category III indicates suitability for industrial installations with high electrical stress.
Functions and Features in Detail
The device is configured as a
reversing contactor combination, meaning it is pre-assembled with an
integrated reversing power busbar. This enables quick and secure installation in applications requiring motor direction change. The
auxiliary contacts (1 S + 1 Ö) are instantaneous and serve for signal transmission in control circuits. The
front cover is integrated, providing enhanced safety and protection against accidental contact with the contacts. The
interlocking type is mechanical, ensuring secure and reliable interlocking between contactors in reversing circuits.
Technical Details Explained
The
rated making capacity is
250 A at 440 V for the circuit, demonstrating the contactor’s ability to safely interrupt high inrush currents during motor start. The
rated breaking capacity is also specified as
250 A at 440 V, indicating the maximum current the device can safely interrupt. The
rated short-time withstand current is defined for various durations, with the maximum value being
210 A for 1 second. The
electrical life is
2 million switching cycles at 12 A AC-3, indicating high operational reliability and longevity. The
power loss per pole is
0.36 W for categories AC-3 and AC-3e, indicating efficient heat dissipation and low energy losses. The
operating time is
12–22 ms for closing and
4–19 ms for opening, ensuring fast response of the contactor.
Compatibility and Accessories
The contactor is designed for mounting on
plate or rail, enabling flexible integration into existing control panels. It is equipped with
EverLink terminals, ensuring reliable and durable connections. Compatible accessories include
auxiliary switch blocks such as the
LAD8N11 (1S+1Ö) or
LADN22 (2S+2Ö),
time blocks such as the
LADT2,
motor protection relays such as the
LRD16, and
protective covers such as the
LAD9ET1S. These components can be used to extend functionality and enhance system safety. The
associated fuse rating for the signal circuit is
10 A gG, representing the necessary protection for the control circuit.
Mounting and Installation
Mounting is done on a
plate or rail, with the tightening torque for all screw terminals being
1.7 Nm. This applies to both the main circuit and control circuit and can be achieved using a flathead screwdriver (Ø 6 mm) or a Phillips screwdriver (No. 2). The narrow width of
45 or 55 mm allows for compact placement in enclosures. The
front cover is already integrated, enhancing safety during installation and operation.
Operational Advantages
The contactor offers
fast and easy installation thanks to its pre-assembled configuration and integrated front cover. The
EverLink terminals ensure durable and reliable connections, increasing serviceability. The
mechanical interlock ensures safe operation in reversing circuits. The
high electrical life and
low power loss contribute to system efficiency and longevity. Certifications according to
IEC 60947-4-1, EN 60947-4-1, CSA C22.2 No. 14, UL 60335-2-40:Annex JJ, and other standards guarantee compliance with international safety and quality standards. The
rated impulse withstand voltage of 6 kV and
overvoltage category III make the device suitable for use in industrial environments with high electrical stress. The
safety level rating (B10d = 1,369,863 cycles) demonstrates the contactor’s reliability under rated load conditions.
Standards and Certifications
The device complies with standards
IEC 60947-4-1, EN 60947-4-1, CSA C22.2 No. 14, UL 60335-2-40:Annex JJ, IEC 60335-1 and is certified by
DNV, CSA, CCC, UL, GL, LROS (Lloyds Register of Shipping), BV, RINA, GOST, UKCA. These certifications confirm suitability for use in various industries, including shipping and industrial automation.
Conclusion
The
LC2D12FE7 is a robust, reliable, and efficient
reversing contactor from the
TeSys Deca series by
Schneider Electric, designed for motor and resistive load control in industrial applications. It offers high electrical life, low power loss, fast operating times, and features mechanical interlocking and an integrated front cover. The pre-assembled configuration with reversing power busbar and EverLink terminals simplifies installation and enhances reliability. Compliance with international standards and certifications makes it suitable for use across various industries. Compatibility with various accessories extends system functionality and safety.