| Complementary |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Climatic withstand | conforming to IACS E10; conforming to IEC 60947-1 Annex Q category D |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Pollution degree | 3 |
| Ambient air temperature for operation | -40…60 °C; 60…70 °C with derating |
| Ambient air temperature for storage | -60…80 °C |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz; Vibrations contactor closed: 4 Gn, 5...300 Hz; Shocks contactor open: 10 Gn for 11 ms; Shocks contactor closed: 15 Gn for 11 ms |
| Height | 77 mm |
| Width | 90 mm |
| Depth | 86 mm |
| Net weight | 0.687 kg |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys; TeSys Deca |
| Product name | TeSys D; TeSys Deca |
| Product or component type | Reversing contactor |
| Device short name | LC2D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-1; AC-3; AC-3e |
| Device presentation | Preassembled with reversing power busbar |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 9 A (at |
| Motor power kW | 2.2 kW at 220...230 V AC 50...60 Hz; 4 kW at 380...400 V AC 50...60 Hz; 4 kW at 415 V AC 50...60 Hz; 4 kW at 440 V AC 50...60 Hz; 5.5 kW at 500 V AC 50...60 Hz; 5.5 kW at 660...690 V AC 50...60 Hz |
| Motor power hp | 0.5 hp at 115 V AC 60 Hz for 1 phase motors; 1 hp at 230/240 V AC 60 Hz for 1 phase motors; 2 hp at 200/208 V AC 60 Hz for 3 phases motors; 2 hp at 230/240 V AC 60 Hz for 3 phases motors; 5 hp at 460/480 V AC 60 Hz for 3 phases motors; 7.5 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 110 V AC 50/60 Hz |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 25 A (at 60 °C) for power circuit |
| Irms rated making capacity | 250 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 25 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Electrical durability | 0.6 Mcycles 25 A AC-1 at Ue |
| Power dissipation per pole | 0.2 W AC-3; 1.56 W AC-1; 0.2 W AC-3e |
| Front cover | With |
| Interlocking type | Mechanical |
| Mounting support | Rail; Plate |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60335-2-40:Annex JJ; IEC 60335-1 |
| Product certifications | DNV; CSA; CCC; UL; GL; LROS (Lloyds register of shipping); BV; RINA; GOST; UKCA |
| Operating time | 12...22 ms closing; 4...19 ms opening |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Maximum operating rate | 3600 cyc/h 60 °C |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.300 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 13.500 cm |
| Package 1 Weight | 810.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 6 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.121 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 96 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 91.248 kg |
The LC2D09F7 is a reversing contactor from the TeSys Deca series by Schneider Electric, designed for controlling electric motors and resistive loads in industrial applications. The device features a 3-pole main contact configuration (3P) and is equipped with an auxiliary switch block consisting of one close and one open contact (1S+1Oe). Control is achieved via a coil with a rated voltage of 110 V AC at 50/60 Hz. The contactor is designed for use in networks with a rated operating voltage up to 690 V (according to IEC 60947-4-1) and complies with standards EN 60947-4-1, IEC 60947-4-1, and CSA C22.2 No. 14. It is also certified by UL, CSA, CCC, DNV, GL, LROS, BV, RINA, GOST, and UKCA, confirming its suitability for international applications.
Applications
This contactor is suitable for motor control in systems with AC-3 loads (three-phase motors) as well as resistive loads (AC-1) and special applications with AC-3e usage category. It is used in industrial machinery, conveyor systems, pump and fan drives, and other drive systems where safe and reliable switching of power is required. Motor power reaches up to 5.5 kW at 660–690 V AC 50–60 Hz and 4 kW at 380–440 V AC 50–60 Hz. In the USA and Canada, the power corresponds to up to 7.5 hp at 575/600 V AC 60 Hz for three-phase motors.
Functions and Equipment in Detail
The device is a pre-assembled reversing contactor combination with a reversing power busbar, enabling simple and secure installation. Contacts are rated for an operating current of 9 A, with a conventional thermal current (Ith) in the circuit of 25 A at 60 °C. The electrical life is 0.6 million switching cycles at 25 A AC-1. The mechanical life is specified with a B10d value of 20,000,000 cycles under mechanical load. The operating time is 12–22 ms for closing and 4–19 ms for opening. The front cover is integrated, and mechanical interlocking ensures safe operation.
Technology Explained Simply
The contactor coil is supplied with 110 V AC, enabling magnetic attraction of the contacts to close or open the circuit. The rated impulse voltage withstand is 6 kV, ensuring safety during transient voltage surges. The overvoltage category III indicates suitability for applications with moderate overvoltage stress. The rated breaking capacity is 250 A at 440 V, describing the contactor’s ability to safely interrupt circuits under load. The rated short-time current withstand is specified for various durations, with the maximum value for the circuit being 210 A at 1 second.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN11 (1S+1Oe, front-mounted) or LAD8N11 (1S+1Oe, side-mounted), as well as time blocks like LADT2 (delayed engagement, 0.10–30.00 s). For motor protection, modules such as GV2ME14 (3p, 6–10 A, push-button actuation) or LRD14 (motor protection relay, 7–10 A) can be used. Additional accessories include connection modules like LAD4RCU (RC element, 110–250 VAC) and interlocking blocks like LAD6K10F (110–127 VAC/DC). The coil LXD1F7 (110 V 50/60 Hz) is specifically designed for D09–D38 size groups.
Mounting and Installation
Mounting is either on a rail or directly on a panel. The tightening torques for screw terminals are 1.7 Nm for power and control circuits, with an alternative torque of 2.5 Nm for power circuits when using a position screwdriver. The width is 90 mm, height 77 mm, and depth 86 mm. Terminals for power ratings from 40 to 65 A are equipped with EverLink technology, ensuring a reliable and durable connection.
Operational Advantages
The contactor offers a narrow width and enables quick and easy installation. The integrated front cover and mechanical interlocking enhance operational safety. The high electrical and mechanical life, along with international standard certifications, make the device a robust solution for industrial applications. Compatibility with various accessories allows flexible adaptation to specific requirements.