| Complementary |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Motor power kW | 4 kW at 380...415 V AC 50/60 Hz; 4 kW at 660...690 V AC 50/60 Hz; 1.1 kW at 220...230 V AC 50/60 Hz |
| [Ith] conventional free air thermal current | 20 A (at 55 °C) for power circuit; 10 A (at 55 °C) for signalling circuit |
| Irms rated making capacity | 85 A AC conforming to NF C 63-110; 85 A AC conforming to IEC 60947 |
| Rated breaking capacity | 68 A at |
| [Icw] rated short-time withstand current | 60 A 55 °C for power circuit |
| Associated fuse rating | 20 A gI at |
| Average impedance | 4 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 690 V conforming to BS 5424; Power circuit: 690 V conforming to IEC 60947; Power circuit: 690 V conforming to UL 508; Power circuit: 690 V conforming to VDE 0110 group C; Power circuit: 690 V conforming to CSA C22.2 No 14 |
| Mounting support | Panel; Rail |
| Standards | EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1 |
| Product certifications | CB Scheme; CE; UKCA; EAC; cULus |
| Connections - terminals | Connector 1 cable(s) 1.5…6 mm²solid; Connector 2 cable(s) 1.5…4 mm²solid; Connector 1 cable(s) 0.5…6 mm²flexible without cable end; Connector 2 cable(s) 0.35…2.5 mm²flexible without cable end; Connector 1 cable(s) 0.35…6 mm²flexible with cable end; Connector 2 cable(s) 0.35…1.5 mm²flexible with cable end |
| Tightening torque | Power circuit: 0.8 N.m - on connector - with screwdriver pozidriv No 1 |
| Operating time | 6...8 ms coil de-energisation and NO opening; 7...14 ms coil energisation and NO closing |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 1200 cyc/h |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc at 50/60 Hz (at |
| Inrush power in VA | 23 VA 50/60 Hz (at 20 °C) |
| Hold-in power consumption in VA | 4.9 VA 50/60 Hz (at 20 °C) |
| Heat dissipation | 1.5 W at 50/60 Hz |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP2X conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50015 |
| Ambient air temperature for operation | -20…50 °C |
| Ambient air temperature for storage | -50…70 °C |
| Operating altitude | 2000 m without derating |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 56 mm |
| Net weight | 0.175 kg |
| Main |
| Range | TeSys |
| Product name | TeSys SK |
| Product or component type | Mini contactor |
| Device short name | LC1SKGC |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-1; AC-3 |
| power pole contact composition | 3P |
| Pole contact composition | 3 NO |
| Auxiliary contact composition | 1 NO |
| [Ie] rated operational current | 20 A (at |
| [Ue] rated operational voltage | Power circuit: 690 V AC 50/60 Hz; Signalling circuit: 690 V AC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.000 cm |
| Package 1 Width | 6.300 cm |
| Package 1 Length | 4.800 cm |
| Package 1 Weight | 169.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 28 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.820 kg |
The mini contactor LC1SKGC310P7 from the TeSys series by Schneider Electric is a compact device designed for use in installation circuits for controlling motors and resistive loads. It features a 3-pole main contact configuration with three closing contacts and an additional auxiliary contact, also configured as a closing contact. The contactor coil is rated for a control circuit voltage of 230 V AC at 50/60 Hz, making it suitable for integration into standard networks and control systems. The rated operational power is 4 kW at 380–415 V AC and 660–690 V AC, with the rated operational current Ie under AC-3 category being 9 A at 400 V AC. With a rated operating voltage of 690 V AC in the circuit, the device is designed for industrial applications with high voltages. The rated insulation voltage is also 690 V and complies with international standards such as IEC 60947, BS 5424, UL 508, VDE 0110 Group C, and CSA C22.2 No. 14.
Applications
This device is intended for motor control and operation of resistive loads in industrial, infrastructure, and building applications. It is suitable for simple machine control systems where a reliable and compact switching solution is required. The interface is easy to operate and enables integration into electronic control systems such as PLC systems. Mounting can be done either on a panel or on a rail, allowing flexible installation in enclosures and distribution systems.
Functions and Equipment in Detail
The contactor has a mechanical life of 10 million switching cycles and a maximum operating rate of 1200 switching operations per hour, making it suitable for frequent switching operations. The operating time is 6–8 ms for coil de-energization and NO opening, and 7–14 ms for coil energization and NO closing. The pickup power is 23 VA, and the holding power consumption is 4.9 VA at 50/60 Hz and 20 °C. The heat dissipation of the device is 1.5 W. The terminals are designed for various cable cross-sections: rigid cables from 1.5 to 6 mm² at terminal 1 and 1.5 to 4 mm² at terminal 2, as well as flexible cables with and without wire end ferrules in cross-sections of 0.35 to 6 mm² (terminal 1) and 0.35 to 2.5 mm² (terminal 2). The pickup torque is 0.8 Nm, with mounting performed using a screwdriver in position No. 1.
Technology Explained Simply
The usage categories AC-1 and AC-3 define the operating conditions: AC-1 for resistive loads, AC-3 for motor control. The rated switching capacity of 85 A complies with standards NF C 63-110 and IEC 60947. The rated breaking capacity is 68 A, and the rated short-time current withstand is 60 A at 55 °C. The associated fuse is rated for 20 A gI. The average impedance is 4 MΩ with a thermal current Ith of 20 A. The conventional thermal current rating is 20 A for the circuit and 10 A for the signal circuit at 55 °C in free air.
Compatibility and Accessories
To extend functionality and protect against overvoltage, accessories such as the overvoltage limiter LA4SKE1E (varistor), LA4SKE1U (110–250 V AC/DC), or LA4SKC1U (24–250 VDC diode) can be used. These components are designed for integration into the contactor system and support the safety and reliability of the installation.
Mounting and Installation
The device can be mounted on a panel or a rail. Dimensions are 45 mm width, 58 mm height, and 56 mm depth. The operating altitude is up to 2000 m without performance reduction. The ambient temperature during operation ranges from -20 °C to 50 °C, and during storage from -50 °C to 70 °C. The protection rating IP2x complies with VDE 0106 and protects against finger contact. The coating TC complies with IEC 60068 and DIN 50015, ensuring resistance to environmental influences.
Advantages in Operation
The mini contactor offers high switching capacity in a compact design, is designed for frequent switching operations, and meets international standards such as EN/IEC 60947-4-1, UL 60947-4-1, and CSA C22.2 No. 60947-4-1. Certifications include CB Regulation, CE, UKCA, EAC, and cULus. Simple mounting and integration into electronic control systems such as PLC systems facilitate use in modern installations. Low heat dissipation and high mechanical life contribute to reliability and ease of maintenance.
The product is available in single packaging (PCE), with one unit per package. The packaging unit S01 includes 28 units. The product weight is 0.175 kg, and the warranty is 18 months.