| Complementary |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 110 V AC 50/60 Hz |
| [Ith] conventional free air thermal current | 12 A (at 55 °C) for power circuit |
| Irms rated making capacity | 66 A at 690 V AC conforming to IEC 60947; 66 A at 690 V AC conforming to NF C 63-110 |
| Rated breaking capacity | 52 A at |
| [Icw] rated short-time withstand current | 50 A 55 °C for power circuit |
| Associated fuse rating | 16 A gI at |
| Average impedance | 4 mOhm - Ith 12 A 50 Hz |
| [Ui] rated insulation voltage | 690 V conforming to IEC 60947; 690 V conforming to VDE 0110 group C; 690 V conforming to BS 5424; 690 V conforming to UL 508; 690 V conforming to CSA C22.2 No 14 |
| Mounting support | Rail |
| Standards | EN/IEC 60947-4-1; UL 60947-4-1; CSA C22.2 No 60947-4-1 |
| Product certifications | CB Scheme; CE; UKCA; EAC; cULus |
| Connections - terminals | Power circuit: connector 1 cable(s) 0.35…6 mm²flexible with cable end; Power circuit: connector 1 cable(s) 0.5…6 mm²flexible without cable end; Power circuit: connector 1 cable(s) 1.5…6 mm²solid; Power circuit: connector 2 cable(s) 0.35…1.5 mm²flexible with cable end; Power circuit: connector 2 cable(s) 0.35…2.5 mm²flexible without cable end; Power circuit: connector 2 cable(s) 1.5…4 mm²solid |
| Tightening torque | 0.8 N.m - on connector - with screwdriver pozidriv No 1 |
| Operating time | 6...8 ms coil de-energisation and NO opening; 7...14 ms coil energisation and NO closing |
| Mechanical durability | 10 Mcycles |
| Maximum operating rate | 1200 cyc/h |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc (at |
| Inrush power in VA | 16 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.2 VA (at 20 °C) |
| Heat dissipation | 1.4 W at 50/60 Hz |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP2X conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50015 |
| Ambient air temperature for operation | -20…50 °C |
| Ambient air temperature for storage | -50…70 °C |
| Operating altitude | 2000 m without derating |
| Height | 56 mm |
| Width | 27 mm |
| Depth | 55.5 mm |
| Net weight | 0.132 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Product name | TeSys SK |
| Product or component type | Mini contactor |
| Device short name | LC1SK |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-1; AC-3 |
| power pole contact composition | 2P |
| Pole contact composition | 2 NO |
| [Ie] rated operational current | 6 A at |
| [Ue] rated operational voltage | Power circuit: 690 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 3.300 cm |
| Package 1 Width | 6.000 cm |
| Package 1 Length | 6.700 cm |
| Package 1 Weight | 120.000 g |
| Unit Type of Package 2 | S01 |
| Number of Units in Package 2 | 40 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 15.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 4.865 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 1280 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 170.700 kg |
Miniature contactor TeSys LC1SK. 2 pole, 2 NO contacts. Rated operational power at AC-3, 400 V 2.2 kW, rated operational current Ie at AC-3, 400 V 6 A, coil 110 V AC. Dimensions (WxHxD) 27x56x55.5 mm, weight 0.132 kg. Category AC-1, AC-3. Simple machine control in industry, infrastructure and building applications. Easy-to-use interface for electronic devices (PLC). Certifications according to cULus. Product standards according to IEC 60947, VDE 0660, BS 5424, NF C 63-110.