| Complementary |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 12 A (at |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Motor power kW | 3 kW at 220...230 V AC 50/60 Hz AC-3; 5.5 kW at 380...415 V AC 50/60 Hz AC-3; 5.5 kW at 440 V AC 50/60 Hz AC-3; 4 kW at 690 V AC 50/60 Hz AC-3; 3 kW at 220...230 V AC 50/60 Hz AC-3e; 5.5 kW at 380...415 V AC 50/60 Hz AC-3e; 5.5 kW at 440 V AC 50/60 Hz AC-3e; 4 kW at 690 V AC 50/60 Hz AC-3e; 3 kW at 220...230 V AC 50/60 Hz AC-4; 5.5 kW at 380...415 V AC 50/60 Hz AC-4; 5.5 kW at 440 V AC 50/60 Hz AC-4; 4 kW at 690 V AC 50/60 Hz AC-4 |
| Auxiliary contact composition | 1 NO |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit |
| Irms rated making capacity | 144 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 115 A 50 °C - 1 s for power circuit; 105 A 50 °C - 5 s for power circuit; 100 A 50 °C - 10 s for power circuit; 75 A 50 °C - 30 s for power circuit; 55 A 50 °C - 1 min for power circuit; 50 A 50 °C - 3 min for power circuit; 25 A 50 °C - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit |
| Associated fuse rating | 25 A gG at |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Inrush power in VA | 30 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.5 VA (at 20 °C) |
| Heat dissipation | 1.3 W |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at = 0.20 Uc (at |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Maximum operating rate | 3600 cyc/h |
| Coil technology | Without built-in suppressor module |
| Auxiliary contacts type | type instantaneous 1 NO |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Mounting support | Plate; Rail |
| Tightening torque | 0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm; 0.8…1.3 N.m - on screw clamp terminals pozidriv No 2 |
| Operating time | 10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Non overlap distance | 0.5 mm |
| Mechanical durability | 10 Mcycles |
| Electrical durability | 1.3 Mcycles 12 A AC-3 at Ue |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Net weight | 0.18 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| IP degree of protection | IP2X conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50016 |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product or component type | Contactor |
| Device short name | LC1K |
| Device application | Control |
| Contactor application | Resistive load; Motor control |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.600 cm |
| Package 1 Width | 6.000 cm |
| Package 1 Length | 4.800 cm |
| Package 1 Weight | 178.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 50 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.340 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 400 |
| Package 3 Height | 45.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 83.340 kg |
The LC1K1210P7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for controlling electrical loads, particularly for motor control and resistive loads. It has a rated operational current of 12 A and is designed for a control circuit voltage of 230 V AC at 50/60 Hz. The main function of the device is to ensure safe and reliable switching operations in industrial and infrastructure applications, and it is certified for categories AC-1, AC-3, AC-3e, and AC-4. The motor power rating is 5.5 kW at 380–415 V AC 50/60 Hz (AC-3), making it suitable for use in medium industrial drives. The device is equipped with an auxiliary contact configured as 1 normally open (1 S) to enable additional control functions such as feedback or interlocking.
Applications
This contactor is designed for controlling electrical machines and drives in industrial, infrastructure, and building applications. It is particularly suitable for applications requiring simple machine control, such as conveyor systems, pumps, fans, or machine tools. The combination of robust design and compact form factor enables flexible integration into existing control systems. Certifications according to UL and CSA ensure compliance with international safety standards, enabling use in various markets.
Functions and Equipment in Detail
The contactor features a coil with an inrush power of 30 VA and a holding power consumption of 4.5 VA at 20 °C. The heat dissipation is 1.3 W, indicating efficient thermal design. The rated impulse voltage withstand is 8 kV, and the overvoltage category is III, ensuring high electrical strength and safety against transient voltage surges. The insulation resistance exceeds 10 MΩ for the signal circuit, ensuring reliable electrical isolation between circuits. The minimum switching voltage is 17 V, and the minimum switching current is 5 mA for the signal circuit, ensuring reliability under low-load conditions.
Technology Explained Simply
The contactor operates using an electromagnetic coil that, when energized with the control voltage (230 V AC), pulls in the armature and closes the main contacts. The contacts are configured as 3 normally open (3 S), meaning all three main contacts close simultaneously to ensure secure power supply. The auxiliary contacts (1 S) are used for signal transmission, for example, to provide feedback of the switching state to a control unit such as a PLC. The coil is designed without an integrated wiring module, enabling simple installation and maintenance. The operational rate is up to 3600 switching operations per hour, indicating high mechanical durability.
Compatibility and Accessories
The contactor is compatible with various auxiliary switch blocks, including models LA1KN31M, LA1KN11, LA1KN31, LA1KN20, LA2KT2E, LA1KN22M, LA1KN40, LA2KT2U, LA1KN02, LA1KN13, LA1KN22, LA1KN04, LA1KN11M, as well as overvoltage limiters such as LA4KE1UG and LA4KA1U. Additionally, motor protection relays such as LR2K0321 or motor protection switches such as GV2LE16 and GV2ME16 can be combined to provide comprehensive protection for the connected motor. Nameplates LA9D90 allow for clear identification of the device in operation.
Mounting and Installation
Mounting is possible either on a panel or on a rail, enabling flexible integration into enclosures and control systems. Connections are made via screw terminals designed for cable cross-sections of 0.34 to 4 mm² (flexible, with and without wire end ferrules) and 1.5 to 4 mm² (rigid). The tightening torque is 0.8 to 1.3 Nm, and the screw terminals are operated using a Phillips screwdriver No. 2, flat screws Ø 6, or position No. 2. The operating time is 10 to 20 ms for coil de-energization and NO opening, as well as for coil energization and NO closing, ensuring fast response.
Advantages in Operation
The contactor offers high reliability at high operational rates and is designed for use in demanding industrial environments. The combination of robust design, high electrical strength, and compact form factor enables efficient use in various application areas. The simple interface for electronic devices such as PLCs facilitates integration into modern control systems. Certifications according to UL and CSA, along with compliance with standards IEC 60947 and UL 508, ensure safety and compatibility in international markets. The maximum rated breaking capacity is 110 A at 440 V, ensuring reliability under short-circuit conditions. The associated fuse is specified as 25 A gG, enabling optimal protection coordination.