| Complementary |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 9 A (at |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Motor power kW | 2.2 kW at 220...230 V AC 50/60 Hz AC-3; 4 kW at 380...415 V AC 50/60 Hz AC-3; 4 kW at 440/690 V AC 50/60 Hz AC-3; 2.2 kW at 220...230 V AC 50/60 Hz AC-3e; 4 kW at 380...415 V AC 50/60 Hz AC-3e; 4 kW at 440/690 V AC 50/60 Hz AC-3e; 2.2 kW at 220...230 V AC 50/60 Hz AC-4; 4 kW at 380...415 V AC 50/60 Hz AC-4; 4 kW at 440/690 V AC 50/60 Hz AC-4 |
| Auxiliary contact composition | 1 NO |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit |
| Irms rated making capacity | 110 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit |
| Associated fuse rating | 25 A gG at |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Inrush power in VA | 30 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.5 VA (at 20 °C) |
| Heat dissipation | 1.3 W |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at = 0.20 Uc (at |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Maximum operating rate | 3600 cyc/h |
| Coil technology | Without built-in suppressor module |
| Auxiliary contacts type | type instantaneous 1 NO |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Operating time | 10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Non overlap distance | 0.5 mm |
| Mechanical durability | 10 Mcycles |
| Electrical durability | 1.3 Mcycles 9 A AC-3 at Ue |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50016 |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product or component type | Contactor |
| Device application | Control |
| Contactor application | Resistive load; Motor control |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.600 cm |
| Package 1 Width | 4.800 cm |
| Package 1 Length | 6.200 cm |
| Package 1 Weight | 177.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 50 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.146 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 800 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 162.980 kg |
The
contactor of the
TeSys series by
Schneider Electric, type
LC1K0910P7, is a 3-pole contactor for controlling electrical loads, particularly for
motor control and
resistive loads. It features a
coil with 230 V AC and is designed for operation in industrial, infrastructure, and building applications. The device application falls within the area of
control, where the contactor is suitable for both simple machine control and integration into electronic control devices such as PLCs.
Applications
The contactor is designed for various usage categories, including
AC-3,
AC-3e,
AC-1, and
AC-4, with category AC-3 representing the standard application for motor drives. At an operating voltage of 380–415 V AC and an operating frequency of 50/60 Hz, the
rated operational power is 4 kW and the
operating rated current is 9 A. These values also apply to categories AC-3e and AC-4, while at 220–230 V AC, the motor power is reduced to 2.2 kW. The application thus covers both low-voltage installations and higher voltage levels up to 690 V AC.
Functions and Equipment in Detail
The device features
3 normally closed contacts in the main current circuit and an additional
auxiliary contact (1 normally closed), which can be used for signaling and control purposes. The auxiliary contacts are of the
type non-delayed, enabling direct and rapid response to control signals. The
rated impulse voltage withstand is 8 kV, and the overvoltage category is III, confirming suitability for industrial environments with high electrical stress. The
insulation resistances are over 10 MΩ for the signal circuit, ensuring high electrical safety.
Technology Explained Simply
The
coil of the contactor is operated at
230 V AC and has an
attracting power of 30 VA at 20 °C, as well as a
holding power consumption of 4.5 VA. The operating time is 10–20 ms for coil de-energization and NO opening, as well as for coil energization and NO closing, enabling fast switching response. The
heat dissipation is 1.3 W, limiting thermal stress during operation. The
maximum operating rate is 3600 switching operations per hour, suitable for continuous and high loads.
Compatibility and Accessories
The contactor can be combined with various accessories to extend functionality. These include, for example,
motor protection circuit breakers such as GV2ME14 or GV2LE14,
auxiliary switch blocks such as LA1KN11M or LA1KN22, and
motor protection relays such as LR2K0314. These components enable expansion of protection and control functions, especially in systems with increased safety requirements. Combining with a motor protection circuit breaker is typical to protect the motor against overload and short circuit.
Mounting and Installation
Connections are made via
screw terminals, designed for various cable cross-sections: for rigid cables from 1.5 to 4 mm², for flexible cables without cable ends from 0.75 to 4 mm², and with cable ends from 0.34 to 2.5 mm². Mounting is done in standard control panels, with device dimensions of 45 mm (width), 58 mm (height), and 57 mm (depth). Mounting follows standards EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No. 60947-4-1, and other international standards.
Operational Advantages
The contactor offers a high
mechanical life of 10 million switching cycles and an
electrical life of 1.3 million cycles at 9 A AC-3. The
rated short-time current withstand is up to 90 A for 1 second in the circuit, ensuring reliability under transient loads. The
rated breaking capacity is 110 A for voltages up to 440 V and decreases for higher voltages according to IEC 60947 standards. The
associated fuse is specified as 25 A gG, supporting the selection of the correct fuse for protecting the contactor. The
safety levels according to EN/ISO 13849-1 are B10d = 1,369,863 cycles at rated load and B10d = 20,000,000 cycles at mechanical load, emphasizing reliability in safety-critical applications.
Certifications and Standards
The device complies with standards EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No. 60947-4-1, JIS C8201-4-1, as well as IEC 60335-1:Clause 30.2 and IEC 60335-2-40:Annex. Certifications according to CSA and UL confirm suitability for use in various markets, particularly in North America and Europe.