| Complementary |
| Utilisation category | AC-1 |
| Poles description | 4P |
| power pole contact composition | 2 NO + 2 NC |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 20 A (at |
| Control circuit type | AC at 50/60 Hz standard |
| [Uc] control circuit voltage | 24 V AC 50/60 Hz |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Ith] conventional free air thermal current | 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit |
| Irms rated making capacity | 110 A AC for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit |
| Associated fuse rating | 10 A gG for control circuit conforming to IEC 60947; 10 A gG for control circuit conforming to VDE 0660; 25 A gG at |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Control circuit: 690 V conforming to BS 5424; Control circuit: 690 V conforming to IEC 60947; Power circuit: 690 V conforming to BS 5424; Power circuit: 690 V conforming to IEC 60947; Power circuit: 690 V conforming to NF C 20-040; Control circuit: 750 V conforming to VDE 0110 group C; Power circuit: 750 V conforming to VDE 0110 group C; Control circuit: 600 V conforming to CSA C22.2 No 14; Power circuit: 600 V UL 508 certified conforming to CSA C22.2 No 14 |
| Insulation resistance | > 10 MOhm for control circuit |
| Inrush power in VA | 30 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.5 VA 50/60 Hz (at 20 °C) |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc at 50/60 Hz (at = 0.20 Uc at 50/60 Hz (at |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Maximum operating rate | 3600 cyc/h |
| Coil technology | Without built-in suppressor module |
| Minimum switching current | 5 mA for control circuit |
| Minimum switching voltage | 17 V for control circuit |
| Mounting support | Rail; Plate |
| Operating time | 10...20 ms coil de-energisation and NO opening; 15...25 ms coil de-energisation and NC opening; 10...20 ms between energisation of coil and closing of NO contact; 5...15 ms coil energisation and NC opening |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 10 Mcycles |
| Electrical durability | 0.16 Mcycles 20 A AC-1 at Ue |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Net weight | 0.18 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1 |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | Class C2 conforming to NF F 16-101; Class C2 conforming to NF F 16-102; V1 conforming to UL 94 |
| Main |
| Product or component type | Contactor |
| Device short name | LC1K |
| Contactor application | Resistive load |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 4.500 cm |
| Package 1 Width | 5.700 cm |
| Package 1 Length | 5.700 cm |
| Package 1 Weight | 170.000 g |
| Unit Type of Package 2 | BB1 |
| Number of Units in Package 2 | 30 |
| Package 2 Height | 7.100 cm |
| Package 2 Width | 29.500 cm |
| Package 2 Length | 30.300 cm |
| Package 2 Weight | 5.246 kg |
TeSys LC1K power contactor. 4-pole, 2 NO + 2 NC. Additional auxiliary contacts - 2 NO + 2 NC, coil 24 V AC. Dimensions (WxHxD) 45x58x57 mm, weight 0.18 kg. Category AC-1. Coil - AC 50/60 Hz, without built-in amplitude limiter diode. Simple machine control in industry, infrastructure and building applications. Easy-to-use interface for electronic devices (PLC). Certifications according to GOST, CSA, UL. Product standards according to VDE 0660, IEC 60947, BS 5424, NF C 63-110.