| Complementary |
| Utilisation category | AC-3; AC-3e; AC-4 |
| Poles description | 3P |
| power pole contact composition | 3 NO |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 6 A (at |
| Control circuit type | AC at 50/60 Hz |
| [Uc] control circuit voltage | 230...240 V AC 50/60 Hz |
| Motor power kW | 1.5 kW at 220...230 V AC 50/60 Hz AC-3; 2.2 kW at 380...415 V AC 50/60 Hz AC-3; 3 kW at 440/690 V AC 50/60 Hz AC-3; 1.5 kW at 220...230 V AC 50/60 Hz AC-3e; 2.2 kW at 380...415 V AC 50/60 Hz AC-3e; 3 kW at 440/690 V AC 50/60 Hz AC-3e; 1.5 kW at 220...230 V AC 50/60 Hz AC-4; 2.2 kW at 380...415 V AC 50/60 Hz AC-4; 3 kW at 440/690 V AC 50/60 Hz AC-4 |
| Auxiliary contact composition | 1 NC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit |
| Irms rated making capacity | 110 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947 |
| Rated breaking capacity | 110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit |
| Associated fuse rating | 25 A gG at |
| Average impedance | 3 mOhm - Ith 20 A 50 Hz for power circuit |
| [Ui] rated insulation voltage | Power circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14 |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Inrush power in VA | 30 VA (at 20 °C) |
| Hold-in power consumption in VA | 4.5 VA (at 20 °C) |
| Heat dissipation | 1.3 W |
| Control circuit voltage limits | Operational: 0.8...1.15 Uc (at = 0.20 Uc (at |
| Connections - terminals | Screw clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end |
| Maximum operating rate | 3600 cyc/h |
| Coil technology | Without built-in suppressor module |
| Auxiliary contacts type | type instantaneous 1 NC |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Mounting support | Plate; Rail |
| Tightening torque | 0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm |
| Operating time | 10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Non overlap distance | 0.5 mm |
| Mechanical durability | 10 Mcycles |
| Electrical durability | 1.3 Mcycles 6 A AC-3 at Ue |
| Height | 58 mm |
| Width | 45 mm |
| Depth | 57 mm |
| Net weight | 0.18 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; UL; CSA; EAC; CE; UKCA |
| IP degree of protection | IP2X conforming to VDE 0106 |
| Protective treatment | TC conforming to IEC 60068; TC conforming to DIN 50016 |
| Ambient air temperature for storage | -50…80 °C |
| Operating altitude | 2000 m without derating |
| Flame retardance | V1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102 |
| Logistical informations |
| Country of origin | FR |
| Main |
| Range | TeSys |
| Product or component type | Contactor |
| Device short name | LC1K |
| Device application | Control |
| Contactor application | Motor control |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.500 cm |
| Package 1 Width | 6.500 cm |
| Package 1 Length | 5.000 cm |
| Package 1 Weight | 430.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 50 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.360 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 800 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 164.680 kg |
The LC1K0601U7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for motor control in industrial, infrastructure, and building technical applications. It is designed for electrical control of motors and is rated for categories AC-3, AC-3e, and AC-4, enabling use with various load types such as three-phase motors with normal or increased starting power. The device features a main contact configuration of 3 closers and an additional auxiliary contact in normally open configuration. Control is achieved via a coil with a rated control circuit voltage of 230 to 240 V AC at 50/60 Hz. The rated operational power is 2.2 kW at 400 V AC-3, with a rated operational current Ie of 6 A. The coil has an inrush power of 30 VA and a holding power consumption of 4.5 VA at 20 °C. The heat dissipation of the device is 1.3 W.
Applications
This contactor is designed for controlling electric motors in simple machine installations. It is used in industry, infrastructure, and building installations where reliable and simple electrical control is required. Integration with electronic control devices such as PLCs (Programmable Logic Controllers) is possible, as the device features an easy-to-use interface. Certifications according to CSA and UL confirm compliance with international safety and quality standards.
Functions and Equipment in Detail
The device features a contact configuration of 3 closers (3S) in the main circuit and an additional auxiliary contact in normally open configuration (1O). The auxiliary contacts are instantaneous and allow integration into control circuits, for example for status indication or feedback to a control system. The rated surge voltage withstand is 8 kV, and the overvoltage category is III, enabling use in industrial environments with increased electrical stress. The rated insulation voltage is 690 V for both the power circuit and the signal circuit, in accordance with IEC 60947-4-1 and IEC 60947-5-1. The insulation resistance is specified as > 10 MΩ for the signal circuit.
Technology Explained Simply
The contactor coil operates on 230–240 V AC and enables magnetic attraction of the contacts, thereby closing the circuit. The operating time is 10–20 ms for coil de-energization and NO opening, as well as for coil energization and NO closing. The maximum operating rate is 3600 switching operations per hour, enabling high dynamics in control. The inrush torques range from 0.8 to 1.3 Nm, with the screw terminals operated using a Phillips screwdriver No. 2 or flat screws with Ø 6 mm. The terminals are designed for rigid cables with 1.5 to 4 mm² and flexible cables with 0.75 to 4 mm² (without cable end) and 0.34 to 2.5 mm² (with cable end). The average impedance is 3 MΩ at 50 Hz and Ith 20 A.
Compatibility and Accessories
The contactor can be combined with various accessories to extend functionality. These include motor protection relays such as the LR2K0308 (1.8–2.6 A) or LR2K0312 (3.7–5.5 A), which monitor motor load. Auxiliary switch blocks such as the LA2KT2E (delayed response, 1–30 seconds) or LA1KN20 (2 closers) allow expansion of control functions. Additional components such as the overvoltage limiter LA4KE1UG (250 V) or the compact energy meter A9MEM1573 can be integrated into the overall system. Mounting is on a plate or rail, enabling flexible installation in enclosures.
Mounting and Installation
Mounting of the contactor is on a mounting plate or rail, with screw terminals provided for cable connections. Cable cross-sections must match the specified values to ensure a safe and reliable connection. The tightening torques are precisely defined to ensure correct cable fixation. The operating temperature of the device is limited to 60 °C for the power circuit and 50 °C for the signal circuit, with conventional thermal current Ith of 20 A (power circuit) and 10 A (signal circuit).
Operational Advantages
The contactor offers high operational safety by complying with IEC 60947 and UL 508 standards. The rated switching capacity of 110 A AC for both power and signal circuits, along with a nominal breaking capacity of up to 110 A at 220–230 V and 70 A at 660–690 V, ensures reliable performance at various voltage levels. The rated short-time current withstand is 90 A for 1 second in the power circuit, ensuring stability during short-term load peaks. The heat dissipation of 1.3 W is low and contributes to the thermal stability of the installation. The simple interface enables direct integration into existing control systems.