Schneider Electric LC1K0601Q7, EAN: 3389110488067

Schneider Electric LC1K0601Q7 contactor 3p 6A

Industrial Material > Industrial relays and contactors > Contactors

Schneider Electric LC1K0601Q7 contactor 3p 6A

Lieske Part No. 581898
Mfg Part No LC1K0601Q7
EAN-Code 3389110488067
Manufacturer Schneider Electric
Here only 45,39 EUR
54,01 EUR incl. VAT

Further information for Schneider Electric LC1K0601Q7 contactor 3p 6A

Complementary
Utilisation categoryAC-3; AC-3e; AC-4
Poles description3P
power pole contact composition3 NO
[Ue] rated operational voltagePower circuit:
[Ie] rated operational current6 A (at
Control circuit typeAC at 50/60 Hz
[Uc] control circuit voltage380...400 V AC 50/60 Hz
Motor power kW1.5 kW at 220...230 V AC 50/60 Hz AC-3; 2.2 kW at 380...415 V AC 50/60 Hz AC-3; 3 kW at 440/690 V AC 50/60 Hz AC-3; 1.5 kW at 220...230 V AC 50/60 Hz AC-3e; 2.2 kW at 380...415 V AC 50/60 Hz AC-3e; 3 kW at 440/690 V AC 50/60 Hz AC-3e; 1.5 kW at 220...230 V AC 50/60 Hz AC-4; 2.2 kW at 380...415 V AC 50/60 Hz AC-4; 3 kW at 440/690 V AC 50/60 Hz AC-4
Auxiliary contact composition1 NC
[Uimp] rated impulse withstand voltage8 kV
Overvoltage categoryIII
[Ith] conventional free air thermal current20 A (at 60 °C) for power circuit; 10 A (at 50 °C) for signalling circuit
Irms rated making capacity110 A AC for power circuit conforming to IEC 60947; 110 A AC for signalling circuit conforming to IEC 60947
Rated breaking capacity110 A at 220...230 V conforming to IEC 60947; 110 A at 380...400 V conforming to IEC 60947; 110 A at 415 V conforming to IEC 60947; 110 A at 440 V conforming to IEC 60947; 80 A at 500 V conforming to IEC 60947; 70 A at 660...690 V conforming to IEC 60947
[Icw] rated short-time withstand current90 A 50 °C - 1 s for power circuit; 85 A 50 °C - 5 s for power circuit; 80 A 50 °C - 10 s for power circuit; 60 A 50 °C - 30 s for power circuit; 45 A 50 °C - 1 min for power circuit; 40 A 50 °C - 3 min for power circuit; 20 A 50 °C - >= 15 min for power circuit; 80 A - 1 s for signalling circuit; 90 A - 500 ms for signalling circuit; 110 A - 100 ms for signalling circuit
Associated fuse rating25 A gG at
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
[Ui] rated insulation voltagePower circuit: 600 V conforming to UL 508; Power circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-5-1; Signalling circuit: 600 V conforming to UL 508; Power circuit: 600 V conforming to CSA C22.2 No 14; Signalling circuit: 600 V conforming to CSA C22.2 No 14
Insulation resistance> 10 MOhm for signalling circuit
Inrush power in VA30 VA (at 20 °C)
Hold-in power consumption in VA4.5 VA (at 20 °C)
Heat dissipation1.3 W
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at = 0.20 Uc (at
Connections - terminalsScrew clamp terminals 1 cable(s) 1.5…4 mm²solid; Screw clamp terminals 1 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 1 cable(s) 0.34…2.5 mm²flexible with cable end; Screw clamp terminals 2 cable(s) 1.5…4 mm²solid; Screw clamp terminals 2 cable(s) 0.75…4 mm²flexible without cable end; Screw clamp terminals 2 cable(s) 0.34…1.5 mm²flexible with cable end
Maximum operating rate3600 cyc/h
Coil technologyWithout built-in suppressor module
Auxiliary contacts typetype instantaneous 1 NC
Minimum switching current5 mA for signalling circuit
Minimum switching voltage17 V for signalling circuit
Mounting supportRail; Plate
Tightening torque0.8…1.3 N.m - on screw clamp terminals Philips No 2; 0.8…1.3 N.m - on screw clamp terminals flat Ø 6 mm
Operating time10...20 ms coil de-energisation and NO opening; 10...20 ms coil energisation and NO closing
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Non overlap distance0.5 mm
Mechanical durability10 Mcycles
Electrical durability1.3 Mcycles 6 A AC-3 at Ue
Height58 mm
Width45 mm
Depth57 mm
Net weight0.18 kg
Contractual warranty
Warranty (in months)18
Environment
StandardsEN/IEC 60947-4-1; GB/T 14048.4; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ
Product certificationsCB Scheme; CCC; UL; CSA; EAC; CE; UKCA
IP degree of protectionIP2X conforming to VDE 0106
Protective treatmentTC conforming to IEC 60068; TC conforming to DIN 50016
Ambient air temperature for storage-50…80 °C
Operating altitude2000 m without derating
Flame retardanceV1 conforming to UL 94; Requirement 2 conforming to NF F 16-101; Requirement 2 conforming to NF F 16-102
Logistical informations
Country of originFR
Main
RangeTeSys
Product or component typeContactor
Device short nameLC1K
Device applicationControl
Contactor applicationMotor control
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height4.800 cm
Package 1 Width6.200 cm
Package 1 Length6.700 cm
Package 1 Weight176.000 g
Unit Type of Package 2S02
Number of Units in Package 250
Package 2 Height15.000 cm
Package 2 Width30.000 cm
Package 2 Length40.000 cm
Package 2 Weight9.255 kg
TeSys LC1K power contactor. 3-pole, 3 NO contacts. Additional auxiliary contacts - 1 NC contact, rated operating power at AC-3, 400 V 2.2 kW, rated operating current Ie at AC-3, 400 V 6 A, coil 380-400 V AC. Dimensions (WxHxD) 45x58x57 mm, weight 0.18 kg. Category AC-3, AC-4. Simple machine control in industry, infrastructure and building applications. Easy-to-use interface for electronic devices (PLC). Certifications according to UL, CSA. Product standards in accordance with.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/581898
qrcode für Schneider Electric LC1K0601Q7 contactor 3p 6A