| Complementary |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 1050 A (at 40 °C) |
| Rated breaking capacity | 5870 A at 440 V |
| [Icw] rated short-time withstand current | 5.5 kA - 10 s; 4.6 kA - 30 s; 3.6 kA - 1 min; 2.6 kA - 3 min; 1.7 kA - 10 min |
| Associated fuse rating | 800 A aM at |
| Average impedance | 0.000065 Ohm |
| [Ui] rated insulation voltage | 1000 V |
| Power dissipation per pole | 70 W AC-1 - Ith 1050 A; 42 W AC-3 - Ith 800 A |
| Compatibility code | LC1G |
| Pole contact composition | 3 NO |
| Auxiliary contact composition | 1 NO + 1 NC |
| Motor power hp | 300 hp at 200/208 V 60 Hz; 350 hp at 230/240 V 60 Hz; 700 hp at 460/480 V 60 Hz; 800 hp at 575/600 V 60 Hz |
| Irms rated making capacity | 7640 A at 440 V |
| Coil technology | Built-in bidirectional peak limiting |
| Safety reliability level | B10d = 100000 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 1800000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 5 Mcycles |
| inrush power in VA (50/60 Hz, AC) | 560 VA |
| inrush power in W (DC) | 440 W |
| hold-in power consumption in VA (50/60 Hz, AC) | 12 VA |
| hold-in power consumption in W (DC) | 8.8 W |
| Operating time | 40...70 ms closing; 15...50 ms opening |
| Maximum operating rate | 600 cyc/h AC-3; 600 cyc/h AC-3e; 300 cyc/h AC-1; 150 cyc/h AC-4 |
| Connection pitch | 70 mm |
| Mounting support | Plate |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; JIS C8201-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-1; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; cULus; EAC; CE; UKCA; EU-RO-MR by DNV-GL |
| Tightening torque | 58 N.m |
| Height | 388.5 mm |
| Width | 211 mm |
| Depth | 266 mm |
| Net weight | 17.3 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP2X front face with shrouds conforming to IEC 60529; IP2X front face with shrouds conforming to VDE 0106 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Mechanical robustness | Vibrations 5…300 Hz 2 gn contactor open; Vibrations 5…300 Hz 4 gn contactor closed; Shocks 10 gn 11 ms contactor open; Shocks 15 gn 11 ms contactor closed |
| Colour | Dark grey |
| Protective treatment | TH |
| Permissible ambient air temperature around the device | -40…70 °C at Uc |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range | TeSys |
| Range of product | TeSys Giga |
| Product or component type | Contactor |
| Device short name | LC1G |
| Contactor application | Power switching; Motor control |
| Utilisation category | AC-1; AC-3; AC-3e; AC-4; AC-5a; AC-5b; AC-6a; AC-6b; AC-8b; AC-8a; DC-1; DC-3; DC-5 |
| Poles description | 3P |
| [Ie] rated operational current | 1050 A (at |
| [Uc] control circuit voltage | 48...130 V AC 50/60 Hz; 48...130 V DC |
| Control circuit voltage limits | Operational: 0.8 Uc Min...1.1 Uc Max (at |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 35.000 cm |
| Package 1 Width | 31.000 cm |
| Package 1 Length | 52.000 cm |
| Package 1 Weight | 19.398 kg |
| Unit Type of Package 2 | PAL |
| Number of Units in Package 2 | 4 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 80.000 cm |
| Package 2 Length | 65.000 cm |
| Package 2 Weight | 87.592 kg |