| Complementary |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 385 A (at 40 °C) |
| Rated breaking capacity | 2380 A at 440 V |
| [Icw] rated short-time withstand current | 2.2 kA - 10 s; 1.23 kA - 30 s; 0.95 kA - 1 min; 0.62 kA - 3 min; 0.48 kA - 10 min |
| Associated fuse rating | 315 A aM at |
| Average impedance | 0.000144 Ohm |
| [Ui] rated insulation voltage | 1000 V |
| Power dissipation per pole | 20 W AC-1 - Ith 385 A; 11 W AC-3 - Ith 265 A |
| Compatibility code | LC1G |
| Pole contact composition | 4 NO |
| Auxiliary contact composition | 1 NO + 1 NC |
| Irms rated making capacity | 3320 A at 440 V |
| Coil technology | Built-in bidirectional peak limiting |
| Safety reliability level | B10d = 400000 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 3000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| inrush power in VA (50/60 Hz, AC) | 530 VA |
| inrush power in W (DC) | 300 W |
| hold-in power consumption in VA (50/60 Hz, AC) | 16.1 VA |
| hold-in power consumption in W (DC) | 9.0 W |
| Operating time | 40...70 ms closing; 15...50 ms opening |
| Maximum operating rate | 600 cyc/h AC-3; 600 cyc/h AC-3e; 300 cyc/h AC-1 |
| Connection pitch | 45 mm |
| Mounting support | Plate |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; JIS C8201-5-1; UL 60335-1; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; cULus; EAC; CE; UKCA; EU-RO-MR by DNV-GL |
| Tightening torque | 35 N.m |
| Height | 290 mm |
| Width | 185 mm |
| Depth | 226 mm |
| Net weight | 8.9 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP2X front face with shrouds conforming to IEC 60529; IP2X front face with shrouds conforming to VDE 0106 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Mechanical robustness | Vibrations 5…300 Hz 2 gn contactor open; Vibrations 5…300 Hz 4 gn contactor closed; Shocks 10 gn 11 ms contactor open; Shocks 15 gn 11 ms contactor closed |
| Colour | Dark grey |
| Protective treatment | TH |
| Permissible ambient air temperature around the device | -40…70 °C at Uc |
| Main |
| Range | TeSys |
| Range of product | TeSys Giga |
| Product or component type | Contactor |
| Device short name | LC1G |
| Contactor application | Power switching |
| Utilisation category | AC-3; AC-3e; AC-1; AC-5a; AC-5b; AC-6a; AC-6b; DC-1; DC-3; DC-5 |
| Poles description | 4P |
| [Ie] rated operational current | 265 A (at |
| [Uc] control circuit voltage | 200...500 V AC 50/60 Hz; 200...500 V DC |
| Control circuit voltage limits | Operational: 0.8 Uc Min...1.1 Uc Max (at |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 27 cm |
| Package 1 Width | 32 cm |
| Package 1 Length | 37 cm |
| Package 1 Weight | 10.586 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 75.000 cm |
| Package 2 Width | 60.000 cm |
| Package 2 Length | 80.000 cm |
| Package 2 Weight | 97.252 kg |
TeSys control - Giga power contactor, 4 poles (4S) for applications in category AC-1 up to 385A at 400V. The contactor has a wide range AC/DC coil of 200-500V with low energy consumption plus two control inputs 24V DC. Supplied with a mounted auxiliary switch block with one normally open and one normally closed contact. Designed for demanding applications with maximum operating rates of up to 600 cycles per hour and environments up to 60°C. High reliability and durability with a mechanical life of 5 Mcycles. Green Premium compliant (RoHs/Reach).