| Complementary |
| [Uimp] rated impulse withstand voltage | 8 kV |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 305 A (at 40 °C) |
| Rated breaking capacity | 1610 A at 440 V |
| [Icw] rated short-time withstand current | 1.5 kA - 10 s; 0.92 kA - 30 s; 0.74 kA - 1 min; 0.5 kA - 3 min; 0.4 kA - 10 min |
| Associated fuse rating | 200 A aM at |
| Average impedance | 0.00017 Ohm |
| [Ui] rated insulation voltage | 1000 V |
| Power dissipation per pole | 20 W AC-1 - Ith 305 A; 6 W AC-3 - Ith 185 A |
| Compatibility code | LC1G |
| Pole contact composition | 3 NO |
| Auxiliary contact composition | 1 NO + 1 NC |
| Motor power hp | 50 hp at 200/208 V 60 Hz; 60 hp at 230/240 V 60 Hz; 125 hp at 460/480 V 60 Hz; 150 hp at 575/600 V 60 Hz |
| Irms rated making capacity | 2310 A at 440 V |
| Coil technology | Built-in bidirectional peak limiting |
| Safety reliability level | B10d = 400000 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 3000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| inrush power in VA (50/60 Hz, AC) | 640 VA |
| inrush power in W (DC) | 445 W |
| hold-in power consumption in VA (50/60 Hz, AC) | 18.7 VA |
| hold-in power consumption in W (DC) | 7.8 W |
| Operating time | 40...70 ms closing; 15...50 ms opening |
| Maximum operating rate | 600 cyc/h AC-3; 600 cyc/h AC-3e; 300 cyc/h AC-1; 150 cyc/h AC-4 |
| Connection pitch | 35 mm |
| Mounting support | Plate |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; CSA C22.2 No 60947-4-1; JIS C8201-4-1; JIS C8201-5-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-1; UL 60335-2-40:Annex JJ |
| Product certifications | CB Scheme; CCC; cULus; EAC; CE; UKCA; EU-RO-MR by DNV-GL |
| Tightening torque | 18 N.m |
| Height | 193 mm |
| Width | 108 mm |
| Depth | 193 mm |
| Net weight | 3.5 kg |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| IP degree of protection | IP2X front face with shrouds conforming to IEC 60529; IP2X front face with shrouds conforming to VDE 0106 |
| Ambient air temperature for operation | -25…60 °C |
| Ambient air temperature for storage | -60…80 °C |
| Mechanical robustness | Vibrations 5…300 Hz 2 gn contactor open; Vibrations 5…300 Hz 4 gn contactor closed; Shocks 10 gn 11 ms contactor open; Shocks 15 gn 11 ms contactor closed |
| Colour | Dark grey |
| Protective treatment | TH |
| Permissible ambient air temperature around the device | -40…70 °C at Uc |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Giga |
| Product or component type | Contactor |
| Device short name | LC1G |
| Contactor application | Power switching; Motor control |
| Utilisation category | AC-1; AC-3; AC-3e; AC-4; AC-5a; AC-5b; AC-6a; AC-6b; AC-8b; AC-8a; DC-1; DC-3; DC-5 |
| Poles description | 3P |
| [Ie] rated operational current | 305 A (at |
| [Uc] control circuit voltage | 48...130 V AC 50/60 Hz; 48...130 V DC |
| Control circuit voltage limits | Operational: 0.8 Uc Min...1.1 Uc Max (at |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 26 cm |
| Package 1 Width | 17.5 cm |
| Package 1 Length | 32 cm |
| Package 1 Weight | 4.549 kg |
| Unit Type of Package 2 | P06 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 75 cm |
| Package 2 Width | 60 cm |
| Package 2 Length | 80 cm |
| Package 2 Weight | 44.892 kg |
TeSys control - Giga power contactor, 3 poles (3S) for safe switching of motors at AC-3 up to 185A / 110kW at 400V. The contactor has an AC/DC wide range coil of 48-130V with low energy consumption. A mounted auxiliary switch block with one normally open and one normally closed contact is included in the delivery. Designed for demanding applications with maximum operating rates of up to 600 cycles per hour and environments up to 60°C. High reliability and durability with a mechanical life of 5 Mcycles. Green Premium compliant (RoHs/Reach).