| Additional features |
| [Uimp] Rated impulse voltage withstand | 8 kV |
| [Ith] conventional thermal current in free air | 1260 A (at 40 °C) |
| Rated breaking capacity | 1890 A corresponds to IEC 60947-4-1 |
| [Icw] rated short-time current withstand | 3000 A 40 °C - 3 min; 8000 A 40 °C - 10 s; 5200 A 40 °C - 30 s; 4000 A 40 °C - 1 min; 2000 A 40 °C - 10 min |
| Associated fuse | 1000 A gG |
| Average impedance | 0.12 MOhm - Ith 1260 A 50 Hz |
| [Ui] Rated insulation voltage | 1000 V corresponds to IEC 60947-4-1; 1500 V corresponds to VDE 0110 Group C |
| Power dissipation per pole | 120 W AC-1 |
| Over voltage category | III |
| Pole contact composition | 3 S |
| Control circuit voltage limits | Operation: 0.85 - 1.1 Uc 40 - 400 Hz (at 55 °C); Dropout voltage: 0.25 - 0.5 Uc 40 - 400 Hz (at 55 °C) |
| Input power in VA | 1650 VA, 40 - 400 Hz cos phi 0.9 (at 20 °C) |
| Hold power consumption in VA | 22 VA, 40 - 400 Hz cos phi 0.9 (at 20 °C) |
| Max. operating rate | 1200 cyc/h 55 °C |
| Operating time | 40 - 80 ms closing; 100 - 200 ms opening |
| Tightening moment | Control circuit: 1.2 Nm; Power circuit: 58 Nm |
| Mounting bracket | Plate |
| Heat emission | 20 W |
| Standards | EN 60947-1; IEC 60947-1; IEC 60947-4-1; JIS C8201-4-1; EN 60947-4-1 |
| Product certifications | CB; UL; CSA; CQC; CE; UKCA; CCC |
| Compatibility code | LC1F |
| Control circuit type | AC at 40 - 400 Hz |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys |
| Product or component type | Contactor |
| Device short name | LC1F |
| Application of contactor | resistive load |
| Application category | AC-1 |
| Pole description | 3P |
| [Uc] control circuit voltage | 230 V AC 40 - 400 Hz |
| [Ie] rated operational current | 1260 A (at |
| Mounting |
| Coating | TH |
| Operating ambient temperature | -5…40 °C |
| Ambient temperature during storage | -60…80 °C |
| Device ambient temperature | -40…60 °C |
| Height | 338 mm |
| Width | 309 mm |
| Depth | 255 mm |
| Installation height | 3,000 m without power derating |
| Product weight | 19 kg |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 33,0 cm |
| VPE 1 width | 37,0 cm |
| VPE 1 length | 44,0 cm |
| Packaging weight (Lbs) | 20,1 kg |
Leistungsschütz TeSys LC1F. 3 polig, 3 Schließer. Spule 230 V AC. Abmessung (BxHxT) 309x338x255 mm, Gewicht 19 kg. Kategorie AC-1. Für die Überwachung aller Motorentypen in normalen oder schwierigen Betriebsbedingungen. Überwachung von Widerstands-, Induktions- und Kapazitivschaltkreisen. Zertifizierungen nach cETLus, CB, CCC, CSA. Produktstandards gem. EN 60947-1, IEC 60947-1, IEC 60947-4-1, JIS C8201-4-1, EN 60947-4-1.