| Additional features |
| Motor power (kW) | 11 kW at 220/230 V AC 50/60 Hz; 22 kW at 380/400 V AC; 22 kW at 415/440 V AC; 30 kW at 500 V AC; 30 kW at 660/690 V AC; 33 kW at 660 - 690 V |
| Pole contact composition | 3 S |
| [Ith] conventional thermal current in free air | 70 A (at 55 °C) for circuit |
| [Irms] Rated making capacity | 650 A at 440 V AC for circuit conforming to IEC 60947-4-1 |
| Rated breaking capacity | 425 A at 440 V for circuit according to IEC 60947 |
| [Icw] rated short-time current withstand | 400 A 40 °C - 10 s for circuit; 208 A 40 °C - 60 s for circuit; 84 A 40 °C - 600 s for circuit |
| Associated fuse | 100 A gG |
| Average impedance | 1.5 MOhm - Ith 70 A 50 Hz for circuit |
| Power dissipation per pole | 3,8 W AC-3; 7,4 W AC-1 |
| [Ui] Rated insulation voltage | 690 V corresponds to IEC 60947-4-1 |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 6 kV coil not connected to power circuit, complies with IEC 60947 |
| Mechanical life | 5000000 cycles |
| Electrical lifetime | 350000 cycles AC-1; 900000 cycles AC-3 |
| Control circuit type | AC at 50/60 Hz |
| Control circuit voltage limits | 0.85 - 1.1 Uc (-5…55 °C): operation 50/60 Hz; 0.3 - 0.6 Uc (-5…55 °C): drop-out voltage 50/60 Hz |
| Input power in VA | 160 VA 50 Hz cos phi 0.75 (at 20 °C); 140 VA 60 Hz cos phi 0.75 (at 20 °C) |
| Hold power consumption in VA | 15 VA 50 Hz cos phi 0.3 (at 20 °C); 13 VA 60 Hz cos phi 0.3 (at 20 °C) |
| Heat emission | 6…10 W for control circuit |
| Operating time | 20 - 26 ms for closing; 8 - 12 ms for opening |
| Max. operating rate | 1200 cyc/h 60 °C |
| Tightening moment | Control circuit: 1.2 Nm; power circuit: 5 Nm |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| Min. switching voltage | 17 V for auxiliary contact circuit |
| Min. switching current | 5 mA for auxiliary contact circuit |
| Insulation resistance | > 10 MOhm for auxiliary contact circuit |
| Non-overlapping time | 1.5 ms guaranteed between normally closed and normally open contact on energizing; 1.5 ms guaranteed between normally closed and normally open contact on de-energizing |
| Mounting bracket | DIN rail; plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Easy TeSys |
| Product or component type | Contactor |
| Device short name | LC1E |
| Application of contactor | Motor control; resistive load |
| Application category | AC-3; AC-3e; AC-1 |
| Pole description | 3P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 50 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Mounting |
| Standards | EN/IEC 60947-1; EN/IEC 60947-4-1; EN/IEC 60947-5-1; GB/T 14048.1; GB/T 14048.4; GB/T 14048.5; EN/IEC 60335-1:Clause 30.2; EN/IEC 60335-2-40:Annex JJ |
| Product certifications | CB regulation; CCC; CE; EAC |
| Degree of protection (IP) | IP2x complies with IEC 60529 |
| Protection treatment | TH (pollution degree 3) corresponds to IEC 60068-2-30 Test Db |
| Device ambient temperature | -20…70 °C at Uc; -60…80 °C storage; -5…55 °C operation |
| Operating altitude | 3,000 m without power derating |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (1.5 Gn, 5 - 300 Hz); vibrations contactor closed (3 Gn, 5 - 300 Hz); shocks contactor open (6 Gn for 11 ms); shocks contactor closed (7 Gn for 11 ms) |
| Height | 127 mm |
| Width | 75 mm |
| Depth | 114 mm |
| Product weight | 0,98 kg |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 8,300 cm |
| VPE 1 width | 12,800 cm |
| VPE 1 length | 13,200 cm |
| Packaging weight (Lbs) | 988,000 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 9 |
| VPE 2 height | 15,000 cm |
| VPE 2 width | 30,000 cm |
| VPE 2 length | 40,000 cm |
| VPE 2 weight | 9,290 kg |