| Additional features |
| Motor power (kW) | 147 kW at 220/230 V AC 50/60 Hz; 250 kW at 380/400 V AC; 280 kW at 415 V AC; 295 kW at 440 V AC; 335 kW at 500 V AC; 355 kW at 660/690 V AC |
| Pole contact composition | 3 S |
| [Ith] conventional thermal current in free air | 700 A (at 40 °C) for circuit |
| [Irms] Rated making capacity | 5000 A at 440 V AC for circuit conforming to IEC 60947-4-1 |
| Rated breaking capacity | 4000 A at 440 V for circuit corresponds to IEC 60947 |
| [Icw] rated short-time current withstand | 4200 A 40 °C - 10 s for circuit |
| Associated fuse | 800 A gG at |
| Average impedance | 0.18 MOhm - Ith 700 A 50 Hz for circuit |
| Power dissipation per pole | 45 W AC-3; 88 W AC-1 |
| [Ui] Rated insulation voltage | 690 V corresponds to IEC 60947-4-1 |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 8 kV coil not connected to power circuit, complies with IEC 60947 |
| Mechanical life | 4000000 cycles |
| Electrical lifetime | 250000 cycles AC-1; 600000 cycles AC-3 |
| Control circuit type | AC at 50/60 Hz |
| Control circuit voltage limits | 0.85 - 1.1 Uc (-5…55 °C): operation 50/60 Hz; 0.35 - 0.5 Uc (-5…55 °C): drop-out voltage 50/60 Hz |
| Input power in VA | 1100 VA 50 Hz cos phi 0.9 (at 20 °C); 1100 VA 60 Hz cos phi 0.9 (at 20 °C) |
| Hold power consumption in VA | 18 VA 50 Hz cos phi 0.9 (at 20 °C); 18 VA 60 Hz cos phi 0.9 (at 20 °C) |
| Heat emission | 18 W for control circuit; 18 W |
| Operating time | 100 - 170 ms for opening; 40 - 75 ms for closing |
| Max. operating rate | 2400 cyc/h 55 °C |
| Tightening moment | Control circuit: 1.2 Nm; power circuit: 35 Nm |
| Configuration of auxiliary contacts | None |
| Mounting bracket | Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | Easy TeSys |
| Product or component type | Contactor |
| Device short name | LC1E |
| Application of contactor | Motor control; resistive load |
| Application category | AC-3; AC-3e; AC-1 |
| Pole description | 3P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 500 A (at |
| [Uc] control circuit voltage | 220 V AC 50/60 Hz |
| Mounting |
| Standards | EN/IEC 60947-1; EN/IEC 60947-4-1; GB/T 14048.1; GB/T 14048.4 |
| Product certifications | CB regulation; CCC; CE; EAC |
| Degree of protection (IP) | IP00 corresponds to IEC 60529 |
| Device ambient temperature | -20…70 °C at Uc; -60…80 °C storage; -5…55 °C operation |
| Operating altitude | 3,000 m without power derating |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Mechanical robustness | Shocks contactor closed (15 Gn for 11 ms); vibrations contactor open (2 Gn, 5 - 300 Hz); vibrations contactor closed (4 Gn, 5 - 300 Hz); shocks contactor open (9 Gn for 11 ms) |
| Height | 400 mm |
| Width | 233 mm |
| Depth | 232 mm |
| Product weight | 11,35 kg |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 27,000 cm |
| VPE 1 width | 33,000 cm |
| VPE 1 length | 28,000 cm |
| Packaging weight (Lbs) | 11,491 kg |
| VPE 2 type | P06 |
| VPE 2 quantity | 8 |
| VPE 2 height | 75,000 cm |
| VPE 2 width | 60,000 cm |
| VPE 2 length | 80,000 cm |
| VPE 2 weight | 101,804 kg |