| Complementary |
| Compatibility code | LC1D |
| Pole contact composition | 4 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 40 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 450 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 450 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 50 A 40 °C - 10 min for power circuit; 120 A 40 °C - 1 min for power circuit; 240 A 40 °C - 10 s for power circuit; 380 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 63 A gG at |
| Average impedance | 2 mOhm - Ith 40 A 50 Hz for power circuit |
| Power dissipation per pole | 3.2 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 15 Mcycles |
| Electrical durability | 1.4 Mcycles 40 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 2…3 W at 50/60 Hz |
| Operating time | 4...19 ms opening; 12...22 ms closing |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1 |
| Product certifications | CCC; LROS (Lloyds register of shipping); RINA; UL; DNV; BV; CSA; GL; GOST |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (8 Gn for 11 ms) |
| Height | 91 mm |
| Width | 45 mm |
| Depth | 99 mm |
| Net weight | 0.425 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys; TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 40 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 11.700 cm |
| Package 1 Weight | 471.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.996 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 256 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 136.560 kg |
The LC1DT40P7 contactor from the TeSys Deca series by Schneider Electric is a 4-pole contactor for resistive loads, designed for use category AC-1. It features a rated operational current of 40 A in the main circuit and is equipped with a control circuit voltage of 230 V AC at 50/60 Hz. The device is designed for safe and reliable control of electrical loads in industrial applications, with the main circuit contacts configured as 4 NO contacts. Additionally, auxiliary contacts are integrated, consisting of one NO and one NC contact, mechanically linked to ensure suitability for secure control tasks. The coil is designed without an integrated control module, allowing flexible adaptation to various circuits.
Applications
This contactor is designed for use in industrial plants, particularly in applications involving resistive loads, such as heating systems, resistance operation, or other non-inductive loads. Use category AC-1 defines the application scope for low mechanical stress and continuous operation. Certifications according to CCC, LROS, RINA, UL, DNV, BV, CSA, GL, and GOST confirm suitability for international requirements, especially in shipbuilding and marine industries, as well as other safety-critical sectors.
Functions and Equipment in Detail
The device features secure current connections via Everlink and spring terminals, enabling quick and easy installation. The main circuit contacts are configured as 4 NO contacts, with a rated insulation voltage of 600 V for the main circuit, certified according to CSA and UL, and 690 V according to IEC 60947-4-1. The auxiliary contacts consist of one NO and one NC contact, mechanically linked to ensure secure signal transmission. The coil operates at 230 V AC with an inrush power of 70 VA at 50/60 Hz. The holding power consumption is 7.5 VA at 60 Hz and 7 VA at 50 Hz. The operating time is 4–19 ms for opening and 12–22 ms for closing.
Technology Explained Simply
The rated insulation voltage of 690 V for the main circuit and 600 V for the control circuit ensures high electrical safety. Overvoltage category III and pollution degree 3 indicate a robust construction suitable for operation in contaminated or industrial environments. The rated impulse withstand voltage is 6 kV, highlighting the device’s ability to absorb transient voltage surges. The mechanical life is 15 million switching cycles, while the electrical life is 1.4 million cycles, measured at 40 A AC-1 and rated voltage. The rated breaking capacity is 450 A at 440 V, demonstrating the contactor’s ability to safely interrupt current-carrying circuits under load.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include auxiliary switch blocks such as LADN40 (4 NO), LADN31 (3 NO + 1 NC), or LADN11 (1 NO + 1 NC), which can be mounted front-side. Time blocks such as LADT9R1V (power switch) or LADT4 (delayed inrush 10–180 s) enable time-controlled switching operations. Additionally, varistors (e.g., LAD-4VU) are available to limit overvoltages in the control circuit. Combining with control modules such as LAD4RCU (RC circuit) expands switching functions for specific applications.
Mounting and Installation
Mounting is done via screw terminals with a tightening torque of 1.8 Nm for the main circuit and 1.7 Nm for the control circuit, using screwdrivers with flat Ø 6, Phillips No. 2, or position No. 2. Dimensions are 45 mm (width) × 91 mm (height) × 99 mm (depth), allowing installation in standard control panels. Heat dissipation is 2–3 W at 50/60 Hz, limiting thermal load during operation. The maximum operating rate is 3600 switching cycles per hour at 60 °C, enabling high operational readiness in continuous applications.
Operational Advantages
The contactor offers high reliability through mechanically linked auxiliary contacts and mirror contacts, suitable for secure control tasks in safety applications. The use of Everlink and spring terminals ensures a stable and long-lasting current connection. Certifications according to international standards such as IEC 60947, UL, CSA, and GOST confirm suitability for demanding industrial and marine operating conditions. The high life expectancy and robust construction reduce maintenance and replacement intervals during operation.
Safety Level and Lifespan
The device meets safety level requirements B10d = 1369863 cycles at rated load and B10d = 20000000 cycles at mechanical load according to EN/ISO 13849-1. The mechanical life is 15 million cycles, and the electrical life is 1.4 million cycles at 40 A AC-1. The construction with a rated impulse withstand voltage of 6 kV and overvoltage category III makes the device suitable for environments with transient voltage surges. The rated insulation voltage of 690 V for the main circuit and 600 V for the control circuit ensures high electrical safety.