| Complementary |
| Compatibility code | LC1D |
| Pole contact composition | 4 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 25 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 250 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 250 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 30 A 40 °C - 10 min for power circuit; 61 A 40 °C - 1 min for power circuit; 105 A 40 °C - 10 s for power circuit; 210 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 40 A gG at |
| Average impedance | 2.5 mOhm - Ith 25 A 50 Hz for power circuit |
| Power dissipation per pole | 1.56 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 30 Mcycles |
| Electrical durability | 0.8 Mcycles 25 A AC-1 at Ue |
| Control circuit type | DC standard |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.1...0.25 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…60 °C):operational DC; 1...1.25 Uc (60…70 °C):operational DC |
| Inrush power in W | 5.4 W (at 20 °C) |
| Hold-in power consumption in W | 5.4 W at 20 °C |
| Operating time | 20 ±20 % ms opening; 63 ±15 % ms closing |
| Time constant | 28 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | CSA C22.2 No 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1 |
| Product certifications | DNV; GL; CCC; LROS (Lloyds register of shipping); RINA; BV; GOST; UL; CSA; CB |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 99 mm |
| Net weight | 0.365 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys; TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 25 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 5.500 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 12.000 cm |
| Package 1 Weight | 556.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 16 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 9.335 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 256 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 155.500 kg |
The LC1DT25BD contactor from the TeSys Deca series by Schneider Electric is a 4-pole contactor designed for use in industrial applications. It is intended for resistive loads and corresponds to usage category AC-1. The device features a control circuit voltage of 24 V DC and a rated operational current of 25 A. The integrated bidirectional peak-limiting diode suppressor protects the coil from voltage spikes and ensures reliable operation during sudden voltage changes. The main circuits are equipped with 4 make contacts, supplemented by additional auxiliary contacts in the configuration of 1 make + 1 break, which are mechanically linked to ensure secure signal transmission. The auxiliary contacts comply with standards IEC 60947-5-1 and IEC 60947-4-1, with the break contact designed as a mirror contact, which is relevant for safety applications.
Applications
This contactor is designed for use in industrial control and drive systems, particularly in installations with resistive loads such as heaters, lighting, or dynamic braking resistors. Category AC-1 defines the application scope for loads with low inductive components. The high rated breaking capacity of 250 A at 440 V enables use in systems with high inrush currents. The rated impulse voltage withstand of 6 kV and overvoltage category III make the device suitable for environments with increased electrical stress. Insulation resistances exceeding 10 MΩ in the signal circuit ensure reliable isolation between control and main circuits.
Functions and Equipment in Detail
Contacts are equipped with Everlink and spring terminals, enabling a secure and long-lasting current connection. The pickup and holding power are each 5.4 W at 20 °C. The operating time is 20 ±20 % ms for opening and 63 ±15 % ms for closing, ensuring fast response to control commands. The maximum operating rate is 3600 switching operations per hour at 60 °C, sufficient for continuous operating conditions. The mechanical life is 30 million switching cycles, and the electrical life is 0.8 million cycles at 25 A AC-1. The coil is designed for operating voltages between 0.7 and 1.25 Uc (24 V DC), with an operating temperature range of -40 to 70 °C, enabling use in various environments.
Technology Explained Simply
The integrated bidirectional diode suppressor protects the coil from inductive voltage spikes that can occur when the coil is switched off. This extends the coil’s lifespan and prevents disturbances in the control circuit. The mechanically linked auxiliary contacts ensure that the make and break operations occur synchronously, which is important for safety functions. Spring terminals allow for easy and secure connections without additional tools. The rated insulation voltage is 690 V for the signal circuit and 600 V for the main circuit, ensuring high electrical safety.
Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN04 (4 breakers) or LADN02 (2 breakers), time delay blocks such as LADT0 (pickup delayed 0.10–3.00 s) or LADT2 (pickup delayed 0.10–30.00 s), and interlocking blocks such as LAD6K10B (24 V AC/DC). For motor protection applications, motor protection circuit breakers such as GV2ME22 (20–25 A) or GV2L22 (25 A) are available. The protective cover LAD9ET1 is suitable for LC1 D09–D38 and DT20–DT40 units. The special diode LAD4TBDL and the freewheeling diode LAD4DDL can be used for additional protection functions.
Mounting and Installation
Mounting is done via screw terminals with a tightening torque of 1.7 Nm, using either flathead screwdrivers (Ø 6) or Phillips screwdrivers (No. 2). Dimensions are 45 mm (width) × 85 mm (height) × 99 mm (depth), enabling compatibility with standard control panels. The safety cover is integrated as standard, providing additional protection.
Operational Advantages
The contactor offers high operational reliability due to the integrated diode protection and mechanically linked auxiliary contacts. Its long service life and high operating rate make it suitable for continuous applications. Easy mounting and compatibility with various accessories increase flexibility in system design. Certifications according to CCC, GL, BV, LROS, CSA, DNV, RINA, UL, and GOST confirm compliance with international safety and quality standards.