| Additional features |
| Compatibility code | LC1D |
| Pole contact composition | 4 S |
| Safety cover | With |
| [Ith] conventional thermal current in free air | 10 A (at 60 °C) for signal circuits; 20 A (at 60 °C) for power circuits |
| [Irms] Rated making capacity | 140 A AC for Signalschaltkreis conforming to IEC 60947-5-1; 250 A DC for Signalschaltkreis conforming to IEC 60947-5-1; 250 A at 440 V for Stromkreis conforming to IEC 60947 |
| Rated breaking capacity | 250 A at 440 V for circuit, conforms to IEC 60947 |
| [Icw] rated short-time current withstand | 30 A 40 °C - 10 min for circuit; 61 A 40 °C - 1 min for circuit; 105 A 40 °C - 10 s for circuit; 210 A 40 °C - 1 s for circuit; 100 A - 1 s for signal circuit; 120 A - 500 ms for signal circuit; 140 A - 100 ms for signal circuit |
| Associated fuse | 10 A gG for signal circuit according to IEC 60947-5-1; 25 A gG at |
| Average impedance | 2.5 MOhm - Ith 20 A 50 Hz for circuit |
| Power dissipation per pole | 1,56 W AC-1 |
| [Ui] Rated insulation voltage | Circuit: 600 V CSA certified; Circuit: 600 V UL certified; Signal circuit: 690 V compliant with IEC 60947-1; Signal circuit: 600 V CSA certified; Signal circuit: 600 V UL certified; Circuit: 690 V compliant with IEC 60947-4-1 |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 6 kV corresponds to IEC 60947 |
| Security level rating | B10d = 1369863 cycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load corresponds to EN/ISO 13849-1 |
| Mechanical life | 15 Mcycles |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without integrated switching module |
| Control circuit voltage limits | 0.3 - 0.6 Uc (-40…70 °C): drop-out voltage AC 50/60 Hz; 0.8 - 1.1 Uc (-40…60 °C): operation AC 50 Hz; 0.85 - 1.1 Uc (-40…60 °C): operation AC 60 Hz; 1 - 1.1 Uc (60…70 °C): operation AC 50/60 Hz |
| Input power in VA | 70 VA 60 Hz cos phi 0.75 (at 20 °C); 70 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold power consumption in VA | 7.5 VA 60 Hz cos phi 0.3 (at 20 °C); 7 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat emission | 2…3 W at 50/60 Hz |
| Operating time | 4 - 19 ms opening; 12 - 22 ms closing |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Tightening moment | Control circuit: 1.7 Nm - on screw terminals - with flat screwdriver Ø 6; Control circuit: 1.7 Nm - on screw terminals - with Phillips screwdriver No. 2; Power circuit: 1.7 Nm - on screw terminals - with flat screwdriver Ø 6; Power circuit: 1.7 Nm - on screw terminals - with Phillips screwdriver No. 2; Control circuit: 1.7 Nm - on screw terminals - with screwdriver position No. 2; Power circuit: 1.7 Nm - on screw terminals - with screwdriver position No. 2 |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| Type of auxiliary contacts | Mechanically linked type 1 S + 1 NC complies with IEC 60947-5-1; Mirror contact type 1 NO complies with IEC 60947-4-1 |
| Signalling angular frequency | 25 - 400 Hz |
| Min. switching voltage | 17 V for signal circuit |
| Min. switching current | 5 mA for signal circuit |
| Insulation resistance | > 10 MΩ for signal circuits |
| Non-overlapping time | 1.5 ms with switching between normally open and normally closed contact; 1.5 ms with actuation between normally open and normally closed contact |
| Mounting bracket | Plate; rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys; TeSys Deca |
| Product or component type | Contactor |
| Device short name | LC1D |
| Application of contactor | resistive load |
| Application category | AC-1 |
| Pole description | 4P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 20 A (at |
| [Uc] control circuit voltage | 120 V AC 50/60 Hz |
| Mounting |
| Standards | CSA C22.2 No. 14; EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; UL 60947-4-1; IEC 60335-1 |
| Product certifications | RINA; BV; GL; LROS (Lloyds register of shipping); DNV; GOST; UL; CSA; CCC |
| Degree of protection (IP) | IP20 front side corresponds to IEC 60529 |
| Protection treatment | TH corresponds to IEC 60068-2-30 |
| Climate resistance | Complies with IACS E10 damp heat exposure; complies with IEC 60947-1 Annex Q Category D damp heat exposure |
| Device ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Operating altitude | 0 - 3.000 m |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Flame retardancy | V1 corresponds to UL 94 |
| Mechanical robustness | Vibrations contact open (2 Gn, 5 - 300 Hz); vibrations contact closed (4 Gn, 5 - 300 Hz); shocks contact closed (15 Gn for 11 ms); shocks contact open (10 Gn for 11 ms) |
| Height | 85 mm |
| Width | 45 mm |
| Depth | 92 mm |
| Product weight | 0,365 kg |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 5,5 cm |
| VPE 1 width | 9,5 cm |
| VPE 1 length | 11,2 cm |
| Packaging weight (Lbs) | 389 g |
| VPE 2 type | S02 |
| VPE 2 quantity | 16 |
| VPE 2 height | 15 cm |
| VPE 2 width | 30 cm |
| VPE 2 length | 40 cm |
| VPE 2 weight | 6,789 kg |
TeSys LC1D power contactor. 4-pole, 4 NO contacts. Additional auxiliary contacts - 1 NO + 1 NC contact, coil 120 V AC. Dimensions (WxHxD) 45x85x92 mm, weight 0.365 kg. Category AC-1. Without integrated circuit module. Quick and easy setup. Safe and durable power connection with Everlink and spring terminals. Suitable for safety applications due to mechanically coupled contacts and mirror contacts. Certifications according to RINA, BV, GL, LROS (Lloyds register of shipping), DNV, GOST, UL, CSA, CCC. Product standards in accordance with.