| Complementary |
| Compatibility code | LC1D |
| Pole contact composition | 4 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 200 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1260 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 350 A 40 °C - 10 min for power circuit; 600 A 40 °C - 1 min for power circuit; 1280 A 40 °C - 10 s for power circuit; 1800 A 40 °C - 1 s for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 315 A gG at |
| Average impedance | 0.45 mOhm - Ith 200 A 50 Hz for power circuit |
| Power dissipation per pole | 6 W AC-3; 6 W AC-3e; 28.1 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 684932 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 10000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 8 Mcycles |
| Electrical durability | 0.38 Mcycles 200 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz; DC |
| Coil technology | Built-in bidirectional peak limiting diode suppressor |
| Control circuit voltage limits | 0.8 Uc Min...1.1 Uc Max (-40…60 °C):operational AC/DC; 0.1 Uc Max (-40…60 °C):drop-out AC/DC |
| Inrush power in VA | 170 VA (at 20 °C) |
| Inrush power in W | 120 W (at 20 °C) |
| Hold-in power consumption in VA | 7.5 VA (at 20 °C) |
| Hold-in power consumption in W | 5.1 W at 20 °C |
| Heat dissipation | 1.5 W at 20 °C |
| Operating time | 10...80 ms opening; 20...90 ms closing |
| Maximum operating rate | 2400 cyc/h at 60 °C; 3600 cyc/h at Uc at 20 ºC |
| Tightening torque | Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver Philips No 2; Control circuit: 1.7 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 16.67...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; UL 60947-4-1; UL 60947-5-1; CSA C22.2 No 60947-4-1; CSA C22.2 No 60947-5-1; JIS C8201-4-1; JIS C8201-5-1; GB/T 14048.4; GB/T 14048.5 |
| Product certifications | CB Scheme; CCC; cULus; CE; UKCA; EU-RO-MR by DNV-GL |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | None conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C operation; 60…70 °C with derating; -60…80 °C storage |
| Operating altitude | 0...3000 m without derating |
| Fire resistance | 850 °C conforming to IEC 60695-2-11 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) conforming to IEC 60068-2-6; Vibrations contactor closed (4 Gn, 5...300 Hz) conforming to IEC 60068-2-6; Shocks contactor open (10 Gn for 11 ms) conforming to IEC 60068-2-27; Shocks contactor closed (15 Gn for 11 ms) conforming to IEC 60068-2-27 |
| Height | 152 mm |
| Width | 132 mm |
| Depth | 155 mm |
| Net weight | 3 kg |
| Logistical informations |
| Country of origin | CN |
| Main |
| Range | TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4; DC-1; DC-3; DC-5 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 200 A (at |
| [Uc] control circuit voltage | 48...130 V AC 50/60 Hz; 48...130 V DC |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 18.600 cm |
| Package 1 Width | 20.600 cm |
| Package 1 Length | 19.700 cm |
| Package 1 Weight | 3.306 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 30.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 7.115 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 16 |
| Package 3 Height | 73.500 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 66.918 kg |