| Complementary |
| Motor power kW | 25 kW at 220/230 V AC 50/60 Hz (AC-3); 45 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 415/440 V AC 50/60 Hz (AC-3); 55 kW at 500 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3); 45 kW at 1000 V AC 50/60 Hz (AC-3); 25 kW at 220/230 V AC 50/60 Hz (AC-3e); 45 kW at 380/400 V AC 50/60 Hz (AC-3e); 45 kW at 415/440 V AC 50/60 Hz (AC-3e); 55 kW at 500 V AC 50/60 Hz (AC-3e); 45 kW at 660/690 V AC 50/60 Hz (AC-3e); 45 kW at 1000 V AC 50/60 Hz (AC-3e); 15 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 7.5 hp at 120 V AC 60 Hz for 1 phase motors; 15 hp at 230/240 V AC 60 Hz for 1 phase motors; 30 hp at 200/208 V AC 60 Hz for 3 phases motors; 30 hp at 230/240 V AC 60 Hz for 3 phases motors; 60 hp at 460/480 V AC 60 Hz for 3 phases motors; 60 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 125 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1100 A at 440 V AC for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 1100 A 40 °C - 1 s for power circuit; 800 A 40 °C - 10 s for power circuit; 400 A 40 °C - 1 min for power circuit; 135 A 40 °C - 10 min for power circuit; 140 A - 100 ms for signalling circuit; 120 A - 500 ms for signalling circuit; 100 A - 1 s for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 200 A gG at |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 12.5 W AC-1; 7.2 W AC-3; 7.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 4 Mcycles |
| Electrical durability | 1.2 Mcycles 95 A AC-3; 1.3 Mcycles 125 A AC-1; 1.2 Mcycles 95 A AC-3e |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz; 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 1...1.1 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 245 VA 60 Hz cos phi 0.75 (at 20 °C); 245 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 26 VA 60 Hz cos phi 0.3 (at 20 °C); 26 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 6…10 W at 50/60 Hz |
| Operating time | 20...35 ms closing; 6...20 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Tightening torque | Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm; Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
| Product certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Shocks contactor open (8 Gn for 11 ms) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor closed (10 Gn for 11 ms) |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 130 mm |
| Net weight | 1.61 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 95 A (at |
| [Uc] control circuit voltage | 400 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 14.22 cm |
| Package 1 Width | 9.65 cm |
| Package 1 Length | 13.46 cm |
| Package 1 Weight | 1.57 kg |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 5 |
| Package 2 Height | 15 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 8.265 kg |
The LC1D95V7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It features three normally closed contacts in the main circuit and additionally includes one normally closed and one normally open contact in the auxiliary contact section. The rated operational voltage is 400 V AC at 50/60 Hz, with a rated operational current Ie of 95 A under AC-3 operation. The corresponding motor power is 45 kW at 400 V AC, enabling application in medium to large industrial drive systems. The device is designed for use categories AC-1, AC-3, AC-3e, and AC-4, making it suitable for both continuous operation and start/braking operations on electric motors.
Applications
This contactor is primarily used in industrial automation, particularly for controlling electric motors in production plants, conveyor systems, pump and fan installations. The combination of high rated current and additional auxiliary contacts makes it suitable for complex control logic, where signals need to be transmitted to other components or safety functions. Certifications according to DNV, BV, GL, GOST, LROS (Lloyds Register of Shipping), RINA, and CCC confirm its suitability for applications in marine technology, mechanical engineering, and process industries.
Functions and Equipment in Detail
The device is equipped with a coil for 400 V AC 50/60 Hz, ensuring secure and reliable actuation. The control circuit voltage range is 0.8 to 1.1 times the nominal voltage at operating temperatures from -40 °C to 55 °C (for 50 Hz) and -40 °C to 55 °C (for 60 Hz). The drop-out voltage is 0.3 to 0.6 times the nominal voltage. The pickup power is 245 VA at 50/60 Hz, and the holding power is 26 VA. The operating time is 20 to 35 ms for closing and 6 to 20 ms for opening. The maximum operating rate is 3600 switching operations per hour at 60 °C.
Technology Explained Simply
Current connections are made via Everlink and spring terminals, ensuring a secure and long-lasting connection even at high currents. The contacts are mechanically coupled and feature mirror contacts, increasing reliability in safety applications. The rated insulation voltage is 1000 V for the circuit according to IEC 60947-4-1, with an impulse voltage withstand of 8 kV. The overvoltage category is III, and the pollution degree is 3. The rated breaking capacity is 1100 A at 440 V, highlighting the contactor’s ability to interrupt short-circuit currents. The mechanical life is 4 million switching operations, and the electrical life is 1.2 million switching operations at 95 A AC-3.
Compatibility and Accessories
The contactor is equipped with the compatibility code LC1D, enabling use with various accessories from the TeSys series. Compatible accessories include auxiliary switch blocks such as LADN40 (4 normally closed), LADN11 (1 normally closed + 1 normally open), LADN31 (3 normally closed + 1 normally open), LADN22 (2 normally closed + 2 normally open), LADN20 (2 normally closed), LADN04 (4 normally open), LADN13 (1 normally closed + 3 normally open), LADN02 (2 normally open), as well as time delay blocks such as LADT0 (pickup delayed 0.10–3.00 s), LADT4 (pickup delayed 10.00–180.00 s), LADT2 (pickup delayed 0.10–30.00 s), LADR0 (drop-out delayed 0.10–3.00 s), LADR2 (drop-out delayed 1–30.00 s). Additionally, motor protection relays such as LRD3365 (80–104 A, 1NO+1NC, Class 10 A) and RC elements such as LA4-DA2N (380–415 VAC) are available to enhance safety and functionality.
Mounting and Installation
Mounting is done in standard control panels. Dimensions are 85 mm (width) × 127 mm (height) × 130 mm (depth). The tightening torques are 1.2 Nm for control circuit terminals (flat screwdriver Ø 6 or Phillips No. 2) and 12 Nm for main circuit terminals (flat screwdriver Ø 6 to Ø 8 or hexagonal socket 4 mm). Heat dissipation is between 6 and 10 W at 50/60 Hz. Power loss per pole is 12.5 W at AC-1, 7.2 W at AC-3 and AC-3e. The conventional thermal current rating is 125 A in the circuit at 60 °C.
Operational Advantages
The contactor offers high reliability through mechanically coupled contacts and mirror contacts, which is particularly beneficial in safety applications. The use of Everlink and spring terminals ensures a stable current connection. The high electrical and mechanical life reduces maintenance and replacement intervals. The combination with various auxiliary and time delay blocks allows flexible adaptation to different control requirements. Certifications according to international standards ensure suitability for global industrial applications.