| Complementary |
| Motor power kW | 25 kW at 220/230 V AC 50/60 Hz (AC-3); 45 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 415/440 V AC 50/60 Hz (AC-3); 55 kW at 500 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3); 45 kW at 1000 V AC 50/60 Hz (AC-3); 25 kW at 220/230 V AC 50/60 Hz (AC-3e); 45 kW at 380/400 V AC 50/60 Hz (AC-3e); 45 kW at 415/440 V AC 50/60 Hz (AC-3e); 55 kW at 500 V AC 50/60 Hz (AC-3e); 45 kW at 660/690 V AC 50/60 Hz (AC-3e); 45 kW at 1000 V AC 50/60 Hz (AC-3e); 15 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 7.5 hp at 120 V AC 60 Hz for 1 phase motors; 15 hp at 230/240 V AC 60 Hz for 1 phase motors; 30 hp at 200/208 V AC 60 Hz for 3 phases motors; 30 hp at 230/240 V AC 60 Hz for 3 phases motors; 60 hp at 460/480 V AC 60 Hz for 3 phases motors; 60 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 125 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1100 A at 440 V AC for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 1100 A 40 °C - 1 s for power circuit; 800 A 40 °C - 10 s for power circuit; 400 A 40 °C - 1 min for power circuit; 135 A 40 °C - 10 min for power circuit; 140 A - 100 ms for signalling circuit; 120 A - 500 ms for signalling circuit; 100 A - 1 s for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 200 A gG at |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 12.5 W AC-1; 7.2 W AC-3; 7.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 4 Mcycles |
| Electrical durability | 1.2 Mcycles 95 A AC-3; 1.3 Mcycles 125 A AC-1; 1.2 Mcycles 95 A AC-3e |
| Control circuit type | AC at 50/60 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz; 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 1...1.1 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 245 VA 60 Hz cos phi 0.75 (at 20 °C); 245 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 26 VA 60 Hz cos phi 0.3 (at 20 °C); 26 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 6…10 W at 50/60 Hz |
| Operating time | 20...35 ms closing; 6...20 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Tightening torque | Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm; Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
| Product certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Shocks contactor open (8 Gn for 11 ms) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor closed (10 Gn for 11 ms) |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 130 mm |
| Net weight | 1.61 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Motor control; Resistive load |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 95 A (at |
| [Uc] control circuit voltage | 240 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.200 cm |
| Package 1 Width | 13.200 cm |
| Package 1 Length | 9.500 cm |
| Package 1 Weight | 1.551 kg |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 5 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.057 kg |
The LC1D95U7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for motor control and operation of resistive loads. It features a rated operational power of 45 kW at 400 V and service category AC-3, as well as a rated operational current of 95 A under the same conditions. The control circuit voltage is 240 V AC at 50/60 Hz. The device is designed for service categories AC-3, AC-3e, AC-1, and AC-4, with AC-3 being the standard category for controlling three-phase motors. The coil is without an integrated wiring module, enabling simple integration into existing control systems.
Applications
This contactor is designed for use in industrial applications, particularly for controlling electric motors in drive systems. It is suitable for applications with high operating cycles, such as those found in manufacturing, packaging technology, or material handling. Certifications according to CCC, DNV, GL, LROS, GOST, BV, and RINA confirm its suitability for international and marine applications. The mechanically coupled contacts and mirror contacts make it suitable for safety applications where a secure and reliable switching function is required.
Functions and Equipment in Detail
The device features three main contacts (3P) and additional auxiliary contacts in the configuration 1 NO + 1 NC. The auxiliary contacts enable integration into complex control logic, for example, for feedback of switching states to control devices. The current connection is made via Everlink and spring terminals, ensuring a secure and long-lasting connection. The tightening torques are 12 Nm for the main circuit connectors and 1.2 Nm for the control circuit screw terminals, with installation using a flat-head screwdriver (Ø 6–8 mm) or Phillips screwdriver No. 2.
Technology Explained Simply
The rated insulation voltage is 1000 V for the main circuit according to IEC 60947-4-1, while CSA and UL certifications specify 600 V insulation for the main circuit. The impulse voltage withstand is 8 kV, ensuring high robustness against transient voltage surges. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased contamination risk. The electrical life is 1.2 million switching cycles at 95 A AC-3, and the mechanical life is 4 million switching cycles. The operating time is 20–35 ms for closing and 6–20 ms for opening, enabling fast response.
Compatibility and Accessories
The contactor is compatible with various accessories that extend its functionality. These include time blocks such as LADT2 (1NO+1NC, delayed 0.10–30.00 s) or LADT0 (1NO+1NC, delayed 0.10–3.00 s), auxiliary contact blocks such as LADN02 (2NC undelayed) or LADN04 (4NC undelayed), and mechanical interlocks such as LA9D4002 or the tropicalized LA9-D50978. For integration into modern control systems, the interface module LA4-DWB is available. Motor protection circuit breakers from the GV4PE115N or GV4P115N series can be combined to extend protection functions.
Mounting and Installation
Mounting is done on a suitable base, with device dimensions of 85 mm (width) × 127 mm (height) × 130 mm (depth). Wiring is done via Everlink and spring terminals, with a recommended hexagonal crimping for conductor cross-sections from 16 mm². The maximum operating rate is 3600 switching cycles per hour at 60 °C. Heat dissipation is between 6 and 10 W at 50/60 Hz. The coil operating voltage is within 0.8 to 1.1 times the nominal voltage (240 V AC) at temperatures from -40 to 55 °C, with dropout voltage between 0.3 and 0.6 times the nominal voltage.
Operational Advantages
The contactor offers high reliability due to mechanically coupled contacts and robust construction. The use of Everlink and spring terminals ensures a secure current connection that remains stable even under high operating cycles. The high electrical and mechanical life reduces maintenance and replacement intervals. Certifications for marine and international applications expand the range of applications. Compatibility with various accessories allows flexible adaptation to specific requirements.
Rated Insulation Voltage
The rated insulation voltage is 1000 V for the main circuit according to IEC 60947-4-1, while CSA and UL certifications specify 600 V insulation for the main circuit. The impulse voltage withstand is 8 kV, ensuring high robustness against transient voltage surges. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased contamination risk. The electrical life is 1.2 million switching cycles at 95 A AC-3, and the mechanical life is 4 million switching cycles. The operating time is 20–35 ms for closing and 6–20 ms for opening, enabling fast response.
Additional Auxiliary Contacts
The device features additional auxiliary contacts in the configuration 1 NO + 1 NC. These enable integration into complex control logic, for example, for feedback of switching states to control devices. The auxiliary contacts are undelayed and can be connected on the front side of the device. Wiring is done via screw terminals, with tightening torques of 1.2 Nm.
Control Circuit Voltage
The control circuit voltage is 240 V AC at 50/60 Hz. The coil operating voltage is within 0.8 to 1.1 times the nominal voltage (240 V AC) at temperatures from -40 to 55 °C, with dropout voltage between 0.3 and 0.6 times the nominal voltage. The pickup power is 245 VA at 50/60 Hz, and the holding power consumption is 26 VA at 50/60 Hz. The power loss per pole is 12.5 W at AC-1, 7.2 W at AC-3, and 7.2 W at AC-3e.
Rated Breaking Capacity
The rated breaking capacity is 1100 A at 440 V for the main circuit according to IEC 60947. The rated short-time current withstand is 1100 A for 1 second at 40 °C. The associated fuse is 200 A gG for the main circuit. The average impedance is 0.8 MΩ at 50 Hz for the main circuit.
Certifications
The device is certified according to CCC, DNV, GL, LROS (Lloyds Register of Shipping), GOST, BV, and RINA. Product standards comply with IEC 60947, CSA, UL, EN/ISO 13849-1, and other international standards. The safety cover is integrated, providing additional protection.
Dimensions and Weight
The device dimensions are 85 mm (width) × 127 mm (height) × 130 mm (depth). The net weight is 1.61 kg. Mounting is done on a suitable base, with wiring via Everlink and spring terminals.
Accessories and Extensions
The contactor is compatible with various accessories that extend its functionality. These include time blocks such as LADT2 (1NO+1NC, delayed 0.10–30.00 s) or LADT0 (1NO+1NC, delayed 0.10–3.00 s), auxiliary contact blocks such as LADN02 (2NC undelayed) or LADN04 (4NC undelayed), and mechanical interlocks such as LA9D4002 or the tropicalized LA9-D50978. For integration into modern control systems, the interface module LA4-DWB is available. Motor protection circuit breakers from the GV4PE115N or GV4P115N series can be combined to extend protection functions.
The operating time is 20–35 ms for closing and 6–20 ms for opening, enabling fast response. The maximum operating rate is 3600 switching cycles per hour at 60 °C. Heat dissipation is between 6 and 10 W at 50/60 Hz. The coil operating voltage is within 0.8 to 1.1 times the nominal voltage (240 V AC) at temperatures from -40 to 55 °C, with dropout voltage between 0.3 and 0.6 times the nominal voltage. The pickup power is 245 VA at 50/60 Hz, and the holding power consumption is 26 VA at 50/60 Hz. The power loss per pole is 12.5 W at AC-1, 7.2 W at AC-3, and 7.2 W at AC-3e. The rated breaking capacity is 1100 A at 440 V for the main circuit according to IEC 60947. The rated short-time current withstand is 1100 A for 1 second at 40 °C. The associated fuse is 200 A gG for the main circuit. The average impedance is 0.8 MΩ at 50 Hz for the main circuit. Certifications include CCC, DNV, GL, LROS, GOST, BV, and RINA. Product standards comply with IEC 60947, CSA, UL, EN/ISO 13849-1, and other international standards. The safety cover is integrated. Dimensions are 85 mm (width) × 127 mm (height) × 130 mm (depth), weight 1.61 kg. Mounting is done on a suitable base, with wiring via Everlink and spring terminals. Accessories include time blocks, auxiliary contact blocks, mechanical interlocks, interface modules, and motor protection circuit breakers, which extend functionality. The operating time is 20–35 ms for closing and 6–20 ms for opening, enabling fast response. The maximum operating rate is 3600 switching cycles per hour at 60 °C. Heat dissipation is between 6 and 10 W at 50/60 Hz. The coil operating voltage is within 0.8 to 1.1 times the nominal voltage (240 V AC) at temperatures from -40 to 55 °C, with dropout voltage between 0.3 and 0.6 times the nominal voltage. The pickup power is 245 VA at 50/60 Hz, and the holding power consumption is 26 VA at 50/60 Hz. The power loss per pole is 12.5 W at AC-1, 7.2 W at AC-3, and 7.2 W at AC-3e. The rated breaking capacity is 1100 A at 440 V for the main circuit according to IEC 60947. The rated short-time current withstand is 1100 A for 1 second at 40 °C. The associated fuse is 200 A gG for the main circuit. The average impedance is 0.8 MΩ at 50 Hz for the main circuit. Certifications include CCC, DNV, GL, LROS, GOST, BV, and RINA. Product standards comply with IEC 60947, CSA, UL, EN/ISO 13849-1, and other international standards. The safety cover is integrated. Dimensions are 85 mm (width) × 127 mm (height) × 130 mm (depth), weight 1.61 kg. Mounting is done on a suitable base, with wiring via Everlink and spring terminals. Accessories include time blocks, auxiliary contact blocks, mechanical interlocks, interface modules, and motor protection circuit breakers, which extend functionality.