| Complementary |
| Motor power kW | 25 kW at 220/230 V AC 50/60 Hz (AC-3); 45 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 415/440 V AC 50/60 Hz (AC-3); 55 kW at 500 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3); 45 kW at 1000 V AC 50/60 Hz (AC-3); 25 kW at 220/230 V AC 50/60 Hz (AC-3e); 45 kW at 380/400 V AC 50/60 Hz (AC-3e); 45 kW at 415/440 V AC 50/60 Hz (AC-3e); 55 kW at 500 V AC 50/60 Hz (AC-3e); 45 kW at 660/690 V AC 50/60 Hz (AC-3e); 45 kW at 1000 V AC 50/60 Hz (AC-3e); 15 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 7.5 hp at 120 V AC 60 Hz for 1 phase motors; 15 hp at 230/240 V AC 60 Hz for 1 phase motors; 30 hp at 200/208 V AC 60 Hz for 3 phases motors; 30 hp at 230/240 V AC 60 Hz for 3 phases motors; 60 hp at 460/480 V AC 60 Hz for 3 phases motors; 60 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 125 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1100 A at 440 V AC for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 1100 A 40 °C - 1 s for power circuit; 800 A 40 °C - 10 s for power circuit; 400 A 40 °C - 1 min for power circuit; 135 A 40 °C - 10 min for power circuit; 140 A - 100 ms for signalling circuit; 120 A - 500 ms for signalling circuit; 100 A - 1 s for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 200 A gG at |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 12.5 W AC-1; 7.2 W AC-3; 7.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 10 Mcycles |
| Electrical durability | 1.2 Mcycles 95 A AC-3; 1.3 Mcycles 125 A AC-1; 1.2 Mcycles 95 A AC-3e |
| Control circuit type | AC at 50 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50 Hz; 0.85...1.1 Uc (-40…55 °C):operational AC 50 Hz; 1...1.1 Uc (55…70 °C):operational AC 50 Hz |
| Inrush power in VA | 200 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 20 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 6…10 W at 50 Hz |
| Operating time | 20...35 ms closing; 6...20 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Tightening torque | Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm; Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
| Product certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Shocks contactor open (8 Gn for 11 ms) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor closed (10 Gn for 11 ms) |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 130 mm |
| Net weight | 1.61 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 95 A (at |
| [Uc] control circuit voltage | 380 V AC 50 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.500 cm |
| Package 1 Width | 10.500 cm |
| Package 1 Length | 14.000 cm |
| Package 1 Weight | 1.564 kg |
| Unit Type of Package 2 | S03 |
| Number of Units in Package 2 | 8 |
| Package 2 Height | 30 cm |
| Package 2 Width | 30 cm |
| Package 2 Length | 40 cm |
| Package 2 Weight | 12.932 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 64 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 80.000 cm |
| Package 3 Length | 60.000 cm |
| Package 3 Weight | 111.456 kg |
The LC1D95Q5 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for controlling motors and resistive loads. It is designed for use in industrial installations where reliable and safe switching of electrical current is required. The device has a rated operational power of 45 kW at 400 V AC-3 and a rated operational current of 95 A. The control circuit voltage is 380 V AC at 50 Hz, making it suitable for standard industrial applications. The coil is designed without an integrated switching module, enabling flexible integration into existing control systems.
This contactor is approved for use categories AC-1, AC-3, AC-3e, and AC-4, making it suitable for both continuous loads and motor drives with high inrush currents. It can be used in installations with 3-phase motors, with motor power reaching up to 60 hp (460/480 V AC, 60 Hz) depending on voltage. Certifications according to GOST, CCC, DNV, GL, LROS, BV, and RINA also make it suitable for marine and safety-critical applications.
The device features 3 main circuit closing contacts and additional auxiliary contacts configured as 1 closing + 1 opening contact. These auxiliary contacts are used for signal processing and status feedback in control systems. The contacts are mechanically coupled and feature mirror contacts, increasing reliability in safety applications. Electrical connections are made via Everlink and spring terminals, ensuring a secure and long-lasting connection. The safety cover protects against unintended access to live parts.
The rated insulation voltage is 1000 V for the power circuit according to IEC 60947-4-1 and 690 V for the signal circuit according to IEC 60947-1. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with high stress. The rated impulse withstand voltage is 8 kV, protecting the device against transient voltage surges. The mechanical life is 10 million switching cycles, while the electrical life is 1.2 million switching cycles at 95 A AC-3. The operating time is 20–35 ms for closing and 6–20 ms for opening, enabling fast response. The maximum operating rate is 3600 switching operations per hour at 60 °C.
The contactor is compatible with various accessory modules that extend its functionality. These include auxiliary switch blocks such as LAD8N02 or LADN02, time delay blocks such as LADR0 or LADT4, overvoltage limiters such as LA4DE2U, and electronic timer modules such as LA4DT4U. These modules can be used to expand control functions, introduce time delays, or provide protection functions. They are connected via designated terminals on the device.
Mounting is done via designated mounting points. The tightening torques are specified: 1.2 Nm for screw terminals in the control circuit (with flat screwdriver Ø 6 or Phillips No. 2) and 12 Nm for connectors in the power circuit (with flat screwdriver Ø 6–8 or hexagonal screw head 4 mm). Dimensions are 85 mm (width) × 127 mm (height) × 130 mm (depth). Heat dissipation is between 6 and 10 W at 50 Hz, which should be considered during cooling planning.
The contactor offers high reliability due to mechanically coupled contacts and long service life. The use of Everlink and spring terminals ensures a stable electrical connection. Integrated auxiliary contacts allow easy integration into control systems. Certifications for various safety and industrial standards increase application flexibility. The operating rate of 3600 operations per hour at 60 °C makes it suitable for high-load applications. The coil rated at 380 V AC 50 Hz is designed for standard mains voltages, enabling easy integration into existing installations.