| Complementary |
| Motor power kW | 25 kW at 220/230 V AC 50/60 Hz (AC-3); 45 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 415/440 V AC 50/60 Hz (AC-3); 55 kW at 500 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3); 45 kW at 1000 V AC 50/60 Hz (AC-3); 25 kW at 220/230 V AC 50/60 Hz (AC-3e); 45 kW at 380/400 V AC 50/60 Hz (AC-3e); 45 kW at 415/440 V AC 50/60 Hz (AC-3e); 55 kW at 500 V AC 50/60 Hz (AC-3e); 45 kW at 660/690 V AC 50/60 Hz (AC-3e); 45 kW at 1000 V AC 50/60 Hz (AC-3e); 15 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power hp | 7.5 hp at 120 V AC 60 Hz for 1 phase motors; 15 hp at 230/240 V AC 60 Hz for 1 phase motors; 30 hp at 200/208 V AC 60 Hz for 3 phases motors; 30 hp at 230/240 V AC 60 Hz for 3 phases motors; 60 hp at 460/480 V AC 60 Hz for 3 phases motors; 60 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 125 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1100 A at 440 V AC for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 1100 A 40 °C - 1 s for power circuit; 800 A 40 °C - 10 s for power circuit; 400 A 40 °C - 1 min for power circuit; 135 A 40 °C - 10 min for power circuit; 140 A - 100 ms for signalling circuit; 120 A - 500 ms for signalling circuit; 100 A - 1 s for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 200 A gG at |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 12.5 W AC-1; 7.2 W AC-3; 7.2 W AC-3e |
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1; Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1.3 Mcycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20 Mcycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 4 Mcycles |
| Electrical durability | 1.2 Mcycles 95 A AC-3; 1.3 Mcycles 125 A AC-1; 1.2 Mcycles 95 A AC-3e |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.8...1.1 Uc (-40…55 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…55 °C):operational AC 60 Hz; 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 1...1.1 Uc (55…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 245 VA 60 Hz cos phi 0.75 (at 20 °C); 245 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 26 VA 60 Hz cos phi 0.3 (at 20 °C); 26 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 6…10 W at 50/60 Hz |
| Operating time | 20...35 ms closing; 6...20 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Tightening torque | Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm; Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
| Product certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Shocks contactor open (8 Gn for 11 ms) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor closed (10 Gn for 11 ms) |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 130 mm |
| Net weight | 1.61 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 95 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 13.500 cm |
| Package 1 Width | 9.500 cm |
| Package 1 Length | 14.000 cm |
| Package 1 Weight | 1.563 kg |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 5 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 8.133 kg |
| Unit Type of Package 3 | P06 |
| Number of Units in Package 3 | 80 |
| Package 3 Height | 75.000 cm |
| Package 3 Width | 60.000 cm |
| Package 3 Length | 80.000 cm |
| Package 3 Weight | 133.060 kg |
The LC1D95P7 contactor from the TeSys series by Schneider Electric is a 3-pole contactor for controlling electrical loads, particularly for motor drives and resistive loads. It features a rated operational current of 95 A at AC-3 operation and a supply voltage of 400 V, with a rated operational power of 45 kW at AC-3. The control circuit voltage is 230 V AC at 50/60 Hz. The device is designed for use categories AC-1, AC-3, AC-3e, and AC-4, making it suitable for a wide range of applications in industrial automation. The main circuit contacts are configured as 3 normally closed contacts, supplemented by additional auxiliary contacts in the configuration of 1 normally closed + 1 normally open, which can be used for signaling and control tasks.
Applications
The contactor is designed for use in industrial plants, particularly in drive technology, where it is used to control electric motors. The AC-3e category enables control of motors with high starting power, while AC-4 is suitable for frequent start-stop operations. Certifications according to LROS, DNV, GOST, RINA, CCC, BV, and GL demonstrate suitability for marine and industrial applications, especially in safety-critical environments. The mechanically interlocked contacts and mirror contacts enhance reliability in safety applications.
Functions and Equipment in Detail
The device features a coil with a nominal voltage of 230 V AC, operating at 50/60 Hz. The pickup power is 245 VA, and the holding power is 26 VA. The operating time is 20–35 ms for closing and 6–20 ms for opening. The maximum operating rate is 3600 switching operations per hour at 60 °C. The contacts are equipped with Everlink and spring terminals, ensuring a secure and long-lasting electrical connection. The pickup torques are 1.2 Nm for control circuit terminals and 12 Nm for main circuit connectors.
Technology Explained Simply
The rated insulation voltage is 1000 V for the circuit according to IEC 60947-4-1, ensuring high electrical safety. The overvoltage category III and pollution degree 3 indicate suitability for industrial environments with increased stress. The rated impulse withstand voltage is 8 kV, ensuring robustness against transient voltage surges. The rated breaking capacity is 1100 A at 440 V, highlighting the ability to safely interrupt short-circuit currents. The conventional thermal current rating is 125 A in the circuit at 60 °C, describing the thermal load capacity under real operating conditions.
Compatibility and Accessories
The contactor is compatible with various accessory modules, including auxiliary switch blocks such as LAD8N11, LADN13, LADN40, LADN22, LADN20, LADN02, LADN11, LADN31, LAD8N20, LAD8N02, delayed auxiliary switch blocks LAD-S2, LAD-R4, time blocks such as LADT4, LADT0, LADT2, LADR2, time modules such as LA4-DT0U, LA4DT4U, as well as motor protection relays such as LRD3365 and interface modules such as LA4-DFB. These modules extend the functionality of the contactor for specific control and protection requirements.
Mounting and Installation
Mounting is done via integrated plug and screw terminals. Dimensions are 85 mm (width) × 127 mm (height) × 130 mm (depth), and the net weight is 1.61 kg. Installation is in standard control panels, where spring terminals and Everlink technology enable quick and secure connections. The coil is designed without an integrated wiring module, allowing flexible integration into existing control systems.
Operational Advantages
The mechanical life is 4 million switching operations, and the electrical life is 1.2 million switching operations at 95 A AC-3. The power loss per pole is 12.5 W at AC-1 and 7.2 W at AC-3 and AC-3e, ensuring efficient energy use. The heat dissipation is between 6 and 10 W at 50/60 Hz. The safety cover protects against accidental contact with the contacts. Certifications according to EN/ISO 13849-1 with B10d values of 1.3 million switching operations at rated load and 20 million at mechanical load underscore reliability in safety-critical applications.