| Additional features |
| Motor power (kW) | 25 kW at 220/230 V AC 50/60 Hz (AC-3); 45 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 415/440 V AC 50/60 Hz (AC-3); 55 kW at 500 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3); 25 kW at 220/230 V AC 50/60 Hz (AC-3e); 45 kW at 380/400 V AC 50/60 Hz (AC-3e); 45 kW at 415/440 V AC 50/60 Hz (AC-3e); 55 kW at 500 V AC 50/60 Hz (AC-3e); 45 kW at 660/690 V AC 50/60 Hz (AC-3e); 15 kW at 400 V AC 50/60 Hz (AC-4) |
| Motor power HP (UL / CSA standards) | 7.5 hp at 120 V AC 60 Hz for 1-phase motors; 15 hp at 230/240 V AC 60 Hz for 1-phase motors; 30 hp at 200/208 V AC 60 Hz for 3-phase motors; 30 hp at 230/240 V AC 60 Hz for 3-phase motors; 60 hp at 460/480 V AC 60 Hz for 3-phase motors; 60 hp at 575/600 V AC 60 Hz for 3-phase motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 S |
| Safety cover | With |
| [Ith] conventional thermal current in free air | 10 A (at 60 °C) for signal circuits; 125 A (at 60 °C) for power circuits |
| [Irms] Rated making capacity | 1100 A at 440 V AC for circuit conforming to IEC 60947; 140 A AC for signal circuit conforming to IEC 60947-5-1; 250 A DC for signal circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for circuit, corresponds to IEC 60947 |
| [Icw] rated short-time current withstand | 1100 A 40 °C - 1 s for power circuit; 800 A 40 °C - 10 s for power circuit; 400 A 40 °C - 1 min for power circuit; 135 A 40 °C - 10 min for power circuit; 140 A - 100 ms for signal circuit; 120 A - 500 ms for signal circuit; 100 A - 1 s for signal circuit |
| Associated fuse | 10 A gG for signal circuits complies with IEC 60947-5-1; 200 A gG at |
| Average impedance | 0.8 MOhm - Ith 125 A 50 Hz for circuit |
| Power dissipation per pole | 12,5 W AC-1; 7,2 W AC-3; 7,2 W AC-3e |
| [Ui] Rated insulation voltage | Circuit: 1000 V corresponds to IEC 60947-4-1; Signal circuit: 690 V corresponds to IEC 60947-1 |
| Over voltage category | III |
| Pollution degree | 3 |
| [Uimp] Rated impulse voltage withstand | 8 kV corresponds to IEC 60947 |
| Security level rating | B10d = 1.3 Mcycles contactor with rated load corresponds to EN/ISO 13849-1; B10d = 20 Mcycles contactor with mechanical load corresponds to EN/ISO 13849-1 |
| Mechanical life | 10 Mcycles |
| Electrical lifetime | 1.2 Mcycles 95 A AC-3; 1.3 Mcycles 125 A AC-1; 1.2 Mcycles 95 A AC-3e |
| Control circuit type | DC Standard |
| Coil technology | Without integrated switching module |
| Control circuit voltage limits | 0.1 - 0.3 Uc (-40…70 °C): drop-out voltage DC; 0.85 - 1.1 Uc (-40…55 °C): operation DC; 1 - 1.1 Uc (55…70 °C): operation DC |
| Absorption power in W | 22 W (at 20 °C) |
| Holding power consumption in W | 22 W at 20 °C |
| Operating time | 95 - 130 ms closing; 20 - 35 ms opening |
| Time constant | 75 ms |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Connections - terminals | Control circuit: Ring terminal lugs - outer diameter: 8 mm; Power circuit: Rails 1 - rail cross-section: 3 x 16 mm; Power circuit: Ring terminal lugs - outer diameter: 17 mm |
| Configuration of auxiliary contacts | 1 S + 1 Ö |
| Type of auxiliary contacts | Mechanically linked type 1 S + 1 NC complies with IEC 60947-5-1; Mirror contact type 1 NO complies with IEC 60947-4-1 |
| Signalling angular frequency | 25 - 400 Hz |
| Min. switching voltage | 17 V for signal circuit |
| Min. switching current | 5 mA for signal circuit |
| Insulation resistance | > 10 MΩ for signal circuits |
| Non-overlapping time | 1.5 ms with switching between normally open and normally closed contact; 1.5 ms with actuation between normally open and normally closed contact |
| Mounting bracket | Rail; Plate |
| Contractual warranty |
| Warranty (in months) | 18 |
| Main features |
| Product series | TeSys |
| Product or component type | Contactor |
| Device short name | LC1D |
| Application of contactor | Motor control; resistive load |
| Application category | AC-3; AC-3e; AC-1; AC-4 |
| Pole description | 3P |
| [Ue] Rated operational voltage | Circuit: |
| [Ie] rated operational current | 95 A (at |
| [Uc] control circuit voltage | 24 V DC |
| Mounting |
| Standards | EN/IEC 60947-1; EN/IEC 60947-4-1; EN/IEC 60947-5-1; GB/T 14048.4 |
| Product certifications | IECEE CB-Scheme; CCC; EAC; LROS (Lloyds register of shipping); RINA; BV; DNV-GL |
| Degree of protection (IP) | IP20 front side corresponds to IEC 60529 |
| Protection treatment | TH corresponds to IEC 60068-2-30 |
| Climate resistance | complies with IACS E10 damp heat exposure |
| Device ambient temperature | -40…60 °C; 60…70 °C with power reduction |
| Operating altitude | 0 - 3.000 m |
| Fire-resistance | 850 °C corresponds to IEC 60695-2-1 |
| Flame retardancy | V1 corresponds to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5 - 300 Hz); shocks contactor open (8 Gn for 11 ms); vibrations contactor closed (3 Gn, 5 - 300 Hz); shocks contactor closed (10 Gn for 11 ms) |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 186 mm |
| Product weight | 2,61 kg |
| Packaging units |
| VPE 1 type | PCE |
| Number of devices per package | 1 |
| VPE 1 height | 21,0 cm |
| VPE 1 width | 14,0 cm |
| VPE 1 length | 10,0 cm |
| Packaging weight (Lbs) | 2,34 kg |