| Complementary |
| Motor power kW | 22 kW at 220/230 V AC 50/60 Hz (AC-3); 37 kW at 380/400 V AC 50/60 Hz (AC-3); 37 kW at 415 V AC 50/60 Hz (AC-3); 37 kW at 440 V AC 50/60 Hz (AC-3); 37 kW at 500 V AC 50/60 Hz (AC-3); 37 kW at 660/690 V AC 50/60 Hz (AC-3); 22 kW at 220/230 V AC 50/60 Hz (AC-3e); 37 kW at 380/400 V AC 50/60 Hz (AC-3e); 37 kW at 415 V AC 50/60 Hz (AC-3e); 37 kW at 440 V AC 50/60 Hz (AC-3e); 37 kW at 500 V AC 50/60 Hz (AC-3e); 37 kW at 660/690 V AC 50/60 Hz (AC-3e) |
| Motor power hp | 5 hp at 115 V AC 60 Hz for 1 phase motors; 10 hp at 230/240 V AC 60 Hz for 1 phase motors; 20 hp at 200/208 V AC 60 Hz for 3 phases motors; 20 hp at 230/240 V AC 60 Hz for 3 phases motors; 40 hp at 460/480 V AC 60 Hz for 3 phases motors; 50 hp at 575/600 V AC 60 Hz for 3 phases motors |
| Compatibility code | LC1D |
| Pole contact composition | 3 NO |
| Protective cover | With |
| [Ith] conventional free air thermal current | 10 A (at 60 °C) for signalling circuit; 80 A (at 60 °C) for power circuit |
| Irms rated making capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 1000 A at 440 V AC for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 640 A 40 °C - 10 s for power circuit; 900 A 40 °C - 1 s for power circuit; 110 A 40 °C - 10 min for power circuit; 260 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit |
| Associated fuse rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1; 125 A gG at |
| Average impedance | 1.5 mOhm - Ith 80 A 50 Hz for power circuit |
| Power dissipation per pole | 9.6 W AC-1; 6.3 W AC-3; 6.3 W AC-3e |
| [Ui] rated insulation voltage | Signalling circuit: 690 V conforming to IEC 60947-1; Power circuit: 690 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 6 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 6 Mcycles |
| Electrical durability | 0.7 Mcycles 80 A AC-1 at Ue |
| Control circuit type | AC at 50/60 Hz standard |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz |
| Inrush power in VA | 140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 4…5 W at 50/60 Hz |
| Operating time | 4...19 ms opening; 12...26 ms closing |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Auxiliary contact composition | 1 NO + 1 NC |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Signalling circuit frequency | 25...400 Hz |
| Minimum switching voltage | 17 V for signalling circuit |
| Minimum switching current | 5 mA for signalling circuit |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
| Product certifications | CCC; CSA; EAC; UL; KC; DNV-GL; LROS (Lloyds register of shipping) |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms) |
| Height | 122 mm |
| Width | 55 mm |
| Depth | 120 mm |
| Net weight | 0.86 kg |
| Logistical informations |
| Country of origin | ID |
| Main |
| Range | TeSys; TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-3e; AC-1; AC-4 |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: 690 V AC 25...400 Hz; Power circuit: 300 V DC |
| [Ie] rated operational current | 80 A (at |
| [Uc] control circuit voltage | 230 V AC 50/60 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 6.200 cm |
| Package 1 Width | 13.500 cm |
| Package 1 Length | 15.500 cm |
| Package 1 Weight | 927.000 g |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 10 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 9.781 kg |
The LC1D80AP7 contactor from the TeSys Deca series by Schneider Electric is a 3-pole contactor for controlling motors and resistive loads. It features a rated operational current of 80 A and is designed for use categories AC-1, AC-3, and AC-3e, supporting a motor power of 37 kW at 400 V AC-3. The control circuit voltage is 230 V AC at 50/60 Hz, making it suitable for standard industrial networks. The device is designed without an integrated wiring module, enabling flexible integration into existing control systems.
Applications
This contactor is designed for controlling electric drives in industrial plants, particularly in applications with medium to high loads, such as in manufacturing, packaging technology, or conveyor system control. The AC-3e use category allows operation under special drive conditions, such as those found in crane systems or pumps. The rated insulation voltage of 690 V and overvoltage category III make it suitable for installations with increased electrical stress.
Functions and Equipment in Detail
The device features 3 normally closed contacts in the main circuit and an additional auxiliary switch block with 1 normally closed and 1 normally open contact, which can be used for signaling functions in control systems. The contacts are mechanically coupled and equipped with mirror contacts, enhancing reliability in safety applications. Spring terminals and Everlink technology ensure a secure and long-lasting electrical connection, remaining stable even under high operational loads. The maximum operating rate is 3600 switching operations per hour at 60 °C, enabling high dynamic performance during operation.
Technology Explained Simply
The contactor is rated for an operating voltage of 690 V AC in the main circuit and 300 V DC. The rated impulse voltage withstand is 6 kV, ensuring high electrical stability during transient voltage surges. The conventional thermal current rating (Ith) is 80 A in the main circuit at 60 °C, defining the thermal load capacity under real operating conditions. The electrical life is 0.7 million switching cycles at 80 A AC-1, while the mechanical life is 6 million cycles. The operating time is 4–19 ms for opening and 12–26 ms for closing, enabling fast response to control signals.
Compatibility and Accessories
The contactor is compatible with various accessory modules, including delayed auxiliary switch blocks (e.g. LAD-R4, LADR2, LADR0), time blocks (e.g. LADT0, LADT2), auxiliary switch blocks (e.g. LADN31, LADN40, LADN20), and interlocking blocks (e.g. LAD6K10M). These modules extend the functionality of the contactor for specific applications, such as time delays, mechanical interlocks, or additional signal contacts. The coil technology without an integrated wiring module allows flexible adaptation to existing circuit diagrams.
Mounting and Installation
Mounting is performed in standard control panels using screws or mounting rails. Dimensions are 55 mm (width) × 122 mm (height) × 120 mm (depth), allowing it to fit in typical enclosures. Wiring is done via spring terminals, ensuring a secure and durable connection. Installation and maintenance must only be carried out by qualified personnel, as specified in the manufacturer’s instructions.
Operational Advantages
The contactor offers high operational safety through mechanically coupled contacts and mirror contacts, increasing reliability in critical applications. The high electrical and mechanical life, along with fast operating time, ensure efficient and low-maintenance operation. Certifications according to CCC, CSA, EAC, UL, KC, DNV-GL, and LROS (Lloyds Register of Shipping) confirm suitability for international applications, including marine environments. The heat dissipation is 4–5 W at 50/60 Hz, minimizing thermal load in the enclosure.