| Complementary |
| Motor power kW | 22 kW at 220/230 V AC 50 Hz (AC-3); 37 kW at 380/400 V AC 50 Hz (AC-3); 45 kW at 415 V AC 50 Hz (AC-3); 45 kW at 440 V AC 50 Hz (AC-3); 55 kW at 500 V AC 50 Hz (AC-3); 45 kW at 660/690 V AC 50 Hz (AC-3); 45 kW at 1000 V AC 50 Hz (AC-3) |
| Pole contact composition | 3 NO |
| Protective cover | With |
| Auxiliary contacts type | type mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO + 1 NC |
| [Ui] rated insulation voltage | Power circuit: 1000 V conforming to IEC 60947-4-1; Signalling circuit: 690 V conforming to IEC 60947-1 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Overvoltage category | III |
| [Ith] conventional free air thermal current | 125 A (at 60 °C) for power circuit; 10 A (at 60 °C) for signalling circuit |
| Irms rated making capacity | 1100 A at 440 V for power circuit conforming to IEC 60947; 140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| Associated fuse rating | 200 A gG at |
| Time constant | 75 ms |
| Control circuit type | DC wide range |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.1...0.3 Uc (-40…70 °C):drop-out DC; 0.7...1.25 Uc (-40…50 °C):operational DC; 1...1.25 Uc (50…70 °C):operational DC |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 12.5 W AC-1; 5.1 W AC-3; 6.5 W AC-3e |
| Minimum switching current | 5 mA for signalling circuit |
| Minimum switching voltage | 17 V for signalling circuit |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact |
| Operating time | 95...130 ms closing; 20...35 ms opening |
| Maximum operating rate | 3600 cyc/h 60 °C |
| Inrush power in W | 22 W (at 20 °C) |
| Hold-in power consumption in W | 22 W at 20 °C |
| Insulation resistance | > 10 MOhm for signalling circuit |
| Connections - terminals | Control circuit: lugs-ring terminals - external diameter: 8 mm; Power circuit: lugs-ring terminals - external diameter: 17 mm; Power circuit: bars 1 - busbar cross section: 3 x 16 mm |
| Tightening torque | Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver flat Ø 6 mm M3.5; Control circuit: 1.2 N.m - on lugs-ring terminals - with screwdriver Philips No 2 M3.5; Power circuit: 5 N.m - on lugs-ring terminals hexagonal screw head 10 mm M6; Power circuit: 5 N.m - on lugs-ring terminals - with screwdriver flat Ø 8 mm M6; Power circuit: 5 N.m - on bars - with screwdriver flat Ø 8 mm M6; Power circuit: 5 N.m - on bars hexagonal screw head 10 mm M6 |
| Mounting support | Rail; Plate |
| Electrical durability | 1.5 Mcycles 80 A AC-3 at Ue |
| Mechanical durability | 10 Mcycles |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Operating altitude | 0...3000 m |
| Compatibility code | LC1D |
| Standards | EN/IEC 60947-4-1; EN/IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-1:Clause 30.2; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ |
| Product certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Climatic withstand | conforming to IACS E10 |
| Ambient air temperature for storage | -60…80 °C |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Height | 127 mm |
| Width | 85 mm |
| Depth | 186 mm |
| Net weight | 2.59 kg |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor open (8 Gn for 11 ms) |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys; TeSys Deca |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load; Motor control |
| Utilisation category | AC-3; AC-1; AC-3e |
| Poles description | 3P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 125 A (at |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 10.700 cm |
| Package 1 Width | 16.000 cm |
| Package 1 Length | 22.000 cm |
| Package 1 Weight | 2.521 kg |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 2 |
| Package 2 Height | 15.000 cm |
| Package 2 Width | 30.000 cm |
| Package 2 Length | 40.000 cm |
| Package 2 Weight | 5.421 kg |
TeSys LC1D power contactor. 3 pole, 3 NO contacts. Additional auxiliary contacts - 1 NO + 1 NC contact, rated operational power at AC-3, 400 V 37 kW, rated operational current Ie at AC-3, 400 V 80 A, coil 110 V DC. Dimensions (WxHxD) 85x127x186 mm, weight 2.59 kg. Category AC-1, AC-3. Coil - wide range, without integrated circuit module. Quick and easy setup. Safe and durable power connection with Everlink and spring terminals. Suitable for safety applications due to mechanically coupled contacts and mirror contacts.