| Complementary |
| Motor power kW | 22 kW at 220/230 V AC 50/60 Hz (AC-3); 37 kW at 380/400 V AC 50/60 Hz (AC-3); 45 kW at 415/440 V AC 50/60 Hz (AC-3); 55 kW at 500 V AC 50/60 Hz (AC-3); 45 kW at 660/690 V AC 50/60 Hz (AC-3); 45 kW at 1000 V AC 50/60 Hz (AC-3) |
| Compatibility code | LC1D |
| Pole contact composition | 4 NO |
| Protective cover | Without |
| [Ith] conventional free air thermal current | 125 A (at 60 °C) for power circuit |
| Irms rated making capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| Rated breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Icw] rated short-time withstand current | 640 A 40 °C - 10 s for power circuit; 990 A 40 °C - 1 s for power circuit; 135 A 40 °C - 10 min for power circuit; 320 A 40 °C - 1 min for power circuit |
| Associated fuse rating | 200 A gG at |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Power dissipation per pole | 12.5 W AC-1 |
| [Ui] rated insulation voltage | Power circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Power circuit: 1000 V conforming to IEC 60947-4-1 |
| Overvoltage category | III |
| Pollution degree | 3 |
| [Uimp] rated impulse withstand voltage | 8 kV conforming to IEC 60947 |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1 |
| Mechanical durability | 10 Mcycles |
| Electrical durability | 0.8 Mcycles 125 A AC-1 at Ue |
| Control circuit type | AC at 50 Hz |
| Coil technology | Without built-in suppressor module |
| Control circuit voltage limits | 0.3...0.6 Uc (-40…70 °C):drop-out AC 50 Hz; 0.85...1.1 Uc (-40…55 °C):operational AC 50 Hz; 1...1.1 Uc (55…70 °C):operational AC 50 Hz |
| Inrush power in VA | 200 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Hold-in power consumption in VA | 20 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Heat dissipation | 6…10 W at 50 Hz |
| Operating time | 20...35 ms closing; 6...20 ms opening |
| Maximum operating rate | 3600 cyc/h at 60 °C |
| Tightening torque | Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver flat Ø 6 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver Philips No 2; Power circuit: 12 N.m - on connector - with screwdriver flat Ø 6 to Ø 8 mm; Power circuit: 12 N.m - on connector hexagonal screw head 4 mm; Control circuit: 1.2 N.m - on screw clamp terminals - with screwdriver pozidriv No 2 |
| Mounting support | Plate; Rail |
| Contractual warranty |
| Warranty (in months) | 18 |
| Environment |
| Standards | EN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2 |
| Product certifications | CCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC |
| IP degree of protection | IP20 front face conforming to IEC 60529 |
| Protective treatment | TH conforming to IEC 60068-2-30 |
| Climatic withstand | conforming to IACS E10 exposure to damp heat |
| Permissible ambient air temperature around the device | -40…60 °C; 60…70 °C with derating |
| Operating altitude | 0...3000 m |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Mechanical robustness | Vibrations contactor open (2 Gn, 5...300 Hz) ; Shocks contactor open (8 Gn for 11 ms) ; Vibrations contactor closed (3 Gn, 5...300 Hz) ; Shocks contactor closed (10 Gn for 11 ms) |
| Height | 127 mm |
| Width | 96 mm |
| Depth | 125 mm |
| Net weight | 1.76 kg |
| Logistical informations |
| Country of origin | CZ |
| Main |
| Range | TeSys |
| Range of product | TeSys Deca Advanced |
| Product or component type | Contactor |
| Device short name | LC1D |
| Contactor application | Resistive load |
| Utilisation category | AC-1 |
| Poles description | 4P |
| [Ue] rated operational voltage | Power circuit: |
| [Ie] rated operational current | 125 A (at |
| [Uc] control circuit voltage | 230 V AC 50 Hz |
| Packing Units |
| Unit Type of Package 1 | PCE |
| Number of Units in Package 1 | 1 |
| Package 1 Height | 11.0 cm |
| Package 1 Width | 13.5 cm |
| Package 1 Length | 15.5 cm |
| Package 1 Weight | 1.705 kg |
| Unit Type of Package 2 | S02 |
| Number of Units in Package 2 | 5 |
| Package 2 Height | 15.0 cm |
| Package 2 Width | 30.0 cm |
| Package 2 Length | 40.0 cm |
| Package 2 Weight | 8.848 kg |
4-pole (4S) TeSys D contactor for AC-1 load applications up to 125 A/690 V. It has a 230 V 50 Hz coil, power connections via screw terminals and control via screw terminals. Without built-in auxiliary switches, auxiliary switch blocks can be added for side and front mounting (to be ordered separately). With high operating speeds of up to 3600 cycles/hour, it ensures high reliability and durability. It has multiple standards (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliance (RoHs/Reach).