Schneider Electric LC1D65AU7, EAN: 3389119409032

Schneider Electric LC1D65AU7 contactor 3p 65A

Industrial Material > Industrial relays and contactors > Contactors

Schneider Electric LC1D65AU7 contactor 3p 65A

Lieske Part No. 1235878
Mfg Part No LC1D65AU7
EAN-Code 3389119409032
Manufacturer Schneider Electric
Here only 305,56 EUR
363,62 EUR incl. VAT

Further information for Schneider Electric LC1D65AU7 contactor 3p 65A

Complementary
Motor power kW18.5 kW at 220/230 V AC 50/60 Hz (AC-3); 30 kW at 380/400 V AC 50/60 Hz (AC-3); 37 kW at 500 V AC 50/60 Hz (AC-3); 37 kW at 660/690 V AC 50/60 Hz (AC-3); 18.5 kW at 220/230 V AC 50/60 Hz (AC-3e); 30 kW at 380/400 V AC 50/60 Hz (AC-3e); 37 kW at 500 V AC 50/60 Hz (AC-3e); 37 kW at 660/690 V AC 50/60 Hz (AC-3e); 11 kW at 400 V AC 50/60 Hz (AC-4)
Motor power hp40 hp at 460/480 V AC 50/60 Hz for 3 phases motors; 5 hp at 115 V AC 50/60 Hz for 1 phase motors; 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors; 20 hp at 200/208 V AC 50/60 Hz for 3 phases motors; 20 hp at 230/240 V AC 50/60 Hz for 3 phases motors; 50 hp at 575/600 V AC 50/60 Hz for 3 phases motors
Compatibility codeLC1D
Pole contact composition3 NO
Protective coverWith
[Ith] conventional free air thermal current10 A (at 60 °C) for signalling circuit; 80 A (at 60 °C) for power circuit
Irms rated making capacity140 A AC for signalling circuit conforming to IEC 60947-5-1; 250 A DC for signalling circuit conforming to IEC 60947-5-1; 1000 A at 440 V for power circuit conforming to IEC 60947
Rated breaking capacity1000 A at 440 V for power circuit conforming to IEC 60947
[Icw] rated short-time withstand current640 A 40 °C - 10 s for power circuit; 900 A 40 °C - 1 s for power circuit; 110 A 40 °C - 10 min for power circuit; 260 A 40 °C - 1 min for power circuit; 100 A - 1 s for signalling circuit; 120 A - 500 ms for signalling circuit; 140 A - 100 ms for signalling circuit
Associated fuse rating10 A gG for signalling circuit conforming to IEC 60947-5-1; 125 A gG at
Average impedance1.5 mOhm - Ith 80 A 50 Hz for power circuit
Power dissipation per pole9.6 W AC-1; 6.3 W AC-3; 6.3 W AC-3e
[Ui] rated insulation voltagePower circuit: 600 V CSA certified; Power circuit: 600 V UL certified; Signalling circuit: 690 V conforming to IEC 60947-1; Signalling circuit: 600 V CSA certified; Signalling circuit: 600 V UL certified; Power circuit: 690 V conforming to IEC 60947-4-1
Overvoltage categoryIII
Pollution degree3
[Uimp] rated impulse withstand voltage6 kV conforming to IEC 60947
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1; B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
Mechanical durability6 Mcycles
Electrical durability1.4 Mcycles 80 A AC-1 at Ue
Control circuit typeAC at 50/60 Hz
Coil technologyWithout built-in suppressor module
Control circuit voltage limits0.3...0.6 Uc (-40…70 °C):drop-out AC 50/60 Hz; 0.8...1.1 Uc (-40…60 °C):operational AC 50 Hz; 0.85...1.1 Uc (-40…60 °C):operational AC 60 Hz; 1...1.1 Uc (60…70 °C):operational AC 50/60 Hz
Inrush power in VA140 VA 60 Hz cos phi 0.75 (at 20 °C); 160 VA 50 Hz cos phi 0.75 (at 20 °C)
Hold-in power consumption in VA13 VA 60 Hz cos phi 0.3 (at 20 °C); 15 VA 50 Hz cos phi 0.3 (at 20 °C)
Heat dissipation4…5 W at 50/60 Hz
Operating time4...19 ms opening; 12...26 ms closing
Maximum operating rate3600 cyc/h at 60 °C
Auxiliary contact composition1 NO + 1 NC
Auxiliary contacts typetype mechanically linked 1 NO + 1 NC conforming to IEC 60947-5-1; type mirror contact 1 NC conforming to IEC 60947-4-1
Signalling circuit frequency25...400 Hz
Minimum switching voltage17 V for signalling circuit
Minimum switching current5 mA for signalling circuit
Insulation resistance> 10 MOhm for signalling circuit
Non-overlap time1.5 ms on de-energisation between NC and NO contact; 1.5 ms on energisation between NC and NO contact
Mounting supportRail; Plate
Contractual warranty
Warranty (in months)18
Environment
StandardsEN 60947-4-1; EN 60947-5-1; IEC 60947-4-1; IEC 60947-5-1; CSA C22.2 No 14; UL 60947-4-1; IEC 60335-2-40:Annex JJ; UL 60335-2-40:Annex JJ; IEC 60335-1:Clause 30.2
Product certificationsCCC; UL; CB Scheme; CSA; CE; UKCA; Marine; EAC
IP degree of protectionIP20 front face conforming to IEC 60529
Protective treatmentTH conforming to IEC 60068-2-30
Climatic withstandconforming to IACS E10 exposure to damp heat; conforming to IEC 60947-1 Annex Q category D exposure to damp heat
Permissible ambient air temperature around the device-40…60 °C; 60…70 °C with derating
Operating altitude0...3000 m
Fire resistance850 °C conforming to IEC 60695-2-1
Mechanical robustnessVibrations contactor open (2 Gn, 5...300 Hz) ; Vibrations contactor closed (4 Gn, 5...300 Hz) ; Shocks contactor closed (15 Gn for 11 ms) ; Shocks contactor open (10 Gn for 11 ms)
Height122 mm
Width55 mm
Depth120 mm
Net weight0.86 kg
Logistical informations
Country of originID
Main
RangeTeSys; TeSys Deca
Range of productTeSys Deca Advanced
Product or component typeContactor
Device short nameLC1D
Contactor applicationMotor control; Resistive load
Utilisation categoryAC-3; AC-3e; AC-1; AC-4
Poles description3P
[Ue] rated operational voltagePower circuit:
[Ie] rated operational current80 A (at
[Uc] control circuit voltage240 V AC 50/60 Hz
Packing Units
Unit Type of Package 1PCE
Number of Units in Package 11
Package 1 Height6.2 cm
Package 1 Width13.7 cm
Package 1 Length15.2 cm
Package 1 Weight953.0 g
Unit Type of Package 2S02
Number of Units in Package 210
Package 2 Height15.0 cm
Package 2 Width30.0 cm
Package 2 Length40.0 cm
Package 2 Weight9.985 kg
Unit Type of Package 3P06
Number of Units in Package 3160
Package 3 Height77.0 cm
Package 3 Width80.0 cm
Package 3 Length60.0 cm
Package 3 Weight168.26 kg
The LC1D65AU7 contactor from the TeSys Deca series by Schneider Electric is a 3-pole contactor for motor control and operation with resistive loads. It features three main contacts (3P) and integrated auxiliary contacts in the configuration of 1 NO + 1 NC. The control circuit voltage is 240 V AC at 50/60 Hz, with operating voltage variations between 0.8 and 1.1 times the rated voltage (at -40…60 °C). The device is designed for usage categories AC-1, AC-3, AC-3e, and AC-4, with a rated operational power of 30 kW at AC-3 and 400 V AC. The rated operational current Ie is 65 A (at AC-3, 400 V), with technical data also specified for other voltage levels such as 220/230 V, 500 V, and 660/690 V. The maximum operating rate is 3600 switching operations per hour.

Applications
This contactor is designed for controlling electric motors in industrial plants, particularly in applications with medium to high power. It is suitable for drives in the range of 18.5 kW to 37 kW depending on voltage level and usage category. The AC-4 category allows use under heavy starting conditions, such as those found in crane systems or conveyor belts. Certification according to EN/ISO 13849-1 with a safety level B10d of 1369863 cycles at rated load makes it suitable for safety applications, especially when mechanically interlocked contacts and mirror contacts are used to prevent false actuation.

Functions and Equipment in Detail
The device features a safety cover ensuring secure operation. Current connections are made via Everlink and spring terminals, ensuring a secure and long-lasting connection. The coil is designed without an integrated wiring module, enabling flexible installation. The auxiliary contacts are non-delayed and can be used for signal input and output. The mechanical life is 6 million switching cycles, while the electrical life at AC-1 and 80 A is 1.4 million switching cycles.

Technology Explained Simply
The rated insulation voltage is 690 V for the power circuit according to IEC 60947-4-1 and 600 V for the signal circuit according to IEC 60947-1. The overvoltage category III and pollution degree 3 indicate a robust construction suitable for industrial environments. The rated impulse withstand voltage is 6 kV, ensuring reliability during transient voltage surges. The power loss per pole is 9.6 W at AC-1 and 6.3 W at AC-3 and AC-3e, describing the thermal load during operation. The heat dissipation is between 4 and 5 W at 50/60 Hz.

Compatibility and Accessories
The contactor is compatible with various accessories, including auxiliary switch blocks such as LADN13 (1NO3NC), LADN20 (2NO), LADN31 (3NO1NC), and LADN40 (4NO), as well as time blocks such as LADR0 (0.10–3.00 s) and LADR2 (1–30.00 s). Mechanical interlocks such as LAD4CM and interlocking blocks such as LAD6K10M enable safe combination with other contactors. For control circuit power supply, time modules such as LA4-DT0U (0.1–2 s) and LA4-DT2U (1.5–30 s) are also available. Combination with motor protection circuit breakers such as GV3P65 (3p, 48–65 A) enables integrated protection functions.

Mounting and Installation
Mounting is on a 35 mm DIN rail according to EN 50022. Dimensions are 55 mm (width) × 122 mm (height) × 120 mm (depth). The terminals are designed for cross-sections from 1 to 25 mm², with main contacts equipped with Everlink technology and spring terminals. Mounting torques are 5 N·m (44 lb-in) for main contacts and 1 N·m (9 lb-in) for auxiliary contacts. Installation requires no additional tools, as the terminals operate with a click system.

Operational Advantages
The contactor offers high operational safety through mechanically interlocked contacts and mirror contacts, preventing false actuation. The durable construction with a mechanical life of 6 million cycles and an electrical life of 1.4 million cycles at AC-1 ensures long service life. The quick and easy setup via the Everlink system reduces installation time. Certifications according to GOST, UL, CSA, and CCC ensure compliance with international standards. The operating time is 4–19 ms for opening and 12–26 ms for closing, enabling fast response during operation.
This is an offer of:

Lieske Elektronik e.K.

Reutener Str. 10
79279 Vörstetten

https://industry-electronics.com
Tel. 07666/88499-0
Fax. 07666/88499-111

Diesen Artikel finden Sie unter:
industry-electronics.com/artikel/1235878
qrcode für Schneider Electric LC1D65AU7 contactor 3p 65A